Emerson Copeland Scroll Digital ZFD13KVE Application Manuallines

Emerson Copeland Scroll Digital ZFD13KVE Application Manuallines

Compressors for refrigeration
Table of Contents
Digital
Application Guidelines
Digital Scroll™ Compressors for Refrigeration
ZBD21K* to ZBD114K*
ZFD13KVE to ZFD25KVE
ZFD41K5E
Table of Contents
loading

Summary of Contents for Emerson Copeland Scroll Digital ZFD13KVE

  • Page 1 Digital Application Guidelines Digital Scroll™ Compressors for Refrigeration ZBD21K* to ZBD114K* ZFD13KVE to ZFD25KVE ZFD41K5E...
  • Page 2: Table Of Contents

    About these guidelines ....................1 Safety instructions ..................1 1.1 Icon explanation ....................1 1.2 Safety statements....................1 1.3 General instructions .................... 2 Product description ..................3 2.1 Common information about Copeland Scroll Digital™ compressors......3 2.2 Nomenclature ....................4 2.3 Dimensions .......................
  • Page 3 4.2.4 Protection devices ...................18 4.2.5 Crank case heaters ..................18 4.3 Pressure safety controls ..................18 4.3.1 IPR valve (Internal Pressure Relief valve) ...........18 4.3.2 High-pressure control ................18 4.3.3 Low-pressure control ................19 4.4 Discharge temperature protection ................19 4.5 High potential testing ..................20 Starting up &...
  • Page 4: About These Guidelines

    Besides the support they provide, the instructions listed herein are also critical for the proper and safe functioning of the compressors. Emerson Climate Technologies will not guarantee the performance and reliability of the product if it is misused in regard of these guidelines.
  • Page 5: General Instructions

    General instructions WARNING System breakdown! Personal injuries! Never install a system in the field and leave it unattended when it has no charge, a holding charge, or with the service valves closed without electrically locking out the system. System breakdown! Personal injuries! Only approved refrigerants and refrigeration oils must be used.
  • Page 6: Product Description

    Common information about Copeland Scroll Digital™ compressors The Scroll compressor has been under development at Emerson Climate Technologies since 1979. It is the most efficient and durable compressor Emerson Climate Technologies has ever developed for air conditioning and refrigeration. These application guidelines deal with Copeland Scroll Digital™ compressors for refrigeration from ZBD21K* to ZBD114K*, ZFD13K* to ZFD41K*.
  • Page 7: Nomenclature

    Nomenclature The model designation contains the following technical information about the compressor: Dimensions ZBD21KCE 432.4 414.3 363.6 261.6 218.9 ZBD29KCE 463.2 445.2 394.3 291.3 249.7 Figure 1: Dimensions ZBD21KCE & ZBD29KCE Figure 2: Dimensions ZBD30K* to ZBD57K* & ZFD13KVE to ZFD25KVE C6.2.24/1014-0215/E...
  • Page 8: Application Range

    ZBD58KCE 476.3 444.3 211.7 93.6 201.5 74.3 ZBD76KCE 533.2 501.2 122.1 242.8 92.3 ZBD76K5E 533.6 501.8 253.7 277.3 245.7 ZBD114K5E 881.5 519.5 271.3 263.3 Figure 3: Dimensions ZBD58KCE & ZBD76KCE Figure 4: Dimensions ZBD76K5E & ZBD114K5E Application range 2.4.1 Qualified refrigerants and oils IMPORTANT It is essential that the glide of refrigerant blends (primarily R407A and R407F) is carefully considered when adjusting pressure and superheat...
  • Page 9: Application Limits And Operating Envelopes

    2.4.2 Application limits and operating envelopes CAUTION Inadequate lubrication! Compressor breakdown! The superheat at the compressor suction inlet must always be sufficient to ensure that no refrigerant droplets enter the compressor. For a typical evaporator-expansion valve configuration a minimum stable superheat of at least 5K is required. The application envelopes for Digital refrigeration Scroll compressors are for various refrigerants, you can find them in the Copeland brand products Select software, which can be downloaded for free on our website www.emersonclimate.eu.
  • Page 10: Installation

    Installation WARNING High pressure! Injury to skin and eyes possible! Be careful when opening connections on a pressurized item. Compressor handling 3.1.1 Transport and storage WARNING Risk of collapse! Personal injuries! Move compressors only with appropriate mechanical or handling equipment according to weight. Keep in the upright position.
  • Page 11: Solenoid Valves For Models Zbd21K* To Zbd57K* And Zfd13Kve To Zfd25Kve

    Mounting parts ZBD21K* to ZBD114K* & ZFD13K* to ZFD41K* - Soft mountings Figure 6 Solenoid valves for models ZBD21K* to ZBD57K* and ZFD13KVE to ZFD25KVE IMPORTANT The external solenoid valve is a critical component for proper function of this compressor. Only the Copeland brand solenoid valve supplied as a requested accessory must be used.
  • Page 12: Solenoid Valve Installation - General Recommendations

    3.2.2 Solenoid valve installation – General recommendations  The solenoid must be mounted vertically, within ± 15° of vertical. Horizontal mounting is not permitted.  If a suction rotalock fitting is used, the threaded shipping plug in the rotalock fitting must be removed prior to brazing in the vertical solenoid line.
  • Page 13: Vapour Injection (Evi = Economized Vapour Injection)

    Copeland Scroll compressors ZFD13KVE to ZFD25KVE are vapour injection only. Liquid injection alone is not possible. For compressor model ZFD41K5E both liquid injection and vapour injection are possible. Dedicated discharge temperature thermostats (DLT) shall be used for R407A, R407F, R448A and R449A applications and can also be used for R404A.
  • Page 14: Discharge Check Valve

    Figure 13: Wet v apour inj ection cycle for R407A & R407F low temperature applications NOTE: For Digital compressors ZFD13KVE and ZFD25KVE, the DTC valve bulb must replace the existing NTC sensor located at the side of the compressor top cap. The previous NTC sensor has to be removed and the controller, eg, ALCO EC3-D*, has to be modified (disable discharge sensor input).
  • Page 15: Shut-Off Valves And Adaptors

    Copeland Scroll compressors have copper-plated steel suction and discharge tubes. These tubes are far more robust and less prone to leaks than copper tubes. Due to the different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used. shows the proper procedure for brazing Figure 17 the suction and discharge lines to a scroll...
  • Page 16: Oil Separator

    Braze connections can be converted to Rotalock by means of adaptors. Rotalock shut-off valves are available for the suction as well as discharge side. Using either straight or angled adaptors provides a way to convert a Rotalock into a brazing connection. Refer to Table 6 for proper tightening torques: Torque [Nm] Rotalock 3/4"...
  • Page 17: Mufflers

    3.10 Mufflers External mufflers, normally applied to piston compressors in the past, may not be required for Copeland Scroll compressors. Individual system tests should be performed to verify acceptability of sound performance. If adequate attenuation is not achieved, use a muffler with a larger cross-sectional area to inlet area ratio.
  • Page 18: Electrical Connection

    Electrical connection General recommendations The compressor terminal box has a wiring diagram on the inside of its cover. Before connecting the compressor, ensure the supply voltage, the phases and the frequency match the nameplate data. Electrical installation Single-phase (PF*) compressors: Pow er circuit Control circuit Motor terminal connections...
  • Page 19 Three-phase compressors (TF*) with internal motor protection: Power circuit Control circuit Motor terminal connections Three-phase compressors are connected to the T1, T2 and T3 connections Legend B1 ..Room thermostat K1..Contactor B3 ..Discharge gas thermostat R2..Crankcase heater F1 ..Fuse S1..
  • Page 20: Terminal Box

    4.2.1 Terminal box The standard terminal box is IP21 for all models with internal motor protection (TF*/PF*), enclosure class according to IEC 60034-5. Cable glands have an influence on the protection class of the terminal box. It is strongly recommended to use appropriate cable glands in order to reach the rated protection class. We advise installers/service providers to pay attention to this aspect every time they install or replace a Copeland Scroll compressor and to use cable glands according to EN 50262 or any other relevant standard of application in their country/region.
  • Page 21: Motor Protection

    4.2.3 Motor protection For ZBD21K* to ZBD114K*, ZFD13KVE to ZFD25KVE and ZFD41K5E compressors, conventional inherent internal line break motor protection is provided. 4.2.4 Protection devices Independently from the internal motor protection, fuses must be installed before the compressor. Selection of fuses has to be carried out according to VDE 0635, DIN 57635, IEC 269-1 or EN 60-269-1.
  • Page 22: Low-Pressure Control

    4.3.3 Low-pressure control IMPORTANT! Loss of system charge! Bearing malfunction! A low-pressure control is highly recommended for loss of charge protection. Do not bridge or by -pass the low-pressure cut out. Even though these compressors require a discharge temperature sensor, loss of system charge etc.
  • Page 23: High Potential Testing

    Emerson Climate Technologies subjects all Scroll compressors to a high-voltage test after final assembly. Each motor phase winding is tested, according to EN 0530 or VDE 0530 part 1, at a differential voltage of 1000V plus twice the nominal voltage.
  • Page 24: Starting Up & Operation

    Starting up & operation WARNING Diesel effect! Compressor destruction! The mixture of air and oil at high temperature can lead to an explosion. Avoid operating with air. IMPORTANT Oil dilution! Bearing malfunction! Turn the crankcase heater on 12 hours before starting the compressor. Strength pressure test The compressor has been strength-tested in the factory.
  • Page 25: Initial Start-Up

    the compressor before it runs. The majority of the charge should be placed in the high side of the system to prevent bearing washout during first-time start on the assembly line. Initial start-up CAUTION Oil dilution! Bearing malfunction! It is important to ensure that new compressors are not subjected to liquid abuse.
  • Page 26: Deep Vacuum Operation

    To establish the minimum run time obtain a sample compressor equipped with a sight tube (available from Emerson Climate Technologies) and install it in a system with the longest connecting lines that are approved for the system. The minimum on time becomes the time required for oil lost during compressor start -up to return to the compressor sump and restore a minimal oil level that will ensure oil pick -up through the crankshaft.
  • Page 27: Oil Level

    5.15 Oil level The oil level should be maintained at mid-point of the sight glass. If an oil regulator is used the level should be set within the top half of the sight glass. 5.16 Digital system control Due to the pulsing characteristic of Copeland Scroll Digital compressors superheat control needs to be performed by qualified solutions in order to assure the stability, reliability and good performance of the system.
  • Page 28: Maintenance & Repair

    Maintenance & repair Exchanging the refrigerant Qualified refrigerants and oils are given in section 2.4.1. It is not necessary to replace the refrigerant with new unless contamination due to an error such as topping up the system with an incorrect refrigerant is suspected. To verify correct refrigerant composition, a sample can be taken for chemical analysis.
  • Page 29: Lubrication And Oil Removal

    Compressors supplied by Emerson Climate Technologies contain oil with low moisture content, and it may rise during the system assembling process. Therefore, it is recommended that a properly sized filter drier is installed in all POE systems.
  • Page 30: Unbrazing System Components

    3. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson product remains solely with the purchaser or end user.