Starting The Drive Locally - ABB ACS1000 User Manual

Air-cooled
Hide thumbs Also See for ACS1000:
Table of Contents

9.7.3. Starting the drive locally

1. Enable the local control mode of the drive.
2. Check that no alarm or fault messages are displayed on the CDP control panel.
If a fault message is displayed on the CDP control panel, reset the fault.
If a fault cannot be reset, it must be rectified by the responsible personnel.
When no alarms and faults are present and the drive is ready, the CDP control panel displays
RdyForMCBOn:
1 L ->
0.0 rpm
Status
RdyforMCBon
MotorSpeed 0.00 rpm
Power
0.0%
3. Press the MAIN SUPPLY ON push button on the control compartment door to close the
MCB and charge the DC link.
The push button lights up and the status line of the CDP control panel changes to Charging.
1 L ->
0.0 rpm
Status
Charging
MotorSpeed 0.00 rpm
Power
0.0 %
After charging has been finished, the protection IGCTs are closed, the status line of the CDP
control panel changes to Rdy to Strt and the motor can be started.
1 L ->
0.0 rpm
Status
Rdy to Strt
MotorSpeed 0.0 rpm
Power
0.0 %
4. Enter the reference value.
PRODUCT
ACS1000A
0
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS213401 E01
OPERATION
REV.
LANG.
PAGE
L
en
108/164