Output Type (B3) - Panasonic EBL512 G3 User Manual

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents
Panasonic Eco Solutions Nordic AB
MEW01603 Rev: -
5.3
Escape
menu

Output type (B3)

Outputs of the same type can be collectively disabled via menu B3.
Cont. from
, page 7.
B1 Zone or Zone / Address
Press (  ) two times.
B3 Output type
Press ( ).
Disable output type
NOTE! To Re-enable, see ➓ below.
By default is type Control outputs in control unit 00
Press the Soft key "Change type of disablement" to toggle
between:
Control outputs
Ventilation outputs
Extinguishing outputs
Interlocking outputs
Press ( ) and type the control unit number if not All outputs shall
be disabled. Press ( ).
A successful disablement is indicated by a beep and a
shown in the Re-enable list.
A not successful disablement is indicated by another beep and a
Re-enable
➓ Press the Soft key
Disable output type
Re-enable list.
Press (  ) to highlight the output type that shall be Re-enabled.
⓫ Press ( ). A successful Re-enablement is indicated by a beep and it
will also disappear from the Re-enable list
⓬ To leave a menu press ESC.
To leave the menu system press the Soft key "Escape menu".
EBL512 G3 version 2.0.x, Daily user's manual
to toggle between:
"
"
10
All
selected.
It will also be
"√".
"X".
.