INVERTER
INSTRUCTION MANUAL (BASIC)
FR-F740-00023 to 12120-EC
Thank you for choosing this Mitsubishi Inverter.
This Instruction Manual (basic) is intended for users who "just want to run the inverter".
If you are going to utilize functions and performance, refer to the Instruction Manual (applied) [IB-0600193ENG].
Please read the provided CD-ROM for the instruction manual (applied).
1
PRODUCT CHECKING AND PARTS IDENTIFICATION.............................. 1
2
INSTALLATION AND WIRING ...................................................................... 2
2.1
Peripheral devices .....................................................................................................3
2.2
Method of removal and reinstallation of the front cover ............................................4
2.3
Installation of the inverter and instructions ................................................................6
2.4
Wiring.........................................................................................................................7
2.5
Power-off and magnetic contactor (MC)..................................................................24
2.6
Precautions for use of the inverter...........................................................................25
3
DRIVE THE MOTOR .................................................................................... 27
3.1
Step of operation .....................................................................................................27
3.2
Operation panel (FR-DU07) ....................................................................................28
3.3
Overheat protection of the motor by the inverter (Pr. 9)..........................................33
3.4
Start/stop from the operation panel (PU operation mode) ......................................34
3.5
Make a start and stop with terminals (external operation) ......................................42
4
ADJUSTMENT ............................................................................................. 50
4.1
Simple mode parameter list.....................................................................................50
4.2
Increase the starting torque (Pr. 0)..........................................................................51
4.3
Limit the maximum and minimum output frequency (Pr. 1, Pr. 2)...........................52
4.4
When the rated motor frequency is 60Hz (Pr. 3).....................................................53
4.5
Change acceleration and deceleration time (Pr. 7, Pr. 8) .......................................54
4.6
Energy saving operation (Pr. 60).............................................................................55
4.7
Selection of the operation command and frequency command locations (Pr. 79) .57
4.8
Parameter clear, all parameter clear .......................................................................58
4.9
Parameter copy and parameter verification ............................................................59
4.10
Parameter list...........................................................................................................61
4.11
Extended parameters ..............................................................................................63
4.12
Parameter list...........................................................................................................64
5
TROUBLESHOOTING ................................................................................. 89
5.1
Reset method of protective function........................................................................89
5.2
List of alarm display .................................................................................................90
5.3
Causes and corrective actions ................................................................................91
5.4
Correspondences between digital and actual characters .....................................102
5.5
Check and clear of the alarm history.....................................................................103
5.6
Check first when you have troubles ......................................................................105
6
PRECAUTIONS FOR MAINTENANCE AND INSPECTION ..................... 108
6.1
Inspection item.......................................................................................................108
7
SPECIFICATIONS ..................................................................................... 116
7.1
Rating.....................................................................................................................116
7.2
Common specifications .........................................................................................117
7.3
Outline dimension drawings ..................................................................................119
7.4
Heatsink protrusion attachment procedure ...........................................................128
CONTENTS
700
1
2
3
4
5
6
7
Table of Contents
loading

Summary of Contents for Mitsubishi Electric F700

  • Page 1 INVERTER INSTRUCTION MANUAL (BASIC) FR-F740-00023 to 12120-EC Thank you for choosing this Mitsubishi Inverter. This Instruction Manual (basic) is intended for users who "just want to run the inverter". If you are going to utilize functions and performance, refer to the Instruction Manual (applied) [IB-0600193ENG]. Please read the provided CD-ROM for the instruction manual (applied).
  • Page 2 This instruction manual (basic) provides handling information and precautions for use of the equipment. Please forward this instruction manual (basic) to the end user. This section is specifically about safety matters CAUTION (2) Wiring Do not attempt to install, operate, maintain or inspect the inverter until you •...
  • Page 3: Table Of Contents

    — CONTENTS — PRODUCT CHECKING AND PARTS IDENTIFICATION INSTALLATION AND WIRING Peripheral devices...................... 3 Method of removal and reinstallation of the front cover..........4 Installation of the inverter and instructions..............6 Wiring.......................... 7 2.4.1 Terminal connection diagram ....................7 2.4.2 EMC filter...........................
  • Page 4 3.5.6 Change the frequency (50Hz) of the maximum value of potentiometer (at 20mA) ....49 ADJUSTMENT Simple mode parameter list ..................50 Increase the starting torque (Pr. 0) ................51 Limit the maximum and minimum output frequency (Pr. 1, Pr. 2) ......52 When the rated motor frequency is 60Hz (Pr.
  • Page 5 Appendix 3 Instructions for Compliance with the European Directives ....... 135 DU: Operation panel (FR-DU07) PU: Operation panel(FR-DU07) and parameter unit (FR-PU04/FR-PU07) Inverter: Mitsubishi inverter FR-F700 series FR-F700: Mitsubishi inverter FR-F700 series Pr.: Parameter Number PU operation: Operation using the PU (FR-DU07/FR-PU04/FR-PU07).
  • Page 6: Product Checking And Parts Identification

    1 PRODUCT CHECKING AND PARTS IDENTIFICATION Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that the product agrees with your order and the inverter is intact. •...
  • Page 7: Installation And Wiring

    2 INSTALLATION AND WIRING Three-phase AC power supply Inverter Use within the permissible power supply (FR-F700) specifications of the inverter. (Refer to page 116) The life of the inverter is influenced by ambient temperature. The ambient temperature should be as low as possible within the permissible range.
  • Page 8: Peripheral Devices

    Peripheral devices 2.1 Peripheral devices Check the motor capacity of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity. Refer to the following list and prepare appropriate peripheral devices: 400V class Input Side Magnetic Motor Breaker Selection *2,4 Contactor...
  • Page 9: Method Of Removal And Reinstallation Of The

    Method of removal and reinstallation of the front cover 2.2 Method of removal and reinstallation of the front cover •Removal of the operation panel 1) Loosen the two screws on the operation panel. 2) Push the left and right hooks of the operation panel (These screws cannot be removed.) and pull the operation panel toward you to remove.
  • Page 10: Front Cover

    Method of removal and reinstallation of the front cover FR-F740-00770-EC or more • Removal 1) Remove installation screws on 2) Loosen the installation 3) Pull the front cover 2 toward you to the front cover 1 to remove the screws of the front cover 2. remove by pushing an installation front cover 1.
  • Page 11: Installation Of The Inverter And Instructions

    Installation of the inverter and instructions 2.3 Installation of the inverter and instructions • Installation of the Inverter Installation on the enclosure CAUTION 00620 or less 00770 or more ⋅ When encasing multiple inverters, install them in parallel as a cooling measure. ⋅...
  • Page 12: Wiring

    Wiring 2.4 Wiring 2.4.1 Terminal connection diagram Resistor unit *1. DC reactor (FR-HEL) *6. A CN8 connector is Source logic Be sure to connect the DC reactor (Option) provided with the supplied with the 01800 or more. Brake unit Main circuit terminal When a DC reactor is connected 01800 or more.
  • Page 13: Emc Filter

    Wiring 2.4.2 EMC filter This inverter is equipped with a built-in EMC filter (capacitive filter) and common mode core. The EMC filter is effective for reduction of air-propagated noise on the input side of the inverter. The EMC filter is factory-set to enable (ON). To disable it, fit the EMC filter ON/OFF connector to the OFF position. The input side common mode core, built-in the FR-F740-01160 or less inverter, is always valid regardless of on/off of the EMC filter on/off connector.
  • Page 14: Specification Of Main Circuit Terminal

    Wiring 2.4.3 Specification of main circuit terminal Terminal Terminal Name Description Symbol R/L1, Connect to the commercial power supply. S/L2, AC power input Keep these terminals open when using the high power factor converter T/L3 (FR-HC, MT-HC) or power regeneration common converter (FR-CV). U, V, W Inverter output Connect a three-phase squirrel-cage motor.
  • Page 15 Wiring FR-F740-00310, 00380-EC FR-F740-00470, 00620-EC R1/L11 S1/L21 Screw size (M4) R1/L11 S1/L21 Screw size (M4) Charge lamp Jumper Charge lamp Jumper Screw size (M6) Jumper Screw size (M5) R/L1 S/L2 T/L3 Jumper R/L1 S/L2 T/L3 Power supply Motor Motor Power supply Screw size (M6) Screw size (M5) FR-F740-00770 to 01160-EC...
  • Page 16 Wiring FR-F740-03250 to 04810-EC FR-F740-05470 to 12120-EC R1/L11 S1/L21 Screw size (M4) R1/L11 S1/L21 Screw size (M4) Charge lamp Charge lamp Jumper Jumper Screw size (03250/03610: M10 04320/04810: M12) R/L1 S/L2 T/L3 N/- Screw size (M12) R/L1 S/L2 T/L3 N/- Screw size (M10) Power supply...
  • Page 17 Wiring (1) Cable sizes etc., of the main control circuit terminals and earth terminals Select the recommended cable size to ensure that a voltage drop will be 2% max. If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency.
  • Page 18 Wiring (2) Notes on earthing • Leakage currents flow in the inverter. To prevent an electric shock, the inverter and motor must be earthed. This inverter must be earthed. Earthing must conform to the requirements of national and local safety regulations and electrical codes.
  • Page 19 Wiring (5) When connecting the control circuit and the main circuit separately to the power supply (separate power) When the protected circuit is activated, opening of the electromagnetic contactor (MC) on the inverter power supply side results in power loss in the control circuit, disabling the alarm output signal retention.
  • Page 20 Wiring • FR-F740-00310 or more 1) Remove the upper screws. 2) Remove the lower screws. L21 Power supply 3) Pull the jumper toward you to terminal block remove. for the control circuit Power supply terminal block 4) Connect the separate power supply for the control circuit R/L1S/L2 T/L3 cable for the control circuit to the...
  • Page 21: Control Circuit Terminals

    Wiring 2.4.5 Control circuit terminals indicates that terminal functions can be selected using Pr. 178 to Pr. 196 (I/O terminal function selection) (Refer to Instruction Manual (applied).) (1) Input signals Terminal Terminal Rated Description Refer to Symbol Name Specifications Forward Turn on the STF signal to start forward When the STF and rotation start...
  • Page 22 Wiring Terminal Terminal Rated Description Refer to Symbol Name Specifications 10VDC Instruction When connecting the frequency setting potentiometer at an initial Permissible load Manual status, connect it to terminal 10. Frequency current 10mA (applied) Change the input specifications of terminal 2 when connecting it setting power 5VDC supply...
  • Page 23: Changing The Control Logic

    Wiring Terminal Terminal Rated Description Refer to Symbol Name Specifications Load impedance Instruction 200Ω to 450Ω Analog current Manual output Output signal 0 to (applied) Select one e.g. output frequency from 20mADC monitor items. Output item: Output signal 0 to The output signal is proportional to the Output frequency 10VDC...
  • Page 24 Wiring Sink logic and source logic ⋅ In sink logic, a signal switches on when a current flows from the corresponding signal input terminal. Terminal SD is common to the contact input signals. Terminal SE is common to the open collector output signals. ⋅...
  • Page 25: Wiring Of Control Circuit

    Wiring 2.4.7 Wiring of control circuit (1) Control circuit terminal layout CA SD PC STOP RES STF STR PC FU MRS JOG CS (2) Wiring method Loosen the terminal screw and insert the cable into the terminal. Screw Size: M3 Tightening Torque: 0.5N·m to 0.6N·m Cable stripping size Cable size: 0.3mm...
  • Page 26 Wiring Wiring of the control circuit of the 01800 or more For wiring of the control circuit of the 01800 or more, separate away from wiring of the main circuit. Make cuts in rubber bush of the inverter side and lead wires. ...
  • Page 27: When Connecting The Operation Panel Using A Connection Cable

    Wiring 2.4.8 When connecting the operation panel using a connection cable When connecting the operation panel (FR-DU07) to the inverter using a cable, the operation panel can be mounted on the enclosure surface and operationality improves. Parameter unit connection cable (FR-CB2 )(option) Operation panel(FR-DU07)
  • Page 28: Terminal Block

    Wiring 2.4.9 RS-485 terminal block ⋅ Conforming standard: EIA-485(RS-485) ⋅ Transmission format: Multidrop link OPEN ⋅ Communication speed: MAX 38400bps ⋅ Overall length: 500m Terminating resistor switch ⋅ Connection cable:Twisted pair cable Factory-set to "OPEN". (4 paires) Set only the terminating resistor switch of the remotest inverter to the "100Ω"...
  • Page 29: Power-Off And Magnetic Contactor (Mc)

    Power-off and magnetic contactor (MC) 2.5 Power-off and magnetic contactor (MC) (1) Inverter input side magnetic contactor (MC) On the inverter input side, it is recommended to provide an MC for the following purposes. page for selection.) Refer to 1) To release the inverter from the power supply when the inverter's protective function is activated or when the drive is not functioning (e.g.
  • Page 30: Precautions For Use Of The Inverter

    Precautions for use of the inverter 2.6 Precautions for use of the inverter The FR-F700 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may shorten the product life or damage the product. Before starting operation, always recheck the following items.
  • Page 31 Precautions for use of the inverter (13) If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor in the inverter's input side and also make up a sequence which will not switch on the start signal. If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the power is restored.
  • Page 32: Drive The Motor

    Step of operation 3 DRIVE THE MOTOR 3.1 Step of operation The inverter needs frequency command and start command. Turning the start command on start the motor rotating and the motor speed is determined by the frequency command (set frequency). Refer to the flow chart below to perform setting.
  • Page 33: Operation Panel (Fr-Du07)

    Operation panel (FR-DU07) 3.2 Operation panel (FR-DU07) 3.2.1 Parts of the operation panel (FR-DU07) Operation mode indication PU: Lit to indicate PU operation mode. EXT: Lit to indicate external operation mode. NET: Lit to indicate network operation mode. Rotation direction indication FWD: Lit during forward rotation REV: Lit during reverse rotation Forward/reverse operation...
  • Page 34: Basic Operation (Factory Setting)

    Operation panel (FR-DU07) 3.2.2 Basic operation (factory setting) Operation mode switchover At powering on (external operation mode) PU Jog operation mode (Refer to page 32) (Example) Value change and frequency flicker. PU operation mode Frequency setting has been (output frequency monitor) written and completed!! Output current monitor Output voltage monitor...
  • Page 35: Operation Lock (Press [Mode] For An Extended Time (2S))

    Operation panel (FR-DU07) 3.2.3 Operation lock (Press [MODE] for an extended time (2s)) Operation using the setting dial and key of the operation panel can be made invalid to prevent parameter change and unexpected start and stop. · Set "10 or 11" in Pr. 161, then press for 2s to make the setting dial and key operation invalid.
  • Page 36: Monitoring Of Output Current And Output Voltage

    Operation panel (FR-DU07) 3.2.4 Monitoring of output current and output voltage POINT Monitor display of output frequency, output current and output voltage can be changed by pushing during monitoring mode. Operation Display Press during operation to choose the output frequency monitor Independently of whether the inverter is running in any operation mode or at a stop, the output current monitor appears by pressing...
  • Page 37: Change The Parameter Setting Value

    Operation panel (FR-DU07) 3.2.7 Change the parameter setting value Changing example Change the Pr. 1 Maximum frequency . Operation Display Screen at powering on The monitor display appears. PU indication is lit. Press to choose the PU operation mode. The parameter Press to choose the parameter number read...
  • Page 38: Overheat Protection Of The Motor By The Inverter (Pr. 9)

    Overheat protection of the motor by the inverter (Pr. 9) 3.3 Overheat protection of the motor by the inverter (Pr. 9) Set the rated motor current in Pr. 9 Electronic thermal O/L relay to protect the motor from overheat. Parameter Name Initial Value Setting Range...
  • Page 39: Start/Stop From The Operation Panel (Pu Operation Mode)

    Start/stop from the operation panel (PU operation mode) 3.4 Start/stop from the operation panel (PU operation mode) [Connection diagram] POINT Inverter Three-phase R/L1 From where is the frequency command given? Motor S/L2 AC power supply · Operation at the frequency set in the frequency setting mode T/L3 of the operation panel →Refer to 3.4.1 (Refer to page 34) ·...
  • Page 40: Operation Mode

    Start/stop from the operation panel (PU operation mode) 3.4.2 Use the setting dial like a potentiometer to perform operation. POINT Set "0" (extended mode parameter valid) in Pr. 160 User group read selection. Set "1" (setting dial potentiometer mode) in Pr. 161 Frequency setting/key lock operation selection. Operation example Change the frequency from 0Hz to 50Hz during operation Operation Display...
  • Page 41: Use Switches To Give A Start Command And A Frequency Setting (Multi-Speed Setting)

    Start/stop from the operation panel (PU operation mode) 3.4.3 Use switches to give a start command and a frequency setting (multi-speed setting) POINT · Use to give a start command. · Pr. 79 Operation mode selection must be set to "4" (external/PU combined operation mode 2) ·...
  • Page 42 Start/stop from the operation panel (PU operation mode) Operation Display Low speed Turn on the low speed switch (RL). The output frequency increases to " " (10Hz) according to Pr. 7 Acceleration time. Low speed Turn off the low speed switch (RL). The output frequency decreases to "...
  • Page 43: Perform Frequency Setting By Analog (Voltage Input)

    Start/stop from the operation panel (PU operation mode) 3.4.4 Perform frequency setting by analog (voltage input) POINT · Use to give a start command. · Pr. 79 Operation mode selection must be set to "4" (external/PU combined operation mode 2) [Connection diagram] (The inverter supplies 5V of power to the frequency setting potentiometer.(Terminal 10)) Inverter...
  • Page 44 Start/stop from the operation panel (PU operation mode) Operation Display Deceleration Turn the volume (frequency setting potentiometer) counterclockwise slowly to full. Flickering The frequency value on the indication decreases Stop according to Pr. 8 Deceleration time unitl " " (0.00Hz) is displayed and operation status indication of FWD or REV flickers.
  • Page 45: Perform Frequency Setting By Analog (Current Input)

    Start/stop from the operation panel (PU operation mode) 3.4.5 Perform frequency setting by analog (current input) POINT · Use to give a start command. · Turn the AU signal on. · Pr. 79 Operation mode selection must be set to "4" (external/PU combined operation mode 2) [Connection diagram] Inverter Three-phase...
  • Page 46 Start/stop from the operation panel (PU operation mode) Operation Display Acceleration → constant speed Output of the Perform 20mA input. adjustment meter The frequency value on the indication increases (4 to 20mADC) according to Pr. 7 Acceleration time until " "...
  • Page 47: Make A Start And Stop With Terminals (External Operation)

    Make a start and stop with terminals (external operation) 3.5 Make a start and stop with terminals (external operation) POINT From where is the frequency command given? · Operation at the frequency set in the frequency setting mode of the operation panel → Refer to 3.5.1(Refer to page 42) ·...
  • Page 48: External Operation

    Make a start and stop with terminals (external operation) Operation Display While the value is flickering, press to set the frequency. Flicker ··· Frequency setting complete!! If you do not press ,the value flickers for about 5s and the display then returns to 0.00 (display) Hz.
  • Page 49: Use Switches To Give A Start Command And A Frequency Setting (Multi-Speed Setting) (Pr. 4 To Pr. 6)

    Make a start and stop with terminals (external operation) 3.5.2 Use switches to give a start command and a frequency setting (multi-speed setting) (Pr. 4 to Pr. 6) POINT · Start command by terminal STF (STR)-PC · Frequency command by terminal RH, RM, RL and STR-PC ·...
  • Page 50 Make a start and stop with terminals (external operation) Operation Display Mode/monitor check Press twice to choose the monitor/frequency monitor. High speed Turn on the high speed switch (RH). Middle speed Low speed Forward rotation Turn the start switch (STF or STR) on. Reverse rotation "...
  • Page 51: Perform Frequency Setting By Analog (Voltage Input)

    Make a start and stop with terminals (external operation) 3.5.3 Perform frequency setting by analog (voltage input) [Connection diagram] (The inverter supplies 5V of power to frequency setting potentiometer. (Terminal 10)) Inverter Three-phase R/L1 S/L2 Motor AC power supply T/L3 Forward rotation start Reverse rotation...
  • Page 52: Change The Frequency (50Hz) Of The Maximum Value Of Potentiometer (At 5V)

    Make a start and stop with terminals (external operation) The motor will not rotate ... Why? Check that [EXT] is lit. [EXT] is valid when Pr. 79 = "0" (initial value). to lit [EXT]. Check that wiring is correct. Check once again. Change the frequency (0Hz) of the minimum value of potentiometer (at 0V) Adjust the frequency in calibration parameter C2 Terminal 2 frequency setting bias frequency.
  • Page 53: Perform Frequency Setting By Analog (Current Input)

    Make a start and stop with terminals (external operation) 3.5.5 Perform frequency setting by analog (current input) POINT · Switch terminal STF(STR)-PC on to give a start command. · Turn the AU signal on. · Set "2" (external operation mode) in Pr. 79 Operation mode selection [Connection diagram] Inverter Three-phase...
  • Page 54: Change The Frequency (50Hz) Of The Maximum Value Of Potentiometer (At 20Ma)

    Make a start and stop with terminals (external operation) The motor will not rotate ... Why? Check that [EXT] is lit. [EXT] is valid when Pr. 79 = "0" (initial value). to lit [EXT]. Check that the AU signal is on. Turn the AU signal on.
  • Page 55: Adjustment

    Simple mode parameter list 4 ADJUSTMENT 4.1 Simple mode parameter list For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made from the operation panel (FR-DU07).
  • Page 56: Increase The Starting Torque (Pr. 0)

    Increase the starting torque (Pr. 0) 4.2 Increase the starting torque (Pr. 0) Set this parameter when "the motor with a load will not rotate", "an alarm [OL] is output, resulting in an inverter trip due to [OC1], etc. Parameter Setting Name Initial Value...
  • Page 57: Limit The Maximum And Minimum Output Frequency (Pr. 1, Pr. 2)

    Limit the maximum and minimum output frequency (Pr. 1, Pr. 2) 4.3 Limit the maximum and minimum output frequency (Pr. 1, Pr. 2) Parameter Setting Name Initial Value Description Number Range 120Hz 01160 or less Set the upper limit of the output Maximum frequency 0 to 120Hz frequency.
  • Page 58: When The Rated Motor Frequency Is 60Hz (Pr. 3)

    When the rated motor frequency is 60Hz (Pr. 3) 4.4 When the rated motor frequency is 60Hz (Pr. 3) First, check the motor rating plate. If a frequency given on the rating plate is "60Hz" only, always set Pr. 3 Base frequency to "60Hz".
  • Page 59: Change Acceleration And Deceleration Time (Pr. 7, Pr. 8)

    Change acceleration and deceleration time (Pr. 7, Pr. 8) 4.5 Change acceleration and deceleration time (Pr. 7, Pr. 8) Set in Pr. 7 Acceleration time a larger value for a slower speed increase and a smaller value for a faster speed increase. Set in Pr.
  • Page 60: Energy Saving Operation (Pr. 60)

    Energy saving operation (Pr. 60) 4.6 Energy saving operation (Pr. 60) Without a fine parameter setting, the inverter automatically performs energy saving operation. This inverter is appropriate for fan and pump applications Parameter Initial Setting Name Remarks Number Value Range Normal operation mode Energy saving control selection Energy saving operation mode...
  • Page 61 Energy saving operation (Pr. 60) Operation Display Screen at powering on The monitor display appears. PU indication is lit. Press to choose the PU operation mode. The parameter Press to choose the parameter number previously setting mode. read appears. (Pr. 60) Turn until appears.
  • Page 62: Selection Of The Operation Command And Frequency Command Locations (Pr. 79)

    Selection of the operation command and frequency command locations (Pr. 79) 4.7 Selection of the operation command and frequency command locations (Pr. 79) Select the start command location and frequency command location. LED Indication Parameter Initial Setting Name Description : Off Number Value Range...
  • Page 63: Parameter Clear, All Parameter Clear

    Parameter clear, all parameter clear 4.8 Parameter clear, all parameter clear POINT · Set "1" in Pr. CL parameter clear, ALLC All parameter clear to initialize parameters. (Parameters are not cleared when "1" is set in Pr. 77 Parameter write selection. ) ·...
  • Page 64: Parameter Copy And Parameter Verification

    Verify parameters in the inverter and operation panel. (Refer to page 60.) REMARKS · When the copy destination inverter is not the FR-F700 series or parameter copy write is performed after parameter read is stopped, “model error ( )” is displayed.
  • Page 65: Parameter Verification

    It there is no difference, flicker to complete verification. Flicker ··· Parameter verification complete!! REMARKS When the copy destination inverter is not the FR-F700 series, "model error ( )" is displayed. flickers ... Why? Set frequencies, etc. may be different. Check set frequencies.
  • Page 66: Parameter List

    Parameter list 4.10Parameter list 4.10.1 List of parameters classified by purpose of use Set the parameters according to the operating conditions. The following list indicates purpose of use and corresponding parameters. Purpose of Use Parameter Number Manual torque boost Pr. 0, Pr. 46 Simple magnetic flux vector control Pr.
  • Page 67 Parameter list Purpose of Use Parameter Number Restart operation after instantaneous power failure/Flying Pr. 57, Pr. 58, Pr. 162 to Pr. 165, Pr. Operation selection at power start 299, Pr. 611 failure and instantaneous power failure Decelerate the motor to a stop at instantaneous power failure Pr. 261 to Pr. 266 Retry function at alarm occurrence Pr.
  • Page 68: Extended Parameters

    Extended parameters 4.11Extended parameters 4.11.1 Used to display the extended parameters Operation Display Screen at powering on The monitor display appears. PU indication is lit. Press to choose the PU operation mode. The parameter Press to choose the parameter number read previously appears.
  • Page 69: Parameter List

    Parameter list 4.12Parameter list indicates simple mode parameters. Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Set the output voltage at 0Hz as %. Initial values differ according to the inverter capacity.
  • Page 70 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Set the motor acceleration time. 0.1/ 0 to 3600/ Acceleration time 5/15s Initial values differ according to the inverter 0.01s 360s capacity.
  • Page 71 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Jog frequency 0.01Hz 0 to 400Hz Set the frequency for jog operation. Set the acceleration/deceleration time for jog operation.
  • Page 72 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Without compensation Multi-speed input compensation With compensation selection Linear acceleration/ deceleration Acceleration/ S-pattern acceleration/deceleration A deceleration pattern S-pattern acceleration/deceleration B selection Backlash measures...
  • Page 73 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Up-to-frequency 0.1% 0 to 100% Set the level where the SU signal turns on. sensitivity Output frequency Set the frequency where the FU signal 0.01Hz 0 to 400Hz...
  • Page 74 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled The coasting time is as follows: 00038 or less ........ 0.5s, 00052 to 00170......1.0s, 00250 to 01160 ......3.0s, Restart coasting 01800 or more ......
  • Page 75 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Retry selection 0 to 5 An alarm for retry can be selected. No retry function Set the number of retries at alarm 1 to 10 occurrence.
  • Page 76 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled You can select the input specifications of terminal 2 (0 to 5V, 0 to 10V, 0 to 20mA) and input specifications of terminal 1 (0 to ±5V, 0 to ±10V).
  • Page 77 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Write is enabled only during a stop Parameter write is disabled. Parameter write Parameter write is enabled in any selection operation mode regardless of operation status.
  • Page 78 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled V/F1(first 0 to 400Hz, 0.01Hz 9999 9999 frequency) V/F1(first frequency 0.1V 0 to 1000V voltage) V/F2(second 0 to 400Hz, 0.01Hz 9999...
  • Page 79 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Specify the inverter station number. PU communication Set the inverter station numbers when two or 0 to 31 station number more inverters are connected to one personal computer.
  • Page 80 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Terminal 2 Set the frequency of terminal 2 input gain × frequency setting 0.01Hz 50Hz 0 to 400Hz (maximum).
  • Page 81 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled PID control Set the frequency at which the control is 0 to 400Hz automatically changed to PID control. automatic 0.01Hz 9999...
  • Page 82 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Time required for only the differential (D) action to provide the same manipulated 0.01 to variable as that for the proportional (P) PID differential time 10.00s action.
  • Page 83 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Japanese English Germany PU display French × × language selection Spanish Italian Swedish Finnish 148,149 Refer to Pr.22 and Pr.23. —...
  • Page 84 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Setting dial frequency setting mode Key lock mode invalid Setting dial Frequency setting/ potentiometer mode key lock operation ×...
  • Page 85 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled 0, 100: Inverter running 1, 101: Up to frequency RUN terminal × 2, 102: Instantaneous power failure/ function selection 0 to 5, 7, 8, undervoltage...
  • Page 86 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled 232 to 239 Refer to Pr.4 to Pr.6. Refer to Pr.72. — Refer to Pr.125 and Pr.126. 242, 243 Refer to Pr.73.
  • Page 87 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Display whether the control circuit capacitor, main circuit capacitor, cooling Life alarm status × × × (0 to 15) fan, and each parts of the inrush current display...
  • Page 88 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Set the inverter station number. RS-485 communication 0 to 31 (same specifications as Pr.117 ) When "1" station number (Modbus-RTU protocol) is set in Pr.551, the (0 to 247)
  • Page 89 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Refer to Pr.79. — Remote output data clear at powering off Remote output Remote output data retention even at selection powering off Remote output data...
  • Page 90 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled No auxiliary motor operation Auxiliary motor Set the number of auxiliary motors to operation selection 1 to 3 be run Basic system Motor connection...
  • Page 91 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Traverse function invalid Traverse function is valid only in the Traverse function external operation mode selection Traverse function is valid independently of operation mode Maximum...
  • Page 92 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled Refer to Pr.52. Set the load factor for commercial power- supply operation. Load factor 0.1% 100% 30 to 150% This value is used to calculate the power consumption estimated value during...
  • Page 93 Parameter list Parameter Param Param param eter eter eter Incre Initial copy clear Name Range Description clear ments Value : enabled × : disabled CA terminal Calibrate the scale of the meter × (900) calibration connected to terminal CA. AM terminal Calibrate the scale of the analog meter ×...
  • Page 94: Troubleshooting

    Reset method of protective function 5 TROUBLESHOOTING When an alarm (major failures) occurs in the inverter, the protective function is activated bringing the inverter to an alarm stop and the PU display automatically changes to any of the following error (alarm) indications. If your fault does not correspond to any of the following errors or if you have any other problem, please contact your sales representative.
  • Page 95: List Of Alarm Display

    List of alarm display 5.2 List of alarm display Operation Panel Refer Operation Panel Refer Name Name Indication Indication Output side earth fault E.GF E--- Alarm history overcurrent HOLD Operation panel lock E.LF Output phase failure External thermal relay E.OHT Er1 to 4 Parameter write error operation E.PTC* PTC thermistor operation...
  • Page 96: Causes And Corrective Actions

    Causes and corrective actions 5.3 Causes and corrective actions (1) Error Message A message regarding operational troubles is displayed. Output is not shut off. Operation Panel HOLD Indication Name Operation panel lock Description Operation lock mode is set. Operation other than is made invalid.
  • Page 97 2. Check that the power is not turned off or an operation panel is not disconnected, etc. during parameter copy read. 1. Use the same model (FR-F700 series) for parameter copy and verification. Corrective action 2. Perform parameter copy read again.
  • Page 98 Causes and corrective actions (2) Warnings When the protective function is activated, the output is not shut off. Operation Panel FR-PU04 Indication FR-PU07 Name Stall prevention (overcurrent) When the output current of the inverter exceeds the stall prevention operation level (Pr. 22 Stall prevention operation level, etc.), this function stops the increase in frequency until During the overload current decreases to prevent the inverter from resulting in overcurrent...
  • Page 99 Causes and corrective actions Operation Panel FR-PU04 Indication FR-PU07 Name Regenerative brake prealarm Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 Special regenerative brake duty value. If the regenerative brake duty reaches 100%, a regenerative overvoltage (E.
  • Page 100 Causes and corrective actions (3) Minor fault When the protective function is activated, the output is not shut off. You can also output a minor fault signal by making parameter setting. (Set "98" in any of Pr. 190 to Pr. 196 (output terminal function selection). (Refer to Instruction Manual (applied).)) Operation Panel FR-PU04...
  • Page 101 Causes and corrective actions Operation Panel FR-PU04 E.OV1 OV During Acc Indication FR-PU07 Name Regenerative overvoltage shut-off during acceleration If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the Description specified value, the protective circuit is activated to stop the inverter output. The circuit may also be activated by a surge voltage produced in the power supply system.
  • Page 102 Causes and corrective actions FR-PU04 Operation Panel E.FIN H/Sink O/Temp Indication FR-PU07 Name Fin overheat If the heatsink overheats, the temperature sensor is actuated to stop the inverter output. The FIN signal can be output when the temperature becomes approximately 85% of the heatsink overheat protection operation temperature.
  • Page 103 Causes and corrective actions FR-PU04 Fault 14 Operation Panel E.ILF Indication FR-PU07 Input phase loss Name Input phase failure This alarm is output when function valid setting (=1) is set in Pr. 872 Input phase failure protection selection and Description one phase of the three phase power input opens.
  • Page 104 Causes and corrective actions FR-PU04 Operation Panel E.OPT Option Fault Indication FR-PU07 Name Option alarm Appears when the AC power supply is connected to the terminal R/L1, S/L2, T/L3 accidentally when a Description high power factor converter is connected. · Check that the AC power supply is not connected to the terminal R/L1, S/L2, T/L3 when a high power Check point factor converter (FR-HC, MT-HC) or power regeneration common converter (FR-CV) is connected.
  • Page 105 Causes and corrective actions Operation Panel FR-PU04 E.RET Retry No Over Indication FR-PU07 Name Retry count excess If operation cannot be resumed properly within the number of retries set, this function stops the inverter Description output. Check point Find the cause of alarm occurrence. Corrective action Eliminate the cause of the error preceding this error indication.
  • Page 106 Causes and corrective actions FR-PU04 Fault 14 Operation Panel E.SER Indication FR-PU07 VFD Comm error Name Communication error (inverter) This function stops the inverter output when communication error occurs consecutively for more than permissible retry count when a value other than "9999" is set in Pr. 335 RS-485 communication retry count Description during RS-485 communication from the RS-485 terminals.
  • Page 107: Correspondences Between Digital And Actual Characters

    Correspondences between digital and actual characters 5.4 Correspondences between digital and actual characters There are the following correspondences between the actual alphanumeric characters and the digital characters displayed on the operation panel. Actual Digital Actual Digital Actual Digital...
  • Page 108: Check And Clear Of The Alarm History

    Check and clear of the alarm history 5.5 Check and clear of the alarm history (1) Check for the alarm (major fault) history Monitor/frequency setting Parameter setting [Operation panel is used [Parameter setting change] for operation] Alarm history [Operation for displaying alarm history] Eight past alarms can be displayed with the setting dial.
  • Page 109 Check and clear of the alarm history (2) Clearing procedure POINT · The alarm history can be cleared by setting "1" in Er.CL Alarm history clear. (The alarm history is not cleared when "1" is set in Pr. 77 Parameter write selection) Display Operation Screen at powering on...
  • Page 110: Check First When You Have Troubles

    Check first when you have troubles 5.6 Check first when you have troubles POINT If the cause is still unknown after every check, it is recommended to initialize the parameters (initial value) then re- set the required parameter values and check again. 5.6.1 Motor does not start 1) Check the value of Pr.
  • Page 111: Motor Rotates In Opposite Direction

    Check first when you have troubles 5.6.4 Motor rotates in opposite direction Check that the phase sequence of output terminals U, V and W is correct. Check that the start signals (forward rotation, reverse rotation) are connected properly. (Refer to page 42) 5.6.5 Speed greatly differs from the setting Check that the frequency setting signal is correct.
  • Page 112: Operation Mode Is Not Changed Properly

    Check first when you have troubles 5.6.10 Operation mode is not changed properly 1) Inspection of load Check that the STF or STR signal is off. When it is on, the operation mode cannot be changed. 2) Parameter setting Check the Pr. 79 setting. When the Pr.
  • Page 113: Precautions For Maintenance And Inspection

    Inspection item 6 PRECAUTIONS FOR MAINTENANCE AND INSPECTION The inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and vibration, changes in the parts with time, service life, and other factors.
  • Page 114: Daily And Periodic Inspection

    Inspection item 6.1.3 Daily and periodic inspection Interval Corrective Action at Inspection Item Inspection Item Alarm Occurrence Surrounding Check the ambient temperature, humidity, dirt, Improve emvironment environment corrosive gas, oil mist , etc Check alarm location and General Overall unit Check for unusual vibration and noise retighten Power supply...
  • Page 115: Display Of The Life Of The Inverter Parts

    Inspection item 6.1.4 Display of the life of the inverter parts The self-diagnostic alarm is output when the life span of the control circuit capacitor, cooling fan, each parts of the inrush current limit circuit is near to give an indication of replacement time . The life alarm output can be used as a guideline for life judgement.
  • Page 116: Cleaning

    Inspection item (2) Measuring method of life of the main circuit capacitor · If the value of capacitor capacity measured before shipment is considered as 100%, Pr. 255 bit1 is turned on when the measured value falls below 85%. · Measure the capacitor capacity according to the following procedure and check the deterioration level of the capacitor capacity.
  • Page 117 Inspection item (1) Cooling fan The replacement interval of the cooling fan used for cooling the parts generating heat such as the main circuit semiconductor is greatly affected by the ambient temperature. When unusual noise and/or vibration is noticed during inspection, the cooling fan must be replaced immediately. CAUTION For parts replacement, consult the nearest Mitsubishi FA Center.
  • Page 118 Inspection item • Reinstallation (00083 to 03610) 1) After confirming the orientation of the fan, reinstall the fan so that the arrow on the left of "AIR FLOW" faces up. AIR FLOW 2) Reconnect the fan connectors. 00170 to 00380 00083, 00126 00770 to 03610...
  • Page 119 Inspection item • Removal (04320 or more) 1) Remove a fan cover. 2) After removing a fan connector, remove a fan block. 3) Remove a fan. Fan * Fan connection connector * The number of cooling fans differs according to the inverter capacity. •...
  • Page 120: Inverter Replacement

    Inspection item (2) Replacement procedure of the cooling fan when using a heatsink protrusion attachment (FR-A7CN) When replacing a cooling fan, remove a top cover of the heatsink protrusion attachment and perform replacement. After replacing the cooling fan, replace the top cover in the original position.
  • Page 121: Specifications

    Rating 7 SPECIFICATIONS 7.1 Rating •400V class SLD is initially set. 00023 00038 00052 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160 Type FR-F740- Applied motor capacity 0.75 18.5 (kW) Rated capacity 12.2 17.5 22.1 26.7 32.8 43.4 53.3 64.8 80.8...
  • Page 122: Common Specifications

    Common specifications 7.2 Common specifications High carrier frequency PWM control (V/F control)/optimum excitation control/simple Control method magnetic flux vector control Output frequency range 0.5 to 400Hz 0.015Hz/0 to 60Hz (terminal 2, 4: 0 to 10V/12bit) Frequency Analog input 0.03Hz/0 to 60Hz (terminal 2, 4: 0 to 5V/11bit, 0 to 20mA/11bit, terminal 1: 0 to ±10V/12bit) setting 0.06Hz/0 to 60Hz (terminal 1: 0 to ±5V/11bit) resolution...
  • Page 123 Common specifications Output frequency, motor current (steady or peak value), output voltage, alarm indication, frequency setting, running speed, converter output voltage (steady or peak value), electronic thermal relay function load factor, input power, output power, load meter, cumulative energization Operating time, actual operation time, motor load factor, cumulative power, power saving effect, cumulative status saving power, regenerative brake duty...
  • Page 124: Outline Dimension Drawings

    Outline dimension drawings 7.3 Outline dimension drawings 7.3.1 Inverter outline dimension drawings • FR-F740-00023, 00038, 00052, 00083, 00126-EC 2-φ6 hole * The FR-F740-00023 to 00052-EC are not provided with a cooling fan. (Unit: mm) • FR-F740-00170, 00250, 00310, 00380-EC 2-φ6 hole Inverter Type FR-F740-00170, 00250-EC FR-F740-00310, 00380-EC...
  • Page 125 Outline dimension drawings • FR-F740-00470, 00620-EC 2-φ10 hole 10.5 (Unit: mm) • FR-F740-00770, 00930, 01160-EC 2-φd hole Inverter Type FR-F740-00770-EC FR-F740-00930, 01160-EC (Unit: mm)
  • Page 126 Outline dimension drawings • FR-F740-01800-EC 2-φ12 hole Inverter Type FR-F740-01800-EC • DC reactor supplied Rating plate 2-terminal (for M12 bolt) P1, P 4-installation hole (for M6 screw) Within D Earth (ground) terminal (for M6 screw) Mass DC reactor Type (kg) FR-HEL-H90K (FR-F740-01800-EC ) (Unit: mm)
  • Page 127 Outline dimension drawings • FR-F740-02160, 02600, 03250, 03610-EC 2-φ12 hole Inverter Type FR-F740-02160, 02600-EC FR-F740-03250, 03610-EC • DC reactor supplied Rating plate 2-terminal (for M12 bolt) 4-installation hole (for S screw) Within D Earth (ground) terminal (for S1 screw) Mass DC reactor Type (kg) FR-HEL-H110K(FR-F740-02160-EC)
  • Page 128 Outline dimension drawings • FR-F740-04320, 04810-EC 3-φ12 hole • DC reactor supplied Rating plate 2-S2 eye nut 2-terminal (for bolt) W1 1 4-installation hole (for S screw) Within D Earth (ground) terminal (for S1 screw) * Remove the eye nut after installation of the product. Mass φ...
  • Page 129 Outline dimension drawings • FR-F740-05470, 06100, 06830-EC 3- 12 holes S/L2 R/L1 T/L3 • DC reactor supplied Rating plate 2-S2 eye nut 2-terminal (for bolt) W1 1 4-installation hole (for S screw) Within D Earth (ground) terminal (for S1 screw) * Remove the eye nut after installation of the product.
  • Page 130 Outline dimension drawings • FR-F740-07700, 08660-EC 3-φ12 hole R/L1 T/L3 S/L2 • DC reactor supplied Rating plate 2-M8 eye nut 2-terminal 4- 15 hole 4-installation hole (for M10 screw) Within 250 Within 235 Earth (ground) terminal (for M8 screw) * Remove the eye nut after installation of the product. Mass DC reactor Type (kg)
  • Page 131 Outline dimension drawings • FR-F740-09620, 10940, 12120-EC 4-φ12 hole R/L1 S/L2 T/L3 N/- • DC reactor supplied Rating plate 2-terminal 4- 15 hole Earth (ground) terminal (for M12 screw) * Remove the eye nut after installation of the product. Within 245 2-M12 eye nut 4-installation hole (for M10 screw)
  • Page 132 Outline dimension drawings • Operation panel (FR-DU07) Panel 27.8 FR-DU07 3.2max Air- bleeding hole Cable 2-M3 screw Operation panel connection connector (FR-ADP option) • Parameter unit (option) (FR-PU07) 25.05 (14.2) (11.45)
  • Page 133: Heatsink Protrusion Attachment Procedure

    Heatsink protrusion attachment procedure 7.4 Heatsink protrusion attachment procedure When encasing the inverter in an enclosure, the generated heat amount in an enclosure can be greatly reduced by installing the heatsink portion of the inverter outside the enclosure. When installing the inverter in a compact enclosure, etc., this installation method is recommended.
  • Page 134 Heatsink protrusion attachment procedure (2) Shift and removal of a rear side installation frame • FR-F740-05470 to 06830 Shift One installation frame is attached to each of the upper and lower Upper part of the inverter. Change the position of the rear side installa- installation frame tion frame on the upper and lower side of the inverter to the front...
  • Page 135 Heatsink protrusion attachment procedure (3) Installation of the inverter Push the inverter heatsink portion outside the enclosure and fix the enclosure and inverter with upper and lower installation frame. Enclosure * For the FR-F740-05470 or more, there are finger guards behind the enclosure. Therefore, the Inside the Exhausted air enclosure...
  • Page 136: Appendices

    Note that the wiring cover (00023 to 00470) is not compatible. FR-F500 series FR-F700 series (Note that the relay output 2 (A2, B2, C2) specific for the FR-F700 series can not be used with the FR-F500 series terminals.) (3) Instructions for continuous use of the FR-PU04 (parameter unit) 1) For the FR-F700 series, many functions (parameters) have been added.
  • Page 137: Appendix 1-2Replacement Of The Fr-A100 Series

    00250 to 01160:2% used was the initial value, it is not necessary to change the torque boost value from the initial value when replacing with the FR-F700 series.) User group (16) only User group 1 (16), user group 2 (16) Setting methods were partially changed (Pr.
  • Page 138: Appendix 2 Instructions For Ul And Cul Compliance

    Appendix 2 Instructions for UL and cUL Compliance (Conforming standard UL 508C, CSA C22.2 No.14) (1) Installation This inverter is a UL / cUL Listed, enclosed type device with a suitably rated enclosure. Design an enclosure so that the inverter ambient temperature, humidity and atmosphere satisfy the specifications. (Refer to page 117.) Wiring protection For installation in the United States, branch circuit protection must be provided in accordance with the National...
  • Page 139 (4) Motor overload protection This inverter is certified as a motor overload protection device by UL. When using the electronic thermal relay function as motor overload protection, set the rated motor current to Pr. 9 Electronic thermal O/L relay. This function detects the overload (overheat) of the Electronic thermal relay function operation characteristic motor, stops the operation of the inverter's output Pr.
  • Page 140: Appendix 3 Instructions For Compliance With The European Directives

    Appendix 3 Instructions for Compliance with the European Directives (1) EMC Directive We have self-confirmed our inverters as products compliant to the EMC Directive (second environment of conforming standard EN61800- 3) and place the CE mark on the inverters. Note:First environment Environment including residential buildings.
  • Page 141 MEMO...
  • Page 142 REVISIONS *The manual number is given on the bottom left of the back cover. Print Date Revision Manual Number May, 2004 IB(NA)-0600192ENG-A First edition Aug., 2004 IB(NA)-0600192ENG-B Additions FR-F740 - 02600 to 03610 - EC ⋅ Pr.299 Rotation direction detection selection at restarting ⋅...