BUFFER MEMORY
6.17

CH1 Digital Output Value (Un\G100, Un\G1700)

The A/D converted digital output value is set to store.
For information on the buffer memory for CH2 or later, refer to Section 6.1 (1) and Section
6.1 (3).
(1) Stored data
(a) Storage form
(b) Updating cycle (Refer to Section 4.2.1.)
POINT
Digital values are stored into the buffer memory in 16-bit signed binary form.
CH1 Digital output value
(Un\G100)
Figure 6.4 Storage data of CH1 Digital output value (Un\G100)
• Averaging processing executed
• Averaging processing unexecuted
of channels to be used
When reading the digital output values, use A/D conversion completed flag (XE)
or CH1 A/D conversion completed flag (Un\G113) as an interlock.
6.17 CH1 Digital Output Value (Un\G100, Un\G1700)
b15
b14 b13b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Data part
Sign bit
1: Negative value
0: Positive value
Averaging processing cycle set
Sampling processing time (number
500 s)
1
2
3
4
5
6
7
8
6
- 20