Panasonic EBL128 Quick Start Manual
Hide thumbs Also See for EBL128:

Quick Links

EBL128, an intelligent analog addressable fire alarm system for up to 255 addresses
Auto generation of the Site Specific Data for easier c.i.e. programming
Analog addressable system
EBL128 is an intelligent, analog and
addressable
Control and Indicating Equip-
ment for fire detection and fire alarm systems
, which conforms to the EN54-2
for buildings
and the EN54-4 standards. It meets the most
stringent requirements in order to secure real
fire alarms and to reduce nuisance alarms.
Features / functions
A user-friendly PC software EBLWin is
used to create, edit, download and upload
(backup) the Site Specific Data (SSD).
An SSD Auto generation function is
included in EBLWin.
connected to EBL128 can be identified and
the SSD can be auto generated with default
settings and be edited before the download.
Some other features / functions:
Compensation for contamination, i.e.
analog smoke detectors have constant
sensitivity in spite of any contamination.
A Service signal will be given when a
detector has to be replaced.
Advanced alarm algorithms are used
to filter the nuisance alarms from the
real fire alarms and one algorithm is
used for detection of smouldering fires.
User related functions, e.g. Test mode,
Disablements, Alert Annunciation, Fire
door closing, Interlocking combinations
of outputs & inputs, Time channels, Co-
incidence alarm, User definable text
message for each alarm point, etc.
Programmable inputs and outputs. In
the c.i.e. and/or via I/O units on the
COM loop. A large number of trigger
conditions are available.
Panasonic Eco Solutions Nordic AB
Jungmansgatan 12, SE-211 19 Malmö, Sweden
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99
E-mail: [email protected] • Internet: http://pesn.panasonic.se
Fire alarm system
The units that are
EBL128, V2.0
4550
Outputs for routing equipment. Fire
alarm, Fault and Power supply.
Socket for an optional RS485 trans-
ceiver component, i.e. an interface for
up to eight Display Units (Ext. Fire
Brigade Panel, Ext. Presentation Unit
and/or Alert Annunciation Unit).
Interface (RS232) for a PC (EBLWin)
Interface (RS232) and power supply for
Web-server 1598.
Optional RS485 transceiver 4552, provides
an interface for up to eight Display Units.
Up to four optional expansion boards 4580,
4581 and 4583, mounted in an Exp. board
holder (incl. connection cable) 4551.
Up to 255 addresses
The EBL128 c.i.e. has one COM loop for
connection of the loop units (address 001-
255). Each loop unit uses one address.
Some loop units that can be connected:
Analog heat & smoke detectors
Addressable manual call points (with
short circuit isolator)
Addressable short circuit isolators
Addressable input and output units (to
which e.g. conventional detectors and
manual call points can be connected)
Addressable sirens (with short circuit
isolator) & sounder bases
Addressable external power supply units
Miscellaneous
The cabinet has a space for two sealed
Lead-Acid batteries (2x12 V, 16-18 Ah).
EBL128 is intended for indoor use and in
dry premises.
loading

Summary of Contents for Panasonic EBL128

  • Page 1 Fire alarm system EBL128, V2.0 4550  EBL128, an intelligent analog addressable fire alarm system for up to 255 addresses  Auto generation of the Site Specific Data for easier c.i.e. programming Analog addressable system  Outputs for routing equipment. Fire alarm, Fault and Power supply.
  • Page 2 The 4580 board can be used to connect conventional detectors and manual call points to EBL128. End-of-line capacitor (470 nF) in the last alarm point on each zone line. More information is available in the EBL128 Planning Instructions & Operating Instructions.