About Electrical Compliance; About Preferential Kwh Rate Power Supply - Daikin EAVH16S23DA6V Installer's Reference Manual

Hide thumbs Also See for EAVH16S23DA6V:
Table of Contents
9
|
Electrical installation

9.1.3 About electrical compliance

9.1.4 About preferential kWh rate power supply

Installer reference guide
88
Tightening torques
Outdoor unit:
Item
M4 (X1M)
M4 (earth)
Indoor unit:
Item
X1M
X2M
X5M
X6M
X10M
M4 (earth)
Only for the backup heater of the indoor unit
See
"9.3.2 To connect the backup heater power
Electricity companies throughout the world work hard to provide reliable electric
service at competitive prices and are often authorised to bill clients at benefit
rates. E.g. time-of-use rates, seasonal rates, Wärmepumpentarif in Germany and
Austria, ...
This equipment allows for connection to such preferential kWh rate power supply
delivery systems.
Consult with the electricity company acting as provider at the site where this
equipment is to be installed to know whether it is appropriate to connect the
equipment in one of the preferential kWh rate power supply delivery systems
available, if any.
When the equipment is connected to such preferential kWh rate power supply, the
electricity company is allowed to:
interrupt power supply to the equipment for certain periods of time;
demand that the equipment ONLY consumes a limited amount of electricity
during certain periods of time.
The indoor unit is designed to receive an input signal by which the unit switches
into forced OFF mode. At that moment, the outdoor unit compressor will NOT
operate.
The wiring to the unit is different depending on whether the power supply is
interrupted or NOT.
Tightening torque (N•m)
1.2~1.5
Tightening torque (N•m)
2.45 ±10%
0.88 ±10%
0.88 ±10%
2.45 ±10%
0.88 ±10%
1.47 ±10%
4
supply" [
 92].
EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09