Mitsubishi Electric FR-F720-0.75K to 110K Instruction Manual page 170

Table of Contents
(1) Selection of analog input selection
⋅ For the terminals 2, 4 used for analog input, voltage input (0 to 5V, 0 to 10V) or current input (4 to 20mA) can be
selected.
Change parameters (Pr.73, Pr.267) and a voltage/current input switch (switch 1, 2) to change input specifications.
Voltage/current
input switch
4
2
Switch 1
Switch 2
⋅ Rated specifications of terminal 2 and 4 change according to the voltage/current input switch setting.
Voltage input:
Input resistance 10kΩ ± 1kΩ, Maximum permissible voltage 20VDC
Current input:
Input resistance 245Ω ± 5Ω, Maximum permissible current 30mA
CAUTION
⋅ Set Pr.73, Pr.267, and a voltage/current input switch correctly, then input an analog signal in accordance with the
setting. Incorrect setting as in the table below could cause component damage. Incorrect settings other than
below can cause abnormal operation.
Setting Causing Component Damage
Switch setting
Terminal input
ON
Voltage input
(Current input)
OFF
Current input
(Voltage input)
Switch 1:Terminal 4 input
ON: Current input (initial status)
OFF: Voltage input
Switch 2: Terminal 2 input
ON: Current input
OFF: Voltage input (initial status)
This could cause component damage to the analog signal output circuit of signal
output devices. (electrical load in the analog signal output circuit of signal output
devices increases)
This could cause component damage of the inverter signal input circuit. (output
power in the analog signal output circuit of signal output devices increases)
Frequency setting by analog input (terminal 1, 2, 4)
Operation
4
161