INFORMATION
In  case  of  error  code  AH  and  no  interruption  of  the
disinfection  function  occurred  due  to  domestic  hot  water
tapping, following actions are recommended:
▪ When  the  Domestic  hot  water  >  Type  >  Reheat  or
Reheat  +  sched.  is  selected,  it  is  recommended  to
program the start­up of the disinfection function at least
4  hours  later  than  the  last  expected  large  hot  water
tapping.  This  start­up  can  be  set  by  installer  settings
(disinfection function).
▪ When the Domestic hot water > Type > Scheduled only
is  selected,  it  is  recommended  to  program  a  Storage
eco  3  hours  before  the  scheduled  start­up  of  the
disinfection function to preheat the tank.
4.5.2
Instant DHW (no tank installed)
When  there  is  a  demand  for  hot  water  tapping,  the  boiler  provides
DHW instantly. The DHW temperature is visible on the boiler's main
display.
Using the instant DHW home page
Depending on the user profile, the user interface gives you either a
basic or a detailed home page.
User profile = Basic
Tue
01:03
DHW
44°C
Desired temperature
To adjust the instant DHW temperature
1 Go to the instant DHW home page.
2 Press 
 or 
 to adjust the instant DHW temperature (DHW).
The instant DHW set point temperature may NOT be below 40°C.
4.5.3

Tank

The following modes are only applicable if a tank is installed and are
set by the installer.
To determine which DHW tank mode you are using (method 1)
Check the installer settings table filled in by the installer.
To determine which DHW tank mode you are using (method 2)
Prerequisite: User profile = Detailed.
1 Go to the DHW tank temperature home page (Tank).
2 Check which icons are displayed:
If... is displayed
Reheat mode
Scheduled mode
Scheduled + reheat mode
 
EHYHBH05AA + EHYHBH/X05+08AA + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355632­1 – 2013.05
User profile = Detailed
Tue
01:03
44°C
DHW
Desired temperature
Then the DHW tank mode =...
Reheat mode
In  reheat  mode  ( ),  the  DHW  tank  continuously  heats  up  to  the
desired temperature (example: 50°C).
T t
1
60°C
50°C
40°C
15°C
00:00
07:00
▪ T
: DHW tank temperature
t
▪ t: Time
INFORMATION
When  the  DHW  tank  booster  mode  is  active,  the  risk  of
space  heating/cooling  and  capacity  shortage  comfort
problems  is  significant.  In  case  of  frequent  domestic  hot
water  operation,  frequent  and  long  space  heating/cooling
interruptions will happen.
Scheduled mode
In  scheduled  mode  ( ),  the  DHW  tank  produces  hot  water
corresponding  to  a  schedule.  The  best  time  to  allow  the  tank  to
produce hot water is at night, because:
▪ The space heating demand is lower
▪ Electricity tariffs are lower
Example: 
T t
1
2
60°C
50°C
40°C
15°C
00:00
07:00
▪ T
: DHW tank temperature
t
▪ t: Time
▪ Initially,  the  DHW  tank  temperature  is  the  same  as  the
temperature  of  the  domestic  water  entering  the  DHW  tank
(example: 15°C).
▪ At 00:00 the DHW tank is programmed to heat up the water to a
preset value (example: Storage comfort = 60°C).
▪ During  the  morning,  you  consume  hot  water  and  the  DHW  tank
temperature  decreases.  As  long  as  the  DHW  tank  temperature
stays above 40°C, hot water is available.
▪ At 14:00 the DHW tank is programmed to heat up the water to a
preset  value  (example:  Storage  eco  =  50°C).  Hot  water  is
available again.
▪ During  the  afternoon  and  evening,  you  consume  hot  water  again
and the DHW tank temperature decreases again.
▪ At 00:00 the next day, the cycle repeats.
4 Operation
3
2
4
t
14:00
21:00
4
3
5
t
14:00
21:00
User reference guide
11