Test Reports

0101
To send a single Test Report (R# Test
0101
Report), enable Sked Function Code #9
0101
(Test Report) in the Skeds section of the
program.
To expand this Test Report to include any
off-normal point condition or other off-
normal conditions of events listed in Diag
Reports as a Non-status Event following a
Test Report, Expand Test Rpt in Section
2.2 Phone Parameters must be
programmed Yes.
Events R# Log Threshold, R# Log
Overflow, and R# RAM Fail are added to
the reports sent with Expanded Test
Reports if they are enabled in RAM Reports
and Expand Test Rpt is also enabled.
To initiate a Status Report, which includes
all R# S: ____ Events as a Status Event (as
opposed to a Non-status Event), Sked
Function Code #10 must be enabled in the
Skeds section of the program.
Reporting off-normal conditions as a Status
Report following a Test Report is required
by some automation systems. Reporting off-
normal conditions as a Non-status Report,
which follows a Test Report, is required for
other automation systems.
An off-normal condition is any point which is
missing, trouble, supervisory, or in alarm (as
opposed to normal). Also, points not
cleared at the command center report as
off-normal.
Control Panels with Firmware version 6.30
or higher can generate an Expanded Off-
Normal Test Report by using Sked Function
Code 28 or a Non-Expanded Off-Normal
Test Report using Sked Function Code 29.
To generate this event, one or more points
must be in an off-normal state at the time
the Sked executes. Expanded Off-Normal
Test Reports include the Off Normal Test
Report Event as well as events for any
points that are in an off-normal state at the
time the report is generated. Non-Expanded
Off-Normal Test Report Events are only
sent when a point is in the off-normal state
but only sends the Off Normal Test Report
Event.
Bosch Security Systems | 10/03 | 47775E

Table 12: Test Reports

Report
Selections
R# S: Alarm
Yes, No
R# S: Trouble
Yes, No
R# S:
Yes, No
Supervised
R# Status
Yes, No
Report
R# S: Open
Yes, No
R# S: Close
Yes, No
R# Test Report
Yes, No
R# S: Perim
Yes, No
Inst
R# S: Perim
Yes, No
Delay
R# S: Fire Supv
Yes, No
R# S: Fire
Yes, No
Alarm
R# S: Fire Trbl
Yes, No
R# S: Msng
Yes, No
Fire
R# S:
Yes, No
MsngBurgTr
R# S:
Yes, No
MsngBurgAl
R# S:
Yes, No
FireSpMsng
R# S:
Yes, No
SuperMsng
R# S:
Yes, No
DrLeftOpen

Diag Reports

Selecting Yes enables sending a report when the
event occurs. If the off-normal state of the following
events (indicated with an *) still exist, they report
when a Test Report (see the
prompt in Section 2.3.8 Dialing Attempts) is initiated
and Expanded Test Rpt is programmed Yes.
EN | 20
Description
Status Alarm Report
Status Trouble
Report
Status Supervised
Report
Status Report
Status Open Report
Status Close Report
Test Report
Status Perimeter
Instant Arm Report
Status Perimeter
Delay Arm Report
Status Fire
Supervision Report
Status Fire Alarm
Report
Status Fire Trouble
Report
Status Fire Missing
Report
Status Burg Missing
Trouble Report
Status Burg Missing
Alarm Report
Status Fire
Supervision Missing
Report
Status Non-fire
Supervision Missing
Report