Toshiba VF-S15 Instruction Manual page 101

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents
5) Overload characteristic selection aul
Overload characteristic of inverter can be selected to 150%-60s or 120%-60s.
[Parameters settings]
Title
aul
● Regarding to characteristic for aul=1 setting, refer to section 5.6.3).
Note 1) In case of aul=2 setting, be sure to install the input AC reactor (ACL) between power supply and inverter.
Note 2) In case of aul=2 setting in three phase 500V-4.0kW model, be sure to press the grounding capacitor
5
 aul=2 (Variable torque characteristic), f631=0 (120%-60s)
Inverter overload
time [s]
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Function
Overload characteristic selection
switch and connect the grounding capacitors to the ground.
60
0
105%
Inverter overload protection characteristic
Adjustment range
0: -
1: Constant torque
characteristic(150%-60s)
2: Variable torque
characteristic(120%-60s)
Current
[%]
106
110
115
120
140
165
Monitored output current [%]
120%
100%: Inverter rated output current
E-14
E6581611
Default setting
0
Inverter overload time [s]
(Outline data)
900
180
90
60
2
0.5