Daikin EHYHBH05AAV3 Service Manual page 84

Table of Contents
Troubleshooting
1.8
Overview of the Hydro-box Safety Devices
1
Hydro-box
3
Tank
4
5
Part 4 – Troubleshooting
Protector
EVLQXXCAV3
Q1L (Clixon)
F1T (Thermal fuse)
B1L004
B1L008~016
Protector (Clixon)
EKSWW
Q2L
EKSWWU
Q2L
Q3L
EKHWS - V3
Q2L
Q3L
EKHWS - Z2
Q2L
Q3L
EKHWSU - V3
Q2L
Q3L
EKHWE - V3
Q2L
EKWE - Z2
Q2L
Q3L
EHV - CA
No clixon on tank since no BSH in tank. Only relevant clixon is clixon
from BUH.
Cut-out condition
85 +0/-6°C
134°C +3/-2°C
Min 5l/min in hp operation. If
3V BUH: min 12l/min
Min 11l/min in hp operation.
If 3V BUH: min 12l/min
If 9W BUH: min 15l/min
Cut-out condition
85°C ± 3°C
85°C ± 3°C
85°C ± 3°C
85°C ± 3°C
85°C ± 3°C
91°C ± 3°C
85°C ± 3°C
85°C ± 3°C
85°C ± 3°C
89°C +0 / -8°C
89°C +0 / -8°C
89°C +0 / -8°C
84
ESIE13-02A
Reference
4P312728
AD120151
AD120120
AD120120
Reference
4SW03476-1
4SW03476-1
4SW05637-1
4SW05637-2
4SW05637-1
4SW05637-3
4SW05724-1
4SW05724-1