2. System Configuration
MELSEC GOT
@I Communication module
A8GT-RS4-EU (Used for direct connection to the CPU)
A7GT-BUS2-EU (Used for Bus Connection Module connection)
@ Connection cable
A8GT-AC30R4-EU (Used for direct connection to the CPU)
A8GT-A1 SC30NB-EU (Used for Bus Connection Module connection)
@ EMC Box
A8GT- EL-BOX- EU, A8GT-STN- BOX- EU
@ Cable clamp
Model AD75CK cable clamp
a]
PC CPU, base unit, Power Supply Module, and input module used
A1 SCPU, A1 S32B, A1 S62PEU, A1 SX80S1, A1 SX80S2
Connect and wire the MELSEC-GOT series equipment as instructed below.
If the MELSEC-GOT series equipment is configured in a way that differs from the fol owing
instructions then the system will not comply with EMC specifications.
@
Be sure to install a ferrite core when the Power Supply Module's power wires and
ground wires are within 100mm (3.94 inch) of the Power Supply Module's terminal
block. The ferrite core is packaged with the Power Supply Module. (ZCAT303E-1330
made by TDK.)
@
Be sure to connect the ground wire (LG wire) to the protection conductor.
@I Be sure to install a FG mesh wire between the Power Supply Module's FG terminal
and the FG mesh wire ground area of the EMC Box to prevent radiated noise frc:)m the
GOT and Communication Module. The FG mesh wire is packaged with the 130wer
Supply Module.
@
Be sure to install the FG mesh wires of the Bus Connection Module and Serial Com-
munication Module to the FG mesh wire ground area of the EMC Box to prevent
radiated noise from the GOT and Power Supply Module.
@
Be sure to peel the shield covering from the white areas (2 areas) of the cable covering
of the connection cable (A8GT-AC30R4-EU, A8GT-A1 SC30NB-EU) to the GC:IT and
PC CPU control panels using cable clamps to prevent radiated noise from tht, = con-
nection cable.
@ To obtain an electric contact in the control panel installed in the EMC Box be sure to
remove the paint from the control panel surface where the installation will be made.
POINT
For details regarding
above, refer to the system configuration precaution items in llems
2.2.2 and 2.3.2