Miscellaneous Alarms - GE PQMII Instruction Manual

Power quality meter
Table of Contents
5.5.9

Miscellaneous Alarms

MISCELLANEOUS
5–50
PICKUP TIME: The relay assigned in the
clock time equals or exceeds the time specified in this setpoint. Follow the example
below to set the
PICKUP TIME
PICKUP TIME
1 :00:00 am
2
USE THE VALUE
KEYS TO SELECT
VALUE
THE UNDERLINED
QUANTITIES
DROPOUT TIME: The relay assigned in the
PQMII clock time equals or exceeds the time specified in this setpoint. Follow the
example above to set the
PATH: SETPOINTS
S4 ALARMS/CONTROL
[ ]
SERIAL COM1 FAILURE
ALARM DELAY: OFF s
SERIAL COM2 FAILURE
MESSAGE
ALARM DELAY: OFF s
CLOCK NOT SET ALARM:
MESSAGE
ON
DATA LOG 1 MEMORY
MESSAGE
FULL LEVEL: OFF %
DATA LOG 2 MEMORY
MESSAGE
FULL LEVEL: OFF %
SERIAL COM1(2) FAILURE ALARM DELAY: If loss of communications to the external
master is required to activate the alarm relay, select a time delay in the range of 5 to
60 seconds. In this case, an absence of communication polling on the RS485
communication port for the selected time delay will generate the alarm condition.
Disable this alarm if communications is not used or is not considered critical. This
alarm is not available on the front RS232 port.
CLOCK NOT SET ALARM: The software clock in the PQMII will remain running for a
period of approximately thirty days after power has been removed from the PQMII
power supply inputs. Selecting "On" for this setpoint causes a Clock Not Set Alarm to
occur at power-up for power losses greater than thirty days. Once the alarm occurs,
the
S1 PQMII SETUP
CLOCK
DATA LOG 1(2) MEMORY FULL LEVEL: These messages can be used to configure
alarms to indicate that the Data Logger memory is almost full. Separate alarms are
provided for each log. When the log memory reaches the level programmed in this
message a Data Log 1(2) Alarm will occur.
TIME RELAY
.
MESSAGE
MESSAGE
PICKUP TIME
03:0 :00 am
0
NEW SETPOINT
STORED
TIME RELAY
.
DROPOUT TIME
MISCELLANEOUS
setting must be stored to reset the alarm.
SET TIME & DATE
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
setpoint energizes when the PQMII
PICKUP TIME
03:35:0
0
am
MESSAGE
ENTER
PICKUP TIME
03:35:55 am
setpoint de-energizes when the
Range: 5 to 60 s in steps of 1 or OFF
Range: 5 to 60 s in steps of 1 or OFF
Range: Off, On
Range: 50 to 100% in steps of 1 or OFF
Range: 50 to 100% in steps of 1 or OFF