Mitsubishi Electric FR-A720-00030-NA Instruction Manual page 319

Table of Contents
Frequency/torque setting by analog
input (terminal 1, 2, 4)
b) Method to adjust any point without application of a voltage (current) to across terminals 1 and 5(4 and 5)
(To change from 8V (80%) to 10V (100%))
Operation
1.
Confirm the RUN indicator and operation mode
indicator
The inverter must be at a stop.
The inverter must be in the PU operation
mode. (Using
2.
Press
to choose the parameter
setting mode.
3.
Turn
until
4.
Press
to display
5.
Turn
until
appears. Set to C19 Terminal 1 gain (torque).
6.
Press
to display the analog voltage
(current) value (%).
7.
Turn
to set the gain voltage (%).
"0V (0mA) equals to 0%, 10V (5V,
20mA) to 100%"
REMARKS
The present setting at the instant of turning
is displayed.
8.
Press
to set.
REMARKS
You can check the current torque setting bias/gain setting by pressing
You can not check after performing operation in step 7.
308
)
appears.
.
(
)
By turning
, you can read another parameter.
Press
to return to the
Press
twice to show the next parameter (
Display
Terminal 1 input Terminal 4 input
Flicker...Parameter setting complete!!
(Adjustment completed)
indication (step 4).
after step 6.
The parameter
number read
previously appears.
C0 to C41
setting
is enabled.
Analog voltage (current)
value (%) across terminals 1 and 5
(across terminals 4 and 5)
The gain torque is
reached when the analog
voltage (current) value across
terminals 1 and 5 (across terminals
4 and 5) is 100%.
Terminal 1 input Terminal 4 input
).
Table of Contents
loading

Table of Contents