8 Configuration

3 Mount the front panel to the indoor unit.
7.7.2

To close the indoor unit

1 Close the switch box cover.
2 Reinstall the top plate.
3 Reinstall the front panel.
NOTICE
When closing the indoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
8
Configuration
8.1

Overview: Configuration

This chapter describes what you have to do and know to configure
the system after it is installed.
Why
If you do NOT configure the system correctly, it might NOT work as
expected. The configuration influences the following:
▪ The calculations of the software
▪ What you can see on and do with the user interface
How
You can configure the system using two different methods.
Method
Configuring via the
First time – Quick wizard. When you turn
user interface
ON the user interface for the first time (via
the indoor unit), a quick wizard starts to help
you configure the system.
Afterwards. If necessary, you can make
changes to the configuration afterwards.
Configuring via the
You can prepare the configuration off-site on
PC configurator
PC and afterwards upload the configuration
to the system with the PC configurator.
See also:
the switch box" on
INFORMATION
When the installer settings are changed, the user interface
will request to confirm. When confirmed, the screen will
shortly turn OFF and "busy" will be displayed for several
seconds.
Installer reference guide
34
Description
"8.1.1 To connect the PC cable to
page 34.
Accessing settings – Legend for tables
You can access the installer settings using two different methods.
However, NOT all settings are accessible via both methods. If so,
the corresponding table columns in this chapter are set to N/A (not
applicable).
Method
Accessing settings via the breadcrumb in the
menu structure.
Accessing settings via the code in the
overview settings.
See also:
"To access the installer settings" on page 34
"8.5 Menu structure: Overview installer settings" on page 54
8.1.1

To connect the PC cable to the switch box

Prerequisite: The EKPCCAB kit is required.
1 Connect the cable with USB connection to your PC.
2 Connect the plug of the cable to X10A on A1P of the switch box
of the indoor unit.
A1P
X10A
X5M
X2M
3 Pay special attention to the position of the plug!
2
8.1.2

To access the most used commands

To access the installer settings
1 Set the user permission level to Installer.
2 Go to [A]:
> Installer settings.
To access the overview settings
1 Set the user permission level to Installer.
2 Go to [A.8]:
> Installer settings > Overview settings.
To set the user permission level to Installer
1 Set the user permission level to Adv. end user.
2 Go to [6.4]:
> Information > User permission level.
Column in tables
#
Code
3
4
5
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1D – 2016.02