Honeywell MPA2C3 Installation Manual page 151

Access control unit
Hide thumbs Also See for MPA2C3:
Table of Contents
Reader Support
Output Voltage Range at RJ45 reader interfaces
when 12V internally powered
Maximum current output at RJ45 reader
interfaces
when 12V internally powered
Output Voltage Range at RJ45 reader interfaces
when 12V internally powered
Maximum current output at RJ45 reader
interfaces
when 12V internally powered
Voltage Range at RJ45 reader interfaces
when external voltage is applied at
Door 1: V - Ext.V Readers @ push in terminal
block
Max output current at RJ45 reader interfaces
when external voltage is applied at
Door 1: V - Ext.V Readers @ push in terminal
block
Voltage Range at RJ45 reader interfaces
when external voltage is applied at
Door 2: V - Ext.V Readers @ push in terminal
block
Max output current at RJ45 reader interfaces
when external voltage is applied at
Door 2: V - Ext.V Readers @ push in terminal
block
Outputs
Output Contact type
Relay contact max switching voltage and current
(dry contact)
Max output Voltage at Door1/AUX1 output
when OUT1, AUX1 jumper onboard "12V" is
used (wet contact)
MPA2C3 Installation Guide
Reader 1-Wieg.A, 1-Wieg.B/
OSDP1,
Reader 2-Wieg.A, 2-Wieg.B/
OSDP2
Reader 1 - Wieg.A / OSDP1,
Reader 1 - Wieg.B / OSDP1
Reader 2 - Wieg.A / OSDP2,
Reader 2 - Wieg.B / OSDP2
Reader 1 - Wieg.A / OSDP1,
Reader 1 - Wieg.B / OSDP1
Reader 2 - Wieg.A / OSDP2,
Reader 2 - Wieg.B / OSDP2
OUT 1-2, AUX1-2
Aux Outputs 5-8
OUT 1-2, AUX1-2 @ RJ45
OUT 1-2, AUX1-2 @ push in
terminal block**,
Aux Outputs 5-8
OUT 1 @ RJ45 or
OUT 1 @ push in terminal
block**,
AUX 1 @ RJ45 or
AUX 1 @ push in terminal
block**
4 WIEGAND readers: 2 doors/ IN AND
OUT readers per door
4 OSDP readers: 2 doors/ IN AND OUT
readers per door*
10VDC ~ 14VDC
500mA combined for both Wiegand readers
500mA for all OSDP readers*
10VDC ~ 14VDC
500mA combined for both Wiegand readers
500mA for all OSDP readers*
14VDC ~ 24 VDC
1000mA combined for both Wiegand
readers
1000mA for all OSDP readers*
14VDC ~ 24 VDC
1000mA combined for both Wiegand
readers
1000mA for all OSDP readers*
Selectable per jumper OUT 1-2, AUX1-2:
NO (Normally Open) or NC (Normally
Closed)
NO (Normally Open)
500mA @ 30VDC,
500mA @ 22VAC
3A @ 30VDC,
1A @ 22VAC
10VDC ~ 14VDC