For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents
Note 6: Overload characteristic of inverter and region setting are displayed on the monitor as follows;
Note 7: Past trip records are displayed in the following sequence: 1 (latest trip record)  2  3  4  5  6  7  8
Note 8: Parts replacement alarm is displayed based on the value calculated from the annual average ambient
Note 9: The cumulative operation time increments only when the machine is in operation.
Note 10: If there is no trip record, nerr is displayed.
Note 11: Of the items displayed on the monitor, the reference values of items expressed in percent are listed below.
Note 12: Status monitor of * mark is displayed by  to  and  setting. The left side character
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
c -xx
: aul = 1 (Constant torque characteristic) is selected.
v -xx
: aul = 2 (Variable torque characteristic) is selected.
x- eu : Setup menu is selected to eu .
x- as : Setup menu is selected to asia .
x- us : Setup menu is selected to usa .
x- jp : Setup menu is selected to jp .
(oldest trip record). If no trip occurred in the past, the message "  " will be displayed. Details on
past trip record 1 to 8 can be displayed by pressing the center of the setting dial when past trip 1 to 8 is
displayed. Refer to section 8.2.2 for details.
temperature specified using  , the ON time of the inverter, the operating time of the motor and the
output current (load factor). Use this alarm as a guide only, since it is based on a rough estimation.
Output current:
The current monitored is displayed in percentage. The value indicated on the
nameplate is 100%. The unit can be switched to A (amperes).
Input voltage:
The voltage displayed is the voltage determined by converting the voltage
measured in the DC section into an AC voltage. The reference value (100%
value) is 200V (240V class), 400V (500V class). The unit can be switched to V
(volts).
Output voltage:
The voltage displayed is the output command voltage. The reference value
(100% value) is 200V (240V class), 400V (500V class). This unit can be
switched to V (volts).
Depending on the PWM carrier frequency ( f300 ) setting and so on, the
Load factor of inverter:
actual rated current may become smaller than the rated output current
indicated on the nameplate. With the actual rated current at that time (after a
reduction) as 100%, the proportion of the load current to the rated current is
indicated in percent. The load factor is also used to calculate the conditions
for overload trip (  ).
is as following table by each parameter setting number.
H-9
E6581611
8