GE IC754PBSS01 Hardware User's Manual page 10

Quickpanel view communication module
Node Address Switches
Before configuring the AnyBus-S PROFIBUS-DP module the node
address has to be set. This is done with two rotary switches on the
module, this enables address settings from 1-99 in decimal format.
Looking at the front of the module, the leftmost switch is used for
the ten setting and the rightmost switch is used for the setting of the
integers.
Example:
Address = (Left Switch Setting x 10) + (Right Switch Setting x 1)
Note:
Another way of setting the node address is via the mailbox
telegram FB_SET_NODE_ADDRESS.
The node address range is then extended to 1-125.
See chapter that describes FB_SET_NODE_ADDRESS telegram.
Note:
The node address cannot be changed during operation.
10
PROFIBUS Slave Adapter
Features
GFK-2291B