Measurement Verification (P710 To P713) - Siemens HydroRanger 200 Instruction Manual

Table of Contents
P708 Volume Rate Display [6 relay model]
The rate of change of volume in percent of maximum volume per minute.
Please note that this feature applies to the HydroRanger 200 6 relay model only.
Primary Index
Values
Related
This value is used internally to calculate inflow in pumped volume applications (P622=3).
Press READING

Measurement Verification (P710 to P713)

P710 Fuzz Filter
Use this to stabilize the reported level, due to level fluctuations (such as a rippling or
splashing liquid surface) within the Echo Lock Window (P713).
Primary Index
Values
Altered by
Related
This value (in % of Span, P007) is automatically altered when Maximum Process Speed
(P003) is altered. The higher the value entered, the greater the fluctuation stabilized.
7ML19985FC03
Single Point Model
Global
Range: -999 to 9999 (view only)
P622 Inflow / Discharge Adjust
to toggle between percent and volume.
Single Point Model
Global
Range: 0 to 100 (0 = off)
P003 Maximum Process Speed
P007 Span
P713 Echo Lock Window
HydroRanger 200 – INSTRUCTION MANUAL
Dual Point Model
Transducer
Dual Point Model
Transducer
Page 187