Honeywell HC900 Installation And User Manual

Honeywell HC900 Installation And User Manual

Process controller
Hide thumbs Also See for HC900:
Table of Contents
HC900 Process Controller
Installation and User Guide
Doc. No.:
51-52-25-107
Revision:
19
Date:
June 2014
Honeywell Process Solutions
Table of Contents
loading

Summary of Contents for Honeywell HC900

  • Page 1 HC900 Process Controller Installation and User Guide Doc. No.: 51-52-25-107 Revision: Date: June 2014 Honeywell Process Solutions...
  • Page 2 HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 3 However, we assume no responsibility for its use. While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product in the application.
  • Page 4 About This Document Abstract This document provides descriptions and procedures for the installation, operation and maintenance of the HC900 Process Controller hardware. References The following list identifies all documents that may be sources of reference for material discussed in this publication.
  • Page 5 About This Document Support and Contact Information For Europe, Asia Pacific, North and South America contact details, refer to the back page of this manual or the appropriate Honeywell Solution Support web site: Honeywell Organization WWW Address (URL) Corporate http://www.honeywell.com Honeywell Process Solutions www.honeywellprocess.com...
  • Page 6: Symbol Definitions

    Chassis Ground. Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 7: Table Of Contents

    Electrical Considerations........................47 System Monitor Function Blocks ....................... 54 Rack Installation ......................55 Overview ............................55 Mount Racks ............................ 58 Assemble Controller Rack......................... 60 Assemble I/O Expansion Racks ......................64 Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 8 Overview ............................117 Wiring and cabling .......................... 117 Connecting the Operator Interface to the Controller................. 121 Connecting the HC900 Controller to a PC with the Designer Software ..........122 Connecting the HC900 Controller to Modbus device(s) ..............142 Operating Characteristics .................... 145 Introduction.............................
  • Page 9 Safety Considerations - PLAN AHEAD! ................... 184 Specifications ......................194 General Specifications ........................194 HC900 Analog Input Ranges vs. UMC800 Analog Input ranges ............200 System Sizing and Availability Summary ..................203 Fiber Optics Recommendations ...................... 204 Appendix - Installation of Remote Termination Panels (RTPs) ........... 207 Overview ............................
  • Page 10 Table 39 – Installing Backup Battery (CPU not initialized)................192 Table 40 – Replacing a Backup Battery (CPU Powered)) ................. 193 Table 41 - HC900 PV Input Types and Ranges ....................200 Table 42 – System Size and Availability Summary ..................203 Table 43 –...
  • Page 11 Figures Figure 1 – Small HC900 Controller Configuration ....................7 Figure 2 – Expanded HC900 Controller Configuration (C50/C70 CPU only) ............8 Figure 3 – Single process with redundancies ......................9 Figure 4 – Configuration with Multiple Controllers .................... 14 Figure 5 –...
  • Page 12 Figure 67 – Quadrature, Differential, External Power Wiring ................113 Figure 68 – Quadrature, Single Ended, External Power Wiring ................. 114 Figure 69 – Quadrature, Differential, HC900 Power Wiring ................114 Figure 70 – Quadrature, Single Ended, HC900 Power Wiring................115 Figure 71 –...
  • Page 13: Introduction

    Introduction Purpose This publication describes the installation, operation, and maintenance of the Honeywell HC900 Process Controller. This publication includes the following sections. Chapter Title Page Content Introduction Model numbers, how to verify component compatibility, function description of components, feature summary.
  • Page 14: Model Selection Guide

    900H01 - 0102 Digital Output, 24VDC (16 channel) 900H02 - 0102 Digital Output, 24VDC (32 channel) 900H32 - 0001 Digital Output, 120/240 VAC (8 channel) 900H03 - 0102 Pulse/Frequency/Quadrature 900K01 - 0001 HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 15 Null Modem Cable 51404755-501 Null Modem Cable used with 900C70R 50004820-501 250 ohm Shunt Resistor Kit ( (8/pkg.) 51205995-501 Ethernet Switching Hub (8 Ports) 50008930-001 24 VDC Power Supply 51452041-501 Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 16 Controller C50 CPU 900C50-0360-00 Controller C70 CPU 900C70-0360-00 Controller C70R CPU 900C75-0360-00 I/O Scanner - 2 Port (1 per I/O rack) 900S75-0360-00 I/O Scanner - 1 Port (1 per I/O rack) 900S50-0360-00 HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 17 Throughout this guide, where the text “New systems” is used, the following model numbers are applicable. • New System (SIL and Non SIL Model Numbers) − 900C30-0360-00 − 900C50-0360-00 − 900C70-0360-00 − 900C75-0360-00 − 900S75-0360-00 − 900S50-0360-00 Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 18 900S75S-0360-00 ATTENTION For the Legacy systems, it is specifically mentioned in the guide wherever applicable. The other text is applicable to the new HC900 system. Modems are not qualified with the new HC900 system. Checking HC900 Model Numbers for Compatibility ATTENTION Be sure to check your model numbers for compatibility before installation.
  • Page 19: Functional Description

    It comprises a set of hardware and software modules that can be assembled to satisfy any of a broad range of process control applications. The HC900 Process Controller can consist of a single rack, as indicated in Figure 1, or can be can be networked with other controllers via Ethernet links to expand the dimensions of control over a wider range of unit processes, as indicated in Figure 2.
  • Page 20: Figure 2 - Expanded Hc900 Controller Configuration (C50/C70 Cpu Only)

    Figure 2 – Expanded HC900 Controller Configuration (C50/C70 CPU only) The HC900 Controller design enables users and OEMs who are adept in system integration to assemble a system that fits a broad range of requirements. Any configuration can be readily modified or expanded as requirements dictate.
  • Page 21: Figure 3 - Single Process With Redundancies

    I/O racks – 5 racks shown, top to bottom: 4-slot w/1 power supply, 8-slot w/1 power supply, 12-slot w/1 power supply, 8-slot w/redundant power supplies, 12-slot w/redundant power supplies. A Power Status Module (PSM) is required with redundant power supplies. High and low capacity power supplies are available. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 22: Feature Summary

    Ethernet 10/100Base-T connection to: up to 5 PC hosts via Modbus/TCP protocol, Peer-to Peer communication with other HC900 Controllers, and the Internet. C70 has 2 Ethernet ports for connection to up to 10 PC hosts. It also supports Modbus/TCP Initiator function over both ports.
  • Page 23 Device Network − RS-232 or RS-485 Serial Interface; Modbus RTU. Two serial ports available for legacy systems. Each port can be set as Modbus Master or Slave. Host Serial Interface for Honeywell or third party operator interface. − For new systems two serial R2-485 ports are available. Each port can be set as Modbus Master or Slave.
  • Page 24 Introduction - Feature Summary This page is intentionally left blank. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 25: Components And Architecture

    Components and Architecture - Overview Components and Architecture Overview This section provides a description of each of the major components that can be included in an HC900 Controller physical configuration, and indicates some of the methods by which they can be combined. Components The Honeywell HC900 Process Controller includes a set of hardware modules that can be combined and configured as required for a wide range of small to medium process control applications.
  • Page 26: Figure 4 - Configuration With Multiple Controllers

    Figure 4 – Configuration with Multiple Controllers CAUTION The HC900-expansion I/O link is a private network and the switch used for the interconnection of the HC900 Processor and Scanners must not be connected to any other LAN or WAN. Likewise, no devices other than the HC900 components should be connected to the I/O link Switch.
  • Page 27: Table 1 - Descriptions Of Major Components (Figure 4)

    Enables inter-connection of several 10/100Base-T Third-party suppliers. 10/100Base-T Ethernet devices in an Ethernet network. Devices Switch or include other HC900 Controllers, HMIs, and can also Router include routers, brouters, servers, and other devices in wider networks. Ethernet CAT5 Connects I/O expansion racks (C50/C70 CPU only)
  • Page 28: Redundant Components

    Figure 5 – Redundant Configuration with multiple I/O racks CAUTION The HC900-expansion I/O link is a private network and the switch used for the interconnection of the HC900 Processor and Scanners must not be connected to any other LAN or WAN. Likewise, no devices other than the HC900 components should be connected to the I/O link Switch.
  • Page 29: Table 2 - Descriptions Of Major Redundancy Components

    RS-485 to USB converter. HMI (Human- (Optional) PC link to Ethernet network, which may PC is from third-party Machine include other HMIs, other HC900 Controllers, and supplier. Interface) other networks (including Internet). HMI software is Typically includes HMI operating software.
  • Page 30: Hardware Components

    For environmental specifications, refer to the section on Pre-Installation Planning. HC900 Controller Rack An HC900 Controller ("local rack") is shown in the following figure. As indicated in this figure, the Controller Rack includes: 1. Rack, available in 4- 8-, or 12-slot versions 2.
  • Page 31: Figure 8 - I/O Expansion Rack Components

    6. I/O Terminal Blocks 7. Power Status Module (PSM) (req’d if using Reserve Power Supply) 8. Reserve Power Supply (optional). Available in 8- or 12-slot racks. Figure 8 – I/O Expansion Rack Components Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 32: Figure 9 - Rack Options

    C75 only: I/O rack has Scanner 2 Module. 8 and 12 slot I/O racks can be modified with additional slots for optional Reserve Power Supply and Power Status Module. Note: You can install redundant power on any I/O rack. Figure 9 – Rack Options HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 33: Figure 10 - Power Supply

    I/O, a Remote I/O rack or a Redundant C75 CPU. The 60 watt capacity requires minimal de-rating of the available HC900 I/O modules. A tool-secured door covers the voltage connections. An internal non- replaceable fuse limits supply current under certain fault conditions.
  • Page 34: Figure 11 - Power Status Module (Psm)

    When the status is off, either the power supply is off or the voltages are out of tolerance. Figure 11 – Power Status Module (PSM) HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 35: Figure 12 - Controller Module

    7. LED status/diagnostic indicator for controller module. Figure 12 – Controller Module Redundant controller rack contains two C75s. Left CPU is designated CPU-A, right CPU is CPU-B; either CPU can be Lead. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 36: Figure 13 - Redundancy Switch Module

    Controller Module (or to a port on a Switch that connects to the Controller Module) 3. LED status/diagnostic indicators for communications functions. Figure 14 – Scanner 1 Module HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 37: Figure 15 - Scanner 2 Module

    Each I/O module includes a status indicator for the module. Digital Input and Digital Output modules also include a status indicator for each channel. Terminal blocks available include the Euro style (Figure 16 left) and the Barrier style (Figure 16 right). Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 38 For the new system, a PC can be connected to the controller via the RS-485 TO USB cable connected to RS485 Port , which can be connected to external Honeywell qualified RS485 to USB converter, and can also be networked to the controller via the Ethernet 10/100Base-T Open Connectivity Network port.
  • Page 39: Ethernet Devices/Considerations

    The HC900-expansion I/O link is a private network and the switch used for the interconnection of the HC900 Processor and Scanners must not be connected to any other LAN or WAN. Likewise, no devices other than the HC900 components should be connected to the I/O link Switch.
  • Page 40: I/O Network

    10Base-T connectors on the C50 CPU Controller Module and the Scanner Module. ATTENTION: For 2 or more I/O expansion racks a switch is required. Use only Honeywell recommended switches (part no. 50008930-001). The total number of switches is limited to 2 in series between a CPU and its scanners.
  • Page 41: Ethernet Open Connectivity Network

    Controller Module and in each Scanner Module included in the HC900 system. The controller examines the control strategy stored in its memory, verifies that the physical configuration (Rack Numbers, and I/O Module type- by Module Number) matches the stored control strategy, and establishes communication with each of the I/O modules in each of the I/O racks.
  • Page 42: Figure 19 - Modular Network Structure

    Process Controller Function Block User Guide for additional information.) An illustration of HC900 Controller Peer-to-Peer on a Local Area Network (LAN) is given in Figure 19. Typically, a Router is used for interconnection to another network (LAN, WAN, or other).
  • Page 43: Figure 20 - Modbus/Tcp Framing

    LAN or WAN (Wide Area Network) that is network-connected to the controller. Each HC900 Controller has five “sockets” (software and memory resources), each of which can service data requests from any networked PC on a client (host)/server (controller) basis. C75 has 10 sockets. The sockets are available on a first-come, first-served basis.
  • Page 44 − OPC server/client software (various; available from Kepware and others) : The items in this list are not sold by Honeywell. They have not all been tested and certified by Note Honeywell, and are not necessarily recommended or endorsed by Honeywell for any specific use.
  • Page 45 Ethernet Open Connectivity network. In other cases, the HC900 Controller will be a member of a Local Area Network (LAN) as indicated in Figure 19. The HC900 controller LAN may be very simple, or it may include many devices in a complex and very sophisticated structure. In any case, it must always be regarded as a single, modular entity that can be protected from intrusion by any other networking device to which this LAN is connected.
  • Page 46: Figure 21 - Typical Installation Using A Cable Modem

    Components and Architecture - Ethernet Open Connectivity Network Figure 21 – Typical installation using a Cable Modem HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 47: Serial Ports (Rs-232 And Rs-485 For Legacy Systems And Two Rs-485 Ports For New Systems)

    • Controller can be slave to masters such as − Honeywell Operator Interface (1040, 559). Must be on RS-485 port S2. Will not work on port S1 even if set to RS-485. Will not work on port S1. − Honeywell HC Designer PC software −...
  • Page 48: Table 3 - Serial Port Dip Switch Settings

    DIP switches. If you push too hard you could damage the switches or nearby circuitry. Avoid using pencils because the point could break and cause damage. Table 3 – Serial port DIP switch settings Figure 23 – Serial Ports DIP Switch default settings HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 49: Pre-Installation Planning

    Cabling/wiring distance planning (see page 45) • Electrical considerations: controller grounding, CE conformity, grouping wires, master control relay for emergency shutdown (see page 47) • System monitor function blocks (see page 54) Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 50: Ac Power Supply Selection For Racks With I/O

    8. Is the result of 7 less than 28? Yes/No 9. If the answer to 8 is Yes, use power supply 900P02-0001 10. If the answer to 8 is No, use power supply 900P01-0001 HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 51: Dc Power Supply

    Figure 24 and Figure 25. Vertical spacing of racks, which is required for rack ventilation and for routing wires, is shown in Figure 26. Figure 24 – Rack Dimensions (C30 and C50) Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 52: Figure 25 - Rack Dimensions With Reserve Power Supply

    Pre-Installation Planning - Rack Orientation and Mounting Figure 25 – Rack Dimensions with reserve power supply HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 53: Remote Termination Panels

    RTPs to replace the intermediate terminations. Pre-wired cable assemblies for the RTPs eliminate the need for separate wiring terminations between the controller and the intermediate terminal boards. For details see page 207. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 54: Environment

    Pre-Installation Planning - Environment Environment The HC900 Controller must be mounted in suitable equipment enclosures. That is, all components such as the Controller rack, I/O Racks, and the Operator Interface manufactured by Honeywell must be mounted in approved furniture designed for industrial applications.
  • Page 55: Heat Rise De-Rating

    Pre-Installation Planning - Heat Rise De-rating Heat Rise De-rating The HC900 is rated to operate at 60 C. However, for maximum reliability, the following guidelines should be observed for applications above 52 1. Locate lower-power modules (Analog Input, Contact Input, etc) beside the Controller/Scanner Module, and keep higher-power modules (AC Output, AC Input, etc) away from it.
  • Page 56: Figure 27 - Ac Input Module De-Rating

    Pre-Installation Planning - Heat Rise De-rating Figure 27 – AC Input Module de-Rating Figure 28 – Power Supply de-Rating HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 57: Cable/Wiring Distance Planning

    • With redundant CPUs, when using 2 or more I/O racks an Ethernet switch is required between each CPU and the I/O racks. Use Honeywell-approved switches only. (see page 204) • Maximum of 2 switches between each CPU’s I/O port and all I/O racks.
  • Page 58 Wire color/pin number white/orange/1 Tx + white/orange/1 Orange/2 Tx - Orange/2 white/green/3 Rx + white/green/3 Blue/4 Unused Blue/4 white/blue/5 Unused white/blue/5 Green/6 Rx - Green/6 white/brown/7 Unused white/brown/7 Brown/8 Unused Brown/8 HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 59: Electrical Considerations

    Controller Grounding PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is installed shall be in accordance with National Electrical Code (ANSI/NFPA 70) and with local electrical codes. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 60: Figure 29 - Cabinet Wiring, Single Chassis

    Pre-Installation Planning - Electrical Considerations Figure 29 – Cabinet Wiring, Single Chassis HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 61: Figure 30 - Cabinet Wiring, Multiple Chassis

    Pre-Installation Planning - Electrical Considerations Figure 30 – Cabinet Wiring, Multiple Chassis Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 62: Figure 31 - Redundant Power Supplies Each With External Fuse And Switch

    For P02 power supply, use 2.5A, slow-blow for 115VAC operation; 2.0A, slow-blow for 230VAC operation. For P24 power supply use 7.0A slow-blow. Figure 31 – Redundant power supplies each with external fuse and switch HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 63: Table 5 - Guidelines For Grouping Wires

    4-20 mA output signal wiring • Slidewire feedback circuit wiring Communications • Low voltage Low voltage alarm relay output wiring • (<50 Vdc/Vac) Low voltage wiring to solid state type control circuits Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 64 Failure to comply with these instructions could result in death or serious injury. Class 1, Division 2 Installations • DO NOT REMOVE OR REPLACE MODULES WHILE CIRCUIT IS LIVE UNLESS THE AREA IS KNOWN NOT TO CONTAIN FLAMMABLE VAPORS. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 65: Figure 32 - Master Control Relay Wiring Example

    Pre-Installation Planning - Electrical Considerations Figure 32 – Master Control Relay Wiring Example Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 66: System Monitor Function Blocks

    Pre-Installation Planning - System Monitor Function Blocks System Monitor Function Blocks The HC900 Controller includes function blocks that enable the user to monitor the status of system functions. When constructing a control configuration, consider adding the following monitoring function blocks to the control strategy: •...
  • Page 67: Rack Installation

    Rack Installation Overview This section contains procedures for installing one or more HC900 Controllers. It is recommended that the information in this section be reviewed before beginning the installation. Familiarity with the overall procedure will help to prevent errors and will promote efficiency in general.
  • Page 68: Table 7 - Site And Equipment Preparation

    Sheet metal screws, steel #10 or M4, for mounting racks in enclosures (4 screws for 4-slot racks, 8 screws for 8- or 12-slot racks) Install (or verify correct installation of) enclosures for HC900 Mount Racks Controllers and ancillary equipment: Table 8 – Mount Rack •...
  • Page 69 External disconnect switches • Fuses at the power source associated with input sensor or output devices for I/O modules. Arrange and organize items to be installed at or near enclosures. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 70: Mount Racks

    Drill and tap for # 10 (or the electrical cabinet. M4) screws. Note: Always mount racks as shown above. That is, never mount vertically, or with backplane horizontal. • Remove the rack from the enclosure. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 71 Note: You may find it easier to postpone this step until after all components have been installed in the rack. Repeat for each rack in your system. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 72: Assemble Controller Rack

    • Ensure that wiring to the Power Supply is disconnected from the site AC source before installing wiring. • Do not remove Yellow/Green wire from grounding stud on the power supply. Failure to comply with these instructions could result in death or serious injury. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 73 Note: Test-points are electrically connected to the backplane of the rack. If the power supply is not properly seated in the backplane connectors, no voltage will be measured at the test points. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 74 Install under power after the controller configuration is complete. (For more information, refer to Battery Installation/Replacement, page 191.) I/O will be installed later. See Page 66. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 75: Table 10 - Assemble C75 Controller Rack

    (For more information, refer to Battery Installation/Replacement, page 191.) Insert the RSM in the See figure in step 1. middle slot and attach with screws at top and bottom. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 76: Assemble I/O Expansion Racks

    1 in figure above. See Table 10 steps 1 and 2 for details. Insert the PSM between the 2 power supplies. Fasten it in place with screws at top and bottom. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 77 Scanner Module immediately to the right of the Power Supply, and secure it in place with the two captured screws in the faceplate. I/O will be installed later. See Page 66. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 78 Rack Installation - Assemble I/O Expansion Racks This page has been intentionally left blank HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 79: I/O Module Installation And Wiring

    Always tighten both terminal block screws before applying field power to the module. • Do not apply energized (“live”) field wiring to an input/output module that is not installed in one of the racks in the HC900 Controller. • Do not operate the controller without a Protective Earth connection.
  • Page 80: Figure 34 - Terminal Block Styles

    Any of the color-coded labels will fit into the door of any terminal block. Use care to ensure that all hardware components match each other, and also match the control strategy in the configuration file. HC900 Process Controller Installation and User Guide Revision 19...
  • Page 81: Remote Termination Panel (Rtp)

    I/O Module Installation and Wiring - Remote Termination Panel (RTP) Remote Termination Panel (RTP) The optional Remote Termination Panel (RTP) provides an easy way to connect the HC900 controller to the field wiring. The RTP integrates some of the typical externally connected components, reducing wiring and setup time.
  • Page 82: Figure 35 - Signal-Wire Grounding

    In this case, it is necessary to adjust wire length so as to ensure adequate flexibility of the twisted wires and to provide clearance sufficient to remove the I/O module. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 83: Figure 36 - Wire-Shield Grounding

    I/O Module Installation and Wiring - Terminal Block-to-Field (Signal) Wiring Figure 36 – Wire-Shield Grounding Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 84: Figure 37 - Terminal Block Jumper Installation

    V+ terminals on the DC Output Module. Refer to the wiring information on each module, given in this section of this manual. Figure 37 – Terminal Block Jumper Installation HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 85: Removal And Insertion Under Power (Riup)

    I/O module, particularly in a system that is actively controlling a process. All of the I/O Module types in the HC900 Controller System include the Removal and Insertion Under Power (RIUP) feature. That is, while the rack is powered, any of the I/O Modules can be removed or inserted: •...
  • Page 86: I/O Module Installation Procedures

    (tagname side out) into the hinged door for each I/O Module. Slotted tabs, molded into the door at top and bottom, hold the label in place. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 87 I/O Module, break off the "key-tabs" in the pattern that identifies each module type. (For a diagram of each key-tab pattern, use the I/O Modules and/or the diagram shown next page. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 88 The orientation of the diagrams below corresponds to the picture of the terminal block, shown in the previous picture. Diagrams for I/O Module Key-Tabs 120/240 VAC, 125VDC Same as 120/240 Vac IN HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 89 Note: 24VDC external power is required if using 6 or more 8-pt. AO modules or 3 or more 16-pt. AO modules. A small slotted screwdriver or paperclip works well; avoid using pencils. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 90 Settings (using Input 1 as example) Single ended (factory setting): 1 and 2 (SINGLE) = ON, 3 and 4 (DIFF) = OFF Differential: 1 and 2 (SINGLE) = OFF, 3 and 4 (DIFF) = ON HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 91 Insert a wire-tie into the top and/or bottom end of the terminal block. Form a bend in each wire to provide strain relief, and secure the wire bundle with the tie. Euro Terminal Block Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 92 Form a bend in each wire to provide strain relief, and secure the wire bundle with the tie. Install I/O modules in racks. Be sure to follow placement guidelines under Heat Rise De-rating page 43. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 93 (screw terminals). The Filler Block mounts in Block cover, Part number the same manner as a Terminal Block (with captured screws at 900TNF-0001. top and bottom). Blank labels are provided for mounting in the hinged door. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 94: I/O Terminal Block Wiring Diagrams

    RTD input at channel two (terminals 4 and 5). Figure 38 and Figure 42 show examples of RTD input wiring (2-wire and 3-wire RTDs). Four-wire RTD inputs are not available. Figure 38 – RTD Inputs HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 95: Figure 39 - Universal Analog Input Wiring Diagram

    Using switches at field devices disconnect the field wiring from power sources before servicing. Failure to comply with these instructions could result in death or serious injury. Figure 39 – Universal Analog Input Wiring Diagram Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 96: Figure 40 - Examples Of Rtd Input Wiring

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 40 – Examples of RTD Input Wiring HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 97: Figure 41 - Analog Input Wiring - Eight Tcs

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 41 – Analog Input Wiring - Eight TCs Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 98: Figure 42 - Analog Input Wiring - Eight Resistance Inputs

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 42 – Analog Input Wiring - Eight Resistance Inputs HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 99: Figure 43 - Analog Input Wiring - Eight Rtds

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Resistance Temperature Device Inputs Figure 43 – Analog Input Wiring - Eight RTDs Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 100: Figure 44 - Analog Input Wiring - Slidewire (Position Proportion Block)

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Slidewires Figure 44 – Analog Input Wiring – Slidewire (Position Proportion Block) HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 101: Figure 45 - 16 Point High Level Analog Input Wiring

    Hazardous voltages exist at terminal blocks. • Using switches at field devices disconnect the field wiring form power sources before servicing. Failure to comply with these instructions could result in death or serious injury. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 102: Figure 46 - 4 Channel Analog Output Wiring Diagram

    Hazardous voltages exist at terminal blocks. • Using switches at field devices disconnect the field wiring form power sources before servicing. Failure to comply with these instructions could result in death or serious injury. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 103: Figure 47 - 8 Channel Analog Output Wiring Diagram

    OUT 11- OUT 12- OUT 13+ OUT 14+ OUT 13- OUT 14- OUT 15+ OUT 16+ OUT 15- OUT 16- 24VDC+ 24VDC- Figure 48 – 16 channel Analog Output Wiring Diagram Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 104 Hazardous voltages exist at terminal blocks. • Using switches at field devices disconnect the field wiring from power sources before servicing. Failure to comply with these instructions could result in death or serious injury. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 105: Figure 49 - Dc Input Module Wiring Diagram

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 49 – DC Input Module Wiring Diagram Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 106: Figure 50 - Dc Input Module Jumper

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 50 – DC Input Module Jumper HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 107: Figure 51 - 32 Point Dc Input Module Wiring

    The AC Input Module has sixteen inputs. An example of AC Input Module wiring is shown in Figure 52. Specifications for this module and for other modules are given in the Specifications section of this manual. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 108: Figure 52 - Ac Input Module Wiring Diagram

    Using switches at field devices, disconnect the field wiring from power sources before servicing. Failure to comply with these instructions could result in death or serious injury. Figure 52 – AC Input Module Wiring Diagram HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 109: Figure 53 - Ac Input Module Jumper

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 53 – AC Input Module Jumper Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 110 Figure 54. Specifications for this module and for other modules are given in the Specifications section of this manual. Isolation Inputs must be powered from external voltage sources. Inputs are isolated from each other and from controller power. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 111: Figure 54 - Ac/Dc Isolated Input Module Wiring

    IN 16 IN 16 125 VDC 125 VDC External External Legend: Legend: Fuse Fuse Disconnect Disconnect User-Supplied Safety Devices User-Supplied Safety Devices Figure 54 – AC/DC Isolated Input Module Wiring Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 112 Hazardous voltages exist at terminal blocks. • Using switches at field devices disconnect the field wiring from power sources before servicing. Failure to comply with these instructions could result in death or serious injury. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 113: Figure 55 - Contact Input Wiring Diagram

    A potential of ± 34 Volts will cause no damage to the module; a reverse polarity power supply connection allows continuous current flow to the loads that are not controlled by the On/Off state of the output circuits. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 114 Hazardous voltages exist at terminal blocks. • Using switches at field devices disconnect the field wiring from power sources before servicing. Failure to comply with these instructions could result in death or serious injury. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 115: Figure 56 - Dc Output Module Wiring Diagram

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 56 – DC Output Module Wiring Diagram Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 116: Figure 57 - Dc Output Jumpers

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 57 – DC Output Jumpers HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 117: Figure 58 - 32 Point Dc Output Module Wiring

    AC output wiring is shown in Figure 59. Specifications for this module and for other modules are given in the Specifications section of this manual. Output Loading Voltage: 85 to 240 Vac Maximum per output: 2.0A resistive load Maximum per module: 8.0A Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 118 Hazardous voltages exist at terminal blocks. • Using switches at field devices disconnect the field wiring from power sources before servicing. Failure to comply with these instructions could result in death or serious injury. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 119: Figure 59 - Ac Output Module Wiring Diagram

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 59 – AC Output Module Wiring Diagram Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 120: Figure 60 - Ac Output Module Jumper

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 60 – AC Output Module Jumper HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 121: Figure 61 - Schematic Example: Relay Output And External Wiring

    Note: specified relay life is 1,000,000 cycles. For applications requiring constant cycling of output, Honeywell recommends using a solid state AC or DC output module. Required Output Fusing Outputs are not fused in the Relay module. Install a fuse for each output at the field device that is appropriate for the load and the wire used.
  • Page 122: Figure 62 - Relay Output Module Wiring Diagram

    Using switches at field devices disconnect the field wiring from power sources before servicing. Failure to comply with these instructions could result in death or serious injury. Figure 62 – Relay Output Module Wiring Diagram HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 123: Figure 63 - Relay Output Module Jumpers

    The Pulse Output functionality uses the digital output available on the module for outputting pulses. Before installing be sure to set the module DIP switches for differential or single ended. See page 78. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 124: Figure 64 - Pulse Counting Wiring

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 64 – Pulse Counting Wiring Figure 65 – Pulse Output Wiring HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 125: Figure 66 - Frequency Wiring

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 66 – Frequency Wiring Figure 67 – Quadrature, Differential, External Power Wiring Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 126: Figure 68 - Quadrature, Single Ended, External Power Wiring

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 68 – Quadrature, Single Ended, External Power Wiring Figure 69 – Quadrature, Differential, HC900 Power Wiring HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 127: Figure 70 - Quadrature, Single Ended, Hc900 Power Wiring

    I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams Figure 70 – Quadrature, Single Ended, HC900 Power Wiring Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 128 I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams This page has been intentionally left blank HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 129: Communications Installation

    All ports are shown. (Availability depends on controller model, see Figure 12 page 23.) Connect communications cabling. For Modbus connections, see page 142. Communication Ports (all ports shown) Revision 18 HC900 Process Controller Installation and User Guide 02/14...
  • Page 130: Table 17 - Links To Controller Communication Ports

    Table 18.) Connect from each CPU (A and B) to the OI. RS-485 Modbus master Belden #9271 (or Refer to device’s port 3-Plug (controller is equivalent) instructions connector slave) HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 131 C75 CPU A’s I/O port to 100Base-T Scanner 2’s I/O A port. CAT5 cable IO with RJ- 45 connectors C75 CPU B’s I/O port to Scanner 2’s I/O B port. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 132 From this switch to each Scanner 2’s I/O B port. One (1) additional switch may be used, for a total of 2 switches between CPU B and the I/O racks. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 133: Connecting The Operator Interface To The Controller

    Phoenix #1840379 (or Connector (3-pin) (Supplied with the equivalent) for C30/C50 controller CPU module) Phoenix 1803581 for C75. 047260 Ferrite cable clamps (Supplied with the operator interface) 089037 Nylon cable ties Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 134: Connecting The Hc900 Controller To A Pc With The Designer Software

    Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Connecting the HC900 Controller to a PC with the Designer Software To establish communications between the HC900 controller and the Process Control (HC) Designer configuration software use any of the following methods.
  • Page 135: Figure 71 - A Direct Serial Rs-232 Connection

    PC port and the controller. In general, the faster the baud rate the better the performance, however, your PC may not communicate reliably at the faster baud rates. (Refer to the HC900 Designer Software User’s Guide or its respective on-line help, Setting Up PC Com Ports and Connections - PC Serial Com Port Setup and Utilities Worksheet - Set Controller Serial Port, for details on this step).
  • Page 136: Table 19 - Null Modem Cable Connections

    Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software RS-232 Direct Link to PC Configuration Tool The Controller can be connected directly to the PC, in which case a Null Modem Cable is required. The Null Modem Cable can be ordered from Honeywell (Part# 50004820-501).
  • Page 137: Figure 72 - Rs-232 Remote Access Via Modems

    Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Rs-232 Remote Connection to PC Configuration Tool The Controller can also be connected remotely by a set of modems, which are available from third-party suppliers. A Null Modem Cable is used between the Controller and the modem, shown in Figure 72 and shown in Table 19.
  • Page 138: Figure 73 Modem Connection

    Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software B. Modem Connection Figure 73 Modem Connection HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 139 Step Procedure Connect a modem to the HC900 controller’s for a list of approved modems, their settings, and the connection specifics. On the PC, check on the Utilities Worksheet in the HC Designer software to see if the PC modem is properly installed.
  • Page 140 Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Modem requirements Most commercially available modems can be used with the HC900 Controller. The modem must have the following capabilities: • RS-232 interface • Auto answer •...
  • Page 141 Start up a PC terminal program such as Hyperterminal. Configure the PC COM Port for 1200, 2400, 4800, 9600*, 19200*, 38400*, 57600 baud (must match Baud Rate configured in HC900 Controller), no parity, 1 stop bit, and 8 data bits. *recommended Establish communications with the modem.
  • Page 142 Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Modem configuration examples Below are procedures for setting up the following commercially available modems: • 3Com US Robotics 56K Data/Fax External Modem • Zoom 56K Dualmode External Modem (page 132) •...
  • Page 143 Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Step Action Key in the following command string: AT Y0 Then, press the ENTER key. The modem should respond with OK. Key in the following command string: AT &B1...
  • Page 144 Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Zoom 56K Dualmode External Modem Step Action Connect the modem to a PC. If your PC’s RS-232 port has a 25-pin connector, use a DB-25 male to DB-25 female RS-232 cable. If your PC’s RS-232 port has a 9-pin connector, use a DB-25 male to DB-9 female modem cable.
  • Page 145 Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Best Data 56SX Data Fax External Modem Step Action Connect the modem to a PC. If your PC’s RS-232 port has a 2- pin connector, use a DB-9 male to DB-25 female modem cable.
  • Page 146 Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software SixNet VT-MODEM Industrial External Modem Step Action Connect the modem to a PC. If your PC’s RS-232 port has a 25 pin connector, use a DB-9 male to DB-25 female modem cable.
  • Page 147: Figure 74 - Redundant Networks (See Table 20)

    Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Connecting C75 Redundant Ethernet to a PC with HC Designer or other applications Only use Shielded CAT 5 cable IO for network connections. See Figure 74 and Table 20.
  • Page 148: Table 20 - Redundant Network Connections In Figure 74

    Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Table 20 – Redundant Network connections in Figure 74 Key No. Connection/Description Connect CPU-A E1 port to Ethernet switch (3a) Connect CPU-B E1 port to Ethernet switch (3a)
  • Page 149: Table 21 - Redundant Network Connections

    Make sure the PC has 2 Ethernet NICs (Network Interface Cards) installed and enabled. Connect Ethernet 10Base-T straight or crossover cables to the HC900 controller’s E1 and E2 ports. Connect the other end of the cables to the PC’s Ethernet ports.
  • Page 150: Figure 75 - Two Redundant Systems With Pc Supervision

    Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Two redundant systems with PC supervision Figure 75 – Two redundant systems with PC supervision C. Direct Ethernet Connection to one HC900 controller ATTENTION: Always observe the wiring/cabling guidelines on page 45.
  • Page 151 On the PC, use the Utilities Worksheet in the HC Designer software to connect to the controller over Ethernet. Every HC900 controller is shipped with the default IP address of 192.168.1.254 and Subnet Mask of 255.255.255.0. You can use these network parameters initially for testing or configuration use.
  • Page 152 Consult your IT department or network administrator for allocating IP addresses to the controllers if required. You will need to set each controller’s IP address prior to network connection since every HC900 controller is shipped with the default IP address of 192.168.1.254. Placing multiple controllers on the same network before they have been given unique IP addresses will cause problems.
  • Page 153 Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software Step Procedure You may now access any controller on the network for configuration access by assigning Network as the Port and the respective IP Address as the Address of the controller.
  • Page 154: Connecting The Hc900 Controller To Modbus Device(S)

    Use HC Designer software to configure the controller’s RS-485 port as a master or slave. Install resistor as shown for terminated devices except HC900. For terminating HC900, do not install resistor. Instead, set internal DIP switches for termination (page 36).
  • Page 155: Figure 77 - Rs-485 Modbus Slave Wiring With Isolation

    Communications Installation - Connecting the HC900 Controller to Modbus device(s) Figure 77 - RS-485 Modbus slave wiring with isolation For XYR 5000 base stations, if the RS-485 network is intermittent or fails completely over short durations and recovers after the controller is power cycled, the need for additional port biasing may be required.
  • Page 156: Figure 78 - Xyr 5000 Rs-485 Modbus Connections With Isolator

    Communications Installation - Connecting the HC900 Controller to Modbus device(s) Figure 78 shows recommended installation procedure for using an external isolator and additional port bias. Figure 78 - XYR 5000 RS-485 Modbus connections with isolator RS-232 Modbus Connections Connect to the RX, TX, and ground pins of the controller’s 3-pin RS-232 port. (See page 36 for RS-232 DIP switch settings.)
  • Page 157: Operating Characteristics

    Diagnostics section in this user manual. Overview The HC900 Controller components begin operation as soon as power is applied, and continue until power is removed. The operation of the system varies according to the following interacting factors: •...
  • Page 158: Figure 79 - Warm Start Operation

    Mode switch on the controller or RSM, or by exiting the Program mode at an operator interface.) • When initiated by the user (after download with Cold Start selected, or any transition from PROGAM Mode to RUN Mode.) HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 159: Figure 80 - Cold Start Operation

    Operating Characteristics - Power Down / Power Up Figure 80 – Cold Start Operation Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 160: Controller Modes

    Controller Modes The HC900 Controller includes three operating modes. The purpose of each mode is described immediately below, and salient characteristics of each are described in Table 22. The functions of the Mode Switch are described in Table 23, and the procedures that the controller performs in transitions between modes are described in Table 24.
  • Page 161 • EXECUTE prudent control actions (such as placing all control loop in the Manual Mode). Failure to comply with these instructions may result in product damage. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 162: Table 22 - Controller Operating Modes

    Time Proportional Output (TPO): Same duty cycle as in last active state • PPO and TPSC Outputs: digital outputs are Off to freeze the motor position. • Analog output: same current as previous (last active current level) HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 163: Table 23 - Mode Switch Functions

    Transfers all primary tasks to the Reserve Controller, establishing this controller as the new Lead. Does not affect controller mode. Turn key to Failover and hold it there until both Reserve lights are on, then release key. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 164: Table 24 - Controller Behavior In Mode Transition

    Freeze output module channels. Freeze Force LED indications on all output modules. OFFLINE Function Block execution starts immediately. Any calibration process that was in progress is immediately aborted, and the results are discarded. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 165: File Download/Upload Functions

    Pathways for file transactions between the controller and computer devices external to the controller are shown in Figure 82. Figure 82 – Pathways for Upload/Download Transactions Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 166: Table 25 - Configuration File Downloading

    Firmware Download provides a mechanism to upgrade the firmware in your CPU and Scanners. It is available in Program or Program Locked modes only. Specific instructions are provided with the upgrade files. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 167: Redundant Operating Characteristics

    Overview This section describes operating characteristics specific to redundant controllers. In a redundant HC900 system, the Lead Controller performs all primary tasks including interfacing with remote I/O racks, communicating with a local HMI, exchanging data with peer controllers, interfacing with Modbus slave devices, and communicating with a Host PC application.
  • Page 168: Steady State Operations

    • Lead Controller responds to communication messages from host devices on the Supervisory Network and RS-485 interfaces • Lead Controller handles communications with HC900 peers • Lead Controller handles communications with Modbus RTU slave devices • Lead and Reserve exchange system status data to determine conditions for failover.
  • Page 169 Redundant Operating Characteristics - Steady State Operations Execution time HC900 Controllers are designed to execute control functions within fixed scan cycles for analog data types and logic data types. In redundant controllers, the maximum scan time is 500ms for analog data types and 53ms for logic data types.
  • Page 170: Failover

    Loss of communications to Operator Interface − Loss of communications with a Peer controller • During the transition from the Lead to the Reserve, analog and digital output status is maintained at the I/O racks. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 171: File Download/Upload Functions

    − Redundant Link Status – status of communications between Lead and Reserve controllers. − Lead CPU status − Reserve CPU status − Scanner status File Download/Upload Functions See page 153. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 172 Redundant Operating Characteristics - File Download/Upload Functions This page is intentionally left blank. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 173: Diagnostics And Troubleshooting

    Diagnostics and Troubleshooting Overview The HC900 system incorporates a comprehensive set of diagnostic tools that test hardware and software operation. Diagnostic software elements are contained in each system component. The diagnostic elements that are executed at any given time depend on operating conditions such as current operating mode and the current status of hardware and software.
  • Page 174: Figure 85 - Led Indicators On Controller Cpus (See Table 26)

    Diagnostics and Troubleshooting - Controller CPU indicators Figure 85 – LED Indicators on Controller CPUs (See Table 26) HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 175: Table 26 - Led Indications On Controller Cpus

    Flash for activity I/O port Upper LED Yellow (On/Off) On for 100Base-T, Off for 10Base-T Lower LED Green (On/Off/Flash) On for connection, Off for no connection, Flash for activity Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 176: Table 27 - Controller Status Led Diagnostics

    6. Replace rack This diagnostic will cause the HWOK pins of the analog and fast logic “System Monitor” blocks (AYSY and FSYS) to be turned off. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 177 RAM and the controller continues to operate normally. This diagnostic will cause the HWOK pins of the AYSY and FSYS blocks to be turned off. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 178 “Reserve CPU status LED is and time when the lead and reserve Diagnostics” indicating the are synchronized. display. failure, see Real- Time Clock Diagnostics in the “Reserve Diagnostics Overview” dialog box. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 179 • Scanner 2, I/O rack, or power- supply is defective. • C75 module is defective • A bad channel has been detected on one of the modules. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 180 Supply replace the defective supply. DIAGNOSTICS in Diagnostics in ASYS and FSYS blocks’ HW the associated “Rack OK pins are turned off. rack’s “Rack Diagnostics” Diagnostics dialog box. Overview” display. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 181 NETWORK failure, Lead Port PORT E2 in the E1: Network Port “Reserve CPU Diagnostics or Diagnostics” Lead Port E2: display. Network Port Diagnostics in the “Reserve Diagnostics Overview” dialog box. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 182 Diagnostics and Troubleshooting - Controller CPU indicators HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 183: Scanner Indicators

    Off when the host is removed from the link. NOTE: These LEDs indicate activity on the communication port, they are controlled by hardware (PHY chip), not by software. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 184: Table 29 - Scanner Led Diagnostics

    10. Ensure that the Scanner and Controller CPU software versions are compatible. If not, perform a firmware upgrade. 11. Replace the expansion rack’s power supply. 12. Replace the expansion rack. 13. Replace the main CPU. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 185 12. Replace the main CPU. The modules installed do not No action is taken. Verify that the correct modules agree with those required by the are installed for the configuration. configuration. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 186 Scanner determines actions. the condition, not the module itself. One of the power-supplies failed. No action is taken Replace the power-supply HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 187: I/O Module Indicators

    For Inputs, indicates On or Off status output) of the field input even if Forced to the opposite state. For Outputs, indicates On or Off status of the output including if Forced. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 188: Table 31 - I/O Module Led Diagnostics

    This diagnostic should only result in the factory. √ √ √ √ √ √ Shift Register The loopback test of the shift Replace module register failed. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 189: Table 32 - Bad I/O Channel Diagnostics

    The number of configured channels in the Reconfigure the DO function DO function block exceeds the number of block. hardware channels on the DO card. Replace DO card with correct number of channels. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 190: Table 33 - Led Indications On Ethernet Switch

    Remains On as long as host is present; Off when the host is removed from the link. NOTE: These LEDs indicate activity on the communication port, they are controlled by hardware (PHY chip), not by software. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 191 Diagnostics and Troubleshooting - This page is intentionally left blank. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 192: Analog Calibration

    Only trained and authorized personnel should perform the procedures in this section. Failure to comply could result in death or serious injury. ATTENTION For calibration procedures, refer to the Operator Interface manual or Process Control Designer manual. Revision 18 HC900 Process Controller Installation and User Guide 02/14...
  • Page 193 The calibration device(s) must have the following precision characteristics: • TC, mVolts, Volts inputs: 1 microvolt resolution • Ohms, RTD inputs: .01 ohm resolution • 4-20mA inputs: 4 microamp resolution Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 194: Figure 88 - Terminal Board Connections For Ai Calibration

    Analog Calibration - Overview Figure 88 – Terminal Board Connections for AI Calibration HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 195: Figure 89 - Terminal Board Connections For Ao Calibration

    Figure 89. The specifications of the meter must be consistent with calibration requirements. See page 91 for terminal connections for 8 and 16 channel AO. Figure 89 – Terminal board Connections for AO Calibration Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 196: Removal And Replacement Procedures

    All of the modules (input, output, RSM, PSM) available for use in the HC900 Controller have a RIUP designation. That is, they can be Removed and Inserted Under Power, where "power" refers to DC power at the backplane of the rack.
  • Page 197: Table 34 - Power Supply Replacement (All Except C75)

    Replacing the Power Supply The power supply for the HC900 Process Controller is available in two models and is used in the local (controller) rack and in the remote (I/O expansion) racks, in 4-, 8-, and 12-module sizes. This reduces required inventories of spare parts, and also simplifies removal and replacement procedures.
  • Page 198 Ensure power can be applied safely, and use the external (user-supplied) switch to re-connect power to the power supply. Using a meter and the test points on the face of the power supply, ensure that voltages (measured on the backplane) are within specifications. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 199: Table 35 - Controller Module Replacement

    If using the Ethernet port for configuration, use the Designer software to set the proper network address. Download the configuration. Set the Real-Time Clock. If all status indications are green, power may be restored to the I/O modules per the application's procedures. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 200: Table 36 - Scanner Module Replacement

    AC power source. The Scanner Module should resume communications with I/O modules in the rack and with the Controller Module with which it is connected. Check status indications at the Scanner Module, at the Controller Module, and at the OI. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 201: Table 37 - Riup: Potential Hazards And Recommended Actions

    I/O module, particularly in a system that is actively controlling a process. All of the I/O Module types in the HC900 Controller System include the Removal and Insertion Under Power (RIUP) feature. That is, while the rack is powered, any of the I/O Modules can be removed or inserted: •...
  • Page 202: Table 38 - I/O Module Replacement

    Replace the terminal block on the module. If the rack was powered-down for the procedure, restore power to the rack. Re-connect signals to field devices. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 203 CAUTION Installing the backup battery when the CPU is not initialized will cause undue battery drain. Do not install or replace the backup battery until after site power is applied. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 204: Table 39 - Installing Backup Battery (Cpu Not Initialized)

    (front) end of the battery. While maintaining proper orientation (battery toward the left), slide the battery holder into the slot in the Controller Module until it snaps into place. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 205: Table 40 - Replacing A Backup Battery (Cpu Powered))

    (front) end of the battery. While maintaining proper orientation (battery toward the left), slide the battery holder into the slot in the Controller Module until it snaps into place. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 206: Specifications

    (151.7mm) D (rear mounting plate extends redundant power height to 6.9” (175.3mm) support 12 I/O slot chassis 5.4”(137mm) H x 22.5”(571.5mm) W x 6.0” (151.7mm) D (rear mounting plate extends height to 6.9” (175.3mm) HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 207 Transfer Time Operating Modes Run (No configuration download in this position) Run/Program (Download allowed) Program (Outputs Off, initialization on download). Offline mode is available via software selection (for AI calibration). Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 208 16-character tagname, 16-character descriptor,6-character units of measure (analog only), 6 character on/off state (digital only) Variables (Read/Write) Up to 2048 Variable Identification 16-character tagname, 16-character descriptor,6-character units of measure (analog only), 6 character on/off state (digital only) HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 209 For remote connection to Designer software, requires external modem at controller, 1200 baud to 57.6KB RS-485 Ports Ports per controller Two, (connector supplied), Honeywell or Modbus RTU protocol. Only one port for 1042/ 559 operator interface support. Cable type 2-wire plus shield, Belden 9271 or equivalent 1042, 559 Distance from 2000 ft.
  • Page 210 RJ-45 connectors Network Switch to PC 100m /328 ft shielded Ethernet CAT5 cable with RJ-45 connectors Controller to 1042 Operator Shielded cable, Twisted pair 610m /2000 ft Interface HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 211 0 Hz to 14 Hz— amplitude 2.5 mm amplitude 2.5 mm (peak-to-peak) (peak-to-peak) 14 Hz to 250 Hz— 14 Hz to 250 Hz— acceleration 1 g acceleration 1 g * Applies up to 40C Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 212: Hc900 Analog Input Ranges Vs. Umc800 Analog Input Ranges

    When using the Designer Software configuration software to convert UMC800 configuration files to HC900 configuration files, the HC900 range to the left of the UMC800 data will be used by the conversion program. There may also be UMC800 ranges that are not supported by the HC900 Controller. For these ranges the conversion process will default the range data to a null, not-programmed, range.
  • Page 213 Specifications - HC900 Analog Input Ranges vs. UMC800 Analog Input ranges Type Range Range High (Reference): Corresponding UMC800 Input type and range 3100 S 32 2912 F 31 -184 T –200 400 C 40 -300 T –328 752 F 41...
  • Page 214 Specifications - HC900 Analog Input Ranges vs. UMC800 Analog Input ranges Type Range Range High (Reference): Corresponding UMC800 Input type and range mV -50 50 -100 mV –100 100 -500 mV –500 500 0 10 V -1 1 V -2 2...
  • Page 215: System Sizing And Availability Summary

    Steps per sequence Support of dual port scanner Tag descriptor Quantity based on available memory Text bytes Quantity based on available memory Variables 2000 2000 2000 2000 Variables in a Recipe Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 216: Fiber Optics Recommendations

    Specifications - Fiber Optics Recommendations Fiber Optics Recommendations Honeywell recommends that you use the following equipment for extended distances: Table 43 – Fiber Optics Equipment Recommendations Ethernet Switch Moxa Unmanaged Ethernet Switch model EDS-308-MM-SC with (6) 10/100 Ethernet ports, (2) multi-mode fiber ports with SC...
  • Page 217: Figure 91 - Extended Distance Example #2

    Specifications - Fiber Optics Recommendations Figure 91 – Extended Distance Example #2 Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 219: Appendix - Installation Of Remote Termination Panels (Rtps)

    Appendix - Installation of Remote Termination Panels (RTPs) Overview The Remote Termination Panel (RTP) provides an easy way to connect the HC900 controller to the field wiring. The RTP integrates some of the typical externally connected components, reducing wiring and setup time.
  • Page 220: Analog Input

    Install AI module label onto the module connector cover. • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 221 Transmitter Milliamp: Externally Powered SW9 is the red power switch for 24 volt supply. Module RIUP is not affected by using the RTP. See page 214 for RTP internal schematic. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 222: Figure 93 - Analog Input Terminals

    Transmitter Input 8 Input 8 Input 8 Transmitter Transmitter Transmitter Transmitter Transmitter Transmitter Transmitter Transmitter Transmitter Transmitter Transmitter Transmitter Figure 94 – Two–wire transmitter connections with common 24 VDC supply HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 223: Figure 95 - Milliamp Input Connections With 250 Ohm Shunt Resistance

    Input 7 Input 7 Input 1 Input 1 Input 4 Input 4 Input 6 Input 6 Input 2 Input 2 Input 8 Input 8 Figure 96 – Volt, millivolt input connections Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 224: Figure 97 - Three-Wire Rtd Input Connections

    Input 1 Input 2 Input 2 Input 4 Input 4 Input 8 Input 8 Input 3 Input 3 Input 6 Input 6 Figure 98 – Two-wire RTD or ohm input connections HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 225: Figure 99 - Slidewire Feedback Connections For Actuators

    ±0.57% Range (1.540°C) ±0.67% of Range 10Ω Cu. RTD ±0.1% of Range ±0.07% Range (0.140Ω) ±0.17% of Range 200Ω OHMS ±0.1% of Range ±0.04% Range (0.004mV) ±0.14% of Range 0-10mV LINEAR Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 226 SW 5 (2) 250 Ohm SW 6 (2) 250 Ohm SW 7 (2) 250 Ohm SW 8 (2) 250 Ohm 8(1) 7(1) 6(1) 5(1) 4(1) 3(1) 2(1) 1(1) SW 9 HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 227: Relay Output

    Install relay output module label onto the module connector cover. • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 228 As shown in the schematic, each switch is SPST and opens and closes one lead of the relay wiring. If your application requires opening and closing both sides of the load wiring, then an external DPST switch is required. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 229 Appendix - Installation of Remote Termination Panels (RTPs) - Relay Output Relay Output RTP Internal schematic HC900 Terminal Block Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 230 RTP Cable wire positions and colors (applies to 8 point AI and Relay Output) Twisted Pair Number HC900 Module TB Position RTP J1 Plug Connector Color Black Black White Black Green Black Blue Black Yellow Black Brown Black Orange White Green Blue HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 231: Analog Input/Digital Input/Digital Output/Analog Output

    Install AO module label onto the module connector cover. • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 232 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 HC900 Process Controller Installation and User Guide Revision 19...
  • Page 233 Install 16 point contact DI module label into the module connector cover. • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 234 Install 16 point DC DI module label into the module connector cover. • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 235 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 Install jumper wires DC Supply Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 236 Install 16 point AC DI module label into module connector cover. • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 237 Install 16 point DC DO label into the module connector cover. • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 238 See page 73. ATTENTION: SW1 only disconnects the positive terminal, not both sides of the DC power. See page 230 for RTP internal schematic. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 239 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 Install jumper wire DC Supply Note: DC Outputs provide electronic overload protection in the module, but adding a fuse (see picture) protects the wiring. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 240 Install 8 point AC DO label into the module connector cover. • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 241 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 Note: AC Outputs are individually fused in the module, but adding a fuse here protects the wiring. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 242 Color Black Black White Black Green Black Blue Black Yellow Black Brown Black Orange White Green Blue RTP Internal schematic (Applies to 4 AO, 16 DI, 16 DO, 8 DO) HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 243 Install 8 point Analog Output label into the module connector cover. • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 244 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 EXT +24V Install 24V wires as shown: 22 to 10 EXT 24V RTN 22 to 12 24VRTN to 9 External 24VDC supply 24VRTN to 11 HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 245 HC900 Module TB Position RTP A J1 Plug Connector Color Cable A Black Black White Black Green Black Blue Black Yellow Black Brown Black Orange White Green Blue RTP A HC900 Terminal Block Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 246 Install 16 point Analog Output label into the module connector cover. • Connect both shield drain wires to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 247 Install 16 point Analog Input label into the module connector cover. • Connect both shield drain wires to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 248 ATTENTION: SW1 opens current loop on the ground side so that RIUP of module is possible, but voltage is still present on the positive side at RTP and module terminals. See page 242 for RTP internal schematic. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 249: Figure 100 Voltage Input Connections

    Additionally, on RTP A connect the following terminals: 3-22, 4-23, 7-24, 8-25, 15-26, 16-27, 19-29, 20-30 On RTP B connect the following terminals: 1-22, 2-23, 5-24, 6-25, 13-26, 14-27, 17-28, 18-29 Figure 101 Current connections with 2-wire transmitter Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 250 Install 32 point DC DO label into the module connector cover. • Connect both shield drain wires to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 251 Note: SDC- refers to the switched negative side of the DC supply. Note: Terminals 9 and 11 (DC-) are connected through the RTP cable. Same for terminals 10 and 12 (DC+). Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 252 Install 32 point DC DI label into the module connector cover. • Connect both shield drain wires to the grounding bars at the base of the HC900 rack. All field-wiring shields must be grounded as described in the shield grounding section (page 70).
  • Page 253 Note: SDC+ refers to switched positive side of the DC supply. Note: Terminals 9 and 11 (DC-) are connected through the RTP cable. Same for terminals 10 and 12 (DC-). Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 254 Twisted Pair Number of HC900 Module TB Position RTP A J1 Plug Connector Color Cable A Black Black White Black Green Black Blue Black Yellow Black Brown Black Orange White Green Blue HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 255 Twisted Pair Number of HC900 Module TB Position RTP B J1 Plug Connector Color Cable B Black Black White Black Green Black Blue Black Yellow Black Brown Black Orange White Green Blue Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 256 RTP to rail Step Action Mounting screws must be installed at each end of the mounting rail; with additional screws approx. every 8"(203mm) to prevent twisting of the rail. HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 257 Insert other side of DIN rail at B, and push B over the rail to snap into place. To remove, using slot screwdriver to lift C up gently (plastic is fragile) to disengage at B. Lift up and over rail, then disengage at A. Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 258: Declaration Of Conformity

    Declaration of Conformity - Analog Input/Digital Input/Digital Output/Analog Output Declaration of Conformity HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 259: Atex Certification

    ATEX Certification - Analog Input/Digital Input/Digital Output/Analog Output ATEX Certification Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 260 ATEX Certification - Analog Input/Digital Input/Digital Output/Analog Output HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 261: Index

    Controller Rack, 18 I/O Expansion Rack, 19 custom graphics, 32 I/O expansion rack assembly, 64 I/O implementation, 28 I/O Installation Procedures, 74 I/O Module Diagnostics, 176 DC Input Module Wiring, 92 Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 262 I.O network, 29 mounting racks, 58 I/O wiring, 45 modes of operation, 155 network, 29 network connections, 137 Null Modem Cable, 124 networks, 135 operating characteristics, 1, 145, 155 peer-to-peer, 30 HC900 Process Controller Installation and User Guide Revision 19 06/14...
  • Page 263 Signal Grounding, 70 Simple Mail Transport Protocol, 33 Site and Equipment Preparation, 56 SMTP, 33 sockets, 31 Specifications, 194 SpecView32, 32 Status, 145 Subnet Mask, 30 System Monitor Function Blocks, 54 Revision 19 HC900 Process Controller Installation and User Guide 06/14...
  • Page 264: Sales And Service

    Phone: +(822) 799 6114 Fax: +(822) 792 9015 For more information To learn more about SmartLine Transmitters, visit www.honeywellprocess.com Or contact your Honeywell Account Manager Process Solutions Honeywell 1250 W Sam Houston Pkwy S Houston, TX 77042 Honeywell Control Systems Ltd...

Table of Contents