Installation Procedure - Haier AB092XCERA Service Manual

X multi series
Hide thumbs Also See for AB092XCERA:
Table of Contents

5. Installation procedure

1. Drill a hole in the wall and insert the connecting pipe and wire through a PVC wall-through tube
purchased locally. The wall hole shall be with a outward down slope of at least 1/100. (See
Figure 1)
2. Before drilling check that there is no pipe or reinforcing bar just behind the drilling position.
Drilling shall avoid at positions with electric wire or pipe.
3. Mount the unit on a strong and horizontal building roof. If the base is not firm, it will cause
noise, vibration or pipe broken and refrigerant leakage (see Figure 6).
4. Support the unit firmly.
5. Change the form of the connection pipe, connection wire and drain pipe so that they can go
through the wall hole easily.
When installing the ceiling concealed type indoor unit, a specially designed return air bellows
shall be installed, as shown in Figure 3, Figure 4.
Figure 3
Ceiling
Figure 4
Air outlet grille
Air supply
No obstacles
within 1 m(0Pa)
Each air return and supply duct should fix to the floor precast slab by using an iron stand. Use
glue to seal the interface closely. Recommend the distance between the air return duct and the
wall is more than 150mm.
Installing building roof
0.5m(0Pa)or 5m(50Pa)
Unit
Air outlet duct
Air supply
Unit
Return air
-65-
A
Return air bellows
Return air
Return air bellows