Emerson Copeland 4MTL-05 Technical Information
Emerson Copeland 4MTL-05 Technical Information

Emerson Copeland 4MTL-05 Technical Information

Stream compressors
Hide thumbs Also See for Copeland 4MTL-05:

Quick Links

Date of last update: Mar-21
C
FOR
OPELAND
The Copeland™ Compressor Electronics module (previously Next Generation CoreSense) is located in the Stream
compressor terminal box. It is prewired to the oil pressure sensor (for compressors with an oil pump), the motor
thermistor chain (PTC), the discharge temperature sensor and the current sensor.
Figure 1: Terminal box
1. Unscrew the 4 screws located in the corners of the compressor terminal box cover and lift off the terminal box
cover.
2. Open the cover of the Copeland Compressor Electronics module to access the terminals.
Figure 3: Copeland Compressor Electronics module cover open
3. Supply 115 V or 230 V power (N and L1) to the module on extreme left terminals 1 and 2 (both polarities are
possible).
4. Position the jumpers according to starting method and motor type. The jumper position is given on the compressor
wiring diagram.
5. Connect the power supply to the terminal plate.
6. Caution! For part-winding, the power leads from the same phase should go through the current sensor in the
same direction.
TI_Stream_NGCS_04_E_Rev04
C
™ C
OPELAND
OMPRESSOR
™ S
C
TREAM
OMPRESSORS
Ref: TI_Stream_NGCS_04_E_Rev04
E
LECTRONICS
– Q
I
UICK
NSTALLATION
Figure 2: Internal view of terminal box
Figure 4: Current sensor
Application Engineering Europe
G
UIDE
1/2
loading

Summary of Contents for Emerson Copeland 4MTL-05

  • Page 1 Date of last update: Mar-21 Ref: TI_Stream_NGCS_04_E_Rev04 Application Engineering Europe ™ C OPELAND OMPRESSOR LECTRONICS ™ S – Q OPELAND TREAM OMPRESSORS UICK NSTALLATION UIDE The Copeland™ Compressor Electronics module (previously Next Generation CoreSense) is located in the Stream compressor terminal box. It is prewired to the oil pressure sensor (for compressors with an oil pump), the motor thermistor chain (PTC), the discharge temperature sensor and the current sensor.
  • Page 2 7. Connect the Copeland Compressor Electronics module cables for the phase monitoring to terminals U/V/W (2 times 3 cables for each winding, grey GR, black BK and brown BN wires), and to the earth PE (pink PK wire). IMPORTANT For Stream CO small and medium compressor models (4MTL-05 to 4MTL-30 &...