Section 5
Communication set-up
IEC07000247 V1 EN-US
Figure 71:
IEC07000248 V1 EN-US
Figure 72:
RJ–45 pin
1
2
4
5
Metal house
Use a cable with twisted pairs and a high quality shield. Foil shielding alone is not enough. Rx+ and
Rx- should form one twisted pair, and Tx+ and Tx- should form another. A Cat5 S/FTP cable
(shielded/foil-twisted pair) used, for example, in ethernet communication is a good cable. The outer
shield around the cable consists of a braided mesh. In addition, every twisted pair has a foil
shielding.
74
Fibre-optic ports with ST type connectors
G.703 codirectional port (RJ–45)
Name
Tx+ (TIP-out)
Tx- (RING-out)
Rx+ (TIP-in)
Rx- (RING-in)
Shield
© 2017 - 2023 Hitachi Energy. All rights reserved
Direction
From 21-216 transceiver to multiplexer
From 21-216 transceiver to multiplexer
From multiplexer to 21-216 transceiver
From multiplexer to 21-216 transceiver
Cable shield must be connected
Communication set-up, 670/650 series
1MRK505382-UEN Rev. K
Application Guide