Output Reactor - Siemens SINAMICS G120 Original Instructions Manual

Sinamics g120 inverter with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents
Description
3.4 System components for the Power Modules
Line reactors for PM240-2
Power Module 6SL321⃞-...
FSA
Line reactors for PM330
Power Module 6SL3310-...
GX
3.4.3

Output reactor

Output reactors reduce the voltage stress on the
motor windings. Further, they reduce the inverter load
as a result of capacitive recharging currents in the
cables. An output reactor is required for motor cables
longer than 50 m, shielded or 100 m unshielded.
The output reactors are designed for pulse
frequencies of 4 kHz.
Adjacent examples of output reactors.
Power Module PM330 requirements:
An output reactor is required for a motor cable length longer than
● 100 m shielded
● 200 m unshielded
The maximum pulse frequency with an output reactor is 4 kHz.
34
...1PE11-8⃞L0, ...1PE12-3⃞L0,
...1PE13-2⃞L0
...1PE14-3⃞L0, ...1PE16-1⃞L0,
...1PE18-0⃞L0
...1PE33-0AA0
...1PE33-7AA0
Power
0.55 kW ... 1.1 kW
1.5 kW ... 3.0 kW
Power
160 kW
200 kW
for PM240
FSA, FSB
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Line reactor
6SL3203-0CE13-2AA0
6SL3203-0CE21-0AA0
Line reactor
6SL3000-0CE33-3AA0
6SL3000-0CE35-1AA0
for FSGX