  • Page 1 IMPORTANT PRODUCT INFORMATION GFK-2436M June 2023 VersaMax Micro-20/40/64 PLC Ethernet Option Module (IC200UEM001)
  • Page 2 These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met during installation, operation, and maintenance. The information is supplied for informational purposes only, and Emerson makes no warranty as to the accuracy of the information included herein. Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein.
  • Page 3: Important Product Information

    Note: To reduce the risk of this being accidentally or maliciously used, to permanently disable the module, Emerson strongly recommends that TFTP be disabled by the user, and only enabled via (password- protected) telnet when a firmware update is required.
  • Page 4: Release History

    Note: This Class A digital apparatus complies with Canadian ICES-003. Changes or modifications not expressly approved by Emerson could void the user's authority to operate the equipment. Release History...
  • Page 5: Specifications

    GFK-2436M June 2023 Ethernet Option Module Ethernet Module IC200UEM001 can be used with a Micro-20, -40 or -64 -Point PLC to provide an Ethernet Port. Figure 1: IC200UEM001 Connectors When installed on the Micro 20, 40 or 64 PLC, the Ethernet Port Option Module becomes Port 2. It supports the following communications protocols: SRTP, Modbus Server and client (separate download) and pass- through port (separate download).
  • Page 6: Status Leds

    GFK-2436M June 2023 Status LEDs Color Description Link LED Amber, On Connection to Micro PLC established and network is connected Activity Green, Flashing When there is any activity on the network Status No errors Red, On Duplicate IP address present or network controller error Red, Blinking (2x/sec) No DHCP response or Setup menu active Figure 2: Status LED Location...
  • Page 7 GFK-2436M June 2023 2. If a port-type Option Module is being installed, orient the connector on the Option Module with the connector in the Micro PLC. Be careful to avoid contact with the exposed components in the module. Figure 4: Proper Orientation 3.
  • Page 8 GFK-2436M June 2023 Configuration Use of the Port Option module as Port 2 and the protocol selection must be set up in the configuration software. After making those selections, the communications parameters can also be configured. The option port should be configured for Ethernet. If the configuration and hardware do not match, the PLC logs a System Configuration Mismatch fault in the PLC Fault Table.
  • Page 9: Setting The Ip Address

    GFK-2436M June 2023 Setting the IP Address Key items to remember when setting the IP address on the VersaMax Micro Ethernet module (IC200UEM001): The default IP address is 10.10.0.5. • IP address setting must be saved to the Flash on the Ethernet module or it will be lost during power •...
  • Page 10 Files and passwords are: Function Upgrade Kit for Release 3.3 Destination Password Emerson SRTP 82A1587-MS10-000-B1 Modbus TCP (Client and Server in single firmware)* 82A1588-MS10-000-B3 Tunneling or Pass Thru** 82A1589-MS10-000-B1 * When the Ethernet option module is loaded with the Modbus image it cannot communicate with PME.
  • Page 11 GFK-2436M June 2023 3. If your current firmware version is 3.x, go to step 4. Otherwise go to Step 3 a. a. Click on Put File and select “geamxcupg_6104.rom” from upgrade kit for release 3.3. b. Enter password G5 (case sensitive, must be upper case G) in Remote file. For Remote host, enter the IP address of the Micro PLC (for example: 10.10.0.2).
  • Page 12 GFK-2436M June 2023 5. Enter password G7 (case sensitive, must be upper case G) in Remote file. For Remote host, enter the IP address of the Micro PLC (for example: 10.10.0.2) Figure 9: G7 Remote Host 6. When the file is downloaded the utility will respond with the following. Figure 10: G7 Successful Download 7.
  • Page 13: Telnet Configuration

    GFK-2436M June 2023 9. Once the firmware upgrade completes, TFTP Download must be set to Disabled to provide the highest level of security to the module. Telnet Configuration The Ethernet option module will be power cycled and reset under the following conditions: A connection to the Ethernet option module is established through TELNET and disconnected •...
  • Page 14: Common Interface Mode Settings

    GFK-2436M June 2023 Common Interface Mode Settings Common I/F Mode Setting Binary RS-232C, 8-bit, No Parity, 1 stop bit 0100 1100 RS-232C, 7-bit, Even Parity, 1 stop bit 0111 1000 Flow Flow control sets the local handshaking method for stopping serial input/output. This should be set to zero always.
  • Page 15: Remote Port

    175000,8,O,1. 1. Connect PLC with IC200UEM001 on port2 in the Network. 2. For this example, the IP address of the IC200UEM001 is 10.10.0.5 3. Load the Ethernet Option Module firmware upgrade kit, 82A1588-MS10-000-B1 4.
  • Page 16 GFK-2436M June 2023 6. Press 2 to select Serial & Mode Settings. Figure 12: Selecting Serial & Mode Settings 7. Press Enter on Attached Device (1=Slave 2=Master) (1) ? 8. Press Y on Modbus/TCP Client Enabled (Y) ? 9. Press Enter on Close Idle TCP sockets after (3-60 sec, 0=leave open) (10). 10.
  • Page 17 For this example, the current protocol is SRTP and serial settings are 175000,8,O,1. The following procedure explains how to change the existing serial parameters to 38400,8,N,2 For this example, the IP address of the IC200UEM001 is 10.10.0.5 1. Connect PLC with IC200UEM001 on port2 in the Network.
  • Page 18 GFK-2436M June 2023 Figure 17: New SRTP Serial Parameters 8. Press Enter on New T1, Line Turn-Around Delay (2-1280 msec, 1ms resolution) (2) 9. Press Enter on New T2, ACK/NAK Timeout (50-12,950 msec, 50ms resolution) (9000) 10. Press Enter on New T3, Link Idle Timeout (1000-60,000 msec, 250ms resolution) (10000) 11.
  • Page 19: Security Settings

    GFK-2436M June 2023 Security Settings Note: This information replaces the “Security Settings for the Ethernet Option Module” section in chapter 14 of GFK-1645J and will be included in the next revision of that manual. Security settings are provided to prevent unauthorized access to the Ethernet Option Module configuration mode.
  • Page 20: General Contact Information

    Note: If the product is purchased through an Authorized Channel Partner, please contact the seller directly for any support. Emerson reserves the right to modify or improve the designs or specifications of the products mentioned in this manual at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product.