Capacitive Load in Power Supply Network

All CL200 modules contain capacitive interference suppression measures
installed between the power supply lines and protective earth. This fact must
be taken into account when employing an earth-leakage monitoring device.
Module
24 V ³ PE
NT200
ZE200
ZE200A
ZE200M
ZE200AM
ZE201
ZE200-DP /
ZE200A–DP
E24V– (16-way)
E24V– (32-way)
E16/A8
E16/A16
A24V–/0.5A (16-way)
A24V–/0.5A (32-way)
A24V–/2A
AR/2A
E ana
E20 ana
A ana
A20 ana
A10 ana (4)
A10 ana (8)
R200
R200P
COM2–E
POS–SA1
POS–SA2
POS–LR1
POS–LR2
BM–ASI
DP–EA4
AG/S
RM2–DP12
0 V ³ PE
5 nF
100 nF
10 nF
10 nF
25 nF
25 nF
10 nF
20 nF
5 nF
10 nF
5 nF
10 nF
5 nF
15 nF
5 nF
15 nF
15 nF
15 nF
30 nF
30 nF
10 nF
15 nF
15 nF
5 nF
25 nF
25 nF
25 nF
25 nF
5 nF
5 nF
25 nF
25 nF
25 nF
25 nF
25 nF
25 nF
15 nF
15 nF
25 nF
25 nF
15 nF
15 nF
25 nF
25 nF
4.7 nF
4.7 nF
1070 072 145-102 (01.07) GB