Checking Of Device And Installation Conditions - Daikin RXYQ5PY1 Service Manual

R-410a heat pump 50hz/60hz cooling only 50hz
Table of Contents
SiEN34-705

2.10 Checking of Device and Installation Conditions

Be sure to check the followings.
For those doing electrical work
1. Make sure there is no faulty transmission wiring or loosen a nut.
2. Make sure there is no faulty power wiring or loosen a nut.
3. Has the insulation of the main power circuit deteriorated?
For those doing pipe work
1. Make sure piping size is correct.
2. Make sure insulation work is done.
3. Make sure there is no faulty refrigerant piping.
Installation Manual
See "2-7-4 Transmission Wiring Connection Procedure".
See "2-7-5 Power Wiring Connection Procedure".
Measure the insulation and check the insulation is above regular value in accordance with
relevant local and national regulations.
See "2-6-1 Selection of piping material and Refrigerant branching kit".
See "2-9 Pipe Insulation".
See "2-6 Refrigerant Piping".
Heat Pump 60Hz (RXYQ5~54P)
297
Table of Contents
loading

Table of Contents