Multiple Rooms - Two Lwt Zones - Daikin EAVH16S23DA6V Installer's Reference Manual

Hide thumbs Also See for EAVH16S23DA6V:
Table of Contents
6.2.3 Multiple rooms – Two LWT zones
EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
Number of water temperature zones:
#: [4.4]
Code: [7-02]
In this document:
Main zone = Zone with the lowest design temperature in heating, and the highest
design temperature in cooling
Additional zone = Zone with the highest design temperature in heating, and the
lowest design temperature in cooling
CAUTION
If there is more than one leaving water zone, ALWAYS install a mixing valve station in
the main zone to decrease (in heating)/increase (in cooling) the leaving water
temperature when the additional zone has demand.
Typical example:
Room (zone)
Living room (main zone)
Bed rooms (additional zone)
6
Application guidelines
|
Value
0 (Leaving water): Unit operation is
decided based on the leaving water
temperature.
0 (Single zone): Main
Heat emitters: Design temperature
Underfloor heating:
In heating: 35°C
In cooling: 20°C (only refreshment, no
real cooling allowed)
Heat pump convectors:
In heating: 45°C
In cooling: 12°C
Installer reference guide
39