Application Of Wiring And Equipment - GE Fuji Electric FVR-C9S-2UX Series Instruction Manual

Three-phase 230 v ac input type
Table of Contents
CAUTION:
The control circuit terminal wiring should be
kept as far as possible from the main circuit
wiring to prevent operational error due to
noise interference. Never install them in the
same duct or conduit. (A separation dis-
tance of 4 inches [10cm] or more is recom-
mended.) If the control circuit wiring must
cross the main circuit wiring, make sure it
crosses at a right angle.
Use shielded, twisted wire for the control
circuit wiring , which should be as short as
possible (65 feet [20m] or less).
Install a surge absorber in parallel with any
magnet contactors, solenoids, relays or
timer coils, which are close to the drive.

9. Application of Wiring and Equipment

Applicable motor output [Hp]
Drive type
Output rated capacity
Applicable wire size
Main circuit
(AWG)
Contol circuit
MCCB
ELCB
Listed fuse*
* The use of quick-acting fuses is required to validate UL listings. The factory recommendation is
Bussman type JKS or equivalent.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
FVR-C9S-2UX
Long wire lengths between the motor and
the drive will result in increased capacitance
and leakage current. This may cause earlier
activation of such protective function as
overcurrent protection, overheating protec-
tion and electronic thermal overload, or the
error in current detection may become large.
To avoid these, adjust the length of wiring
between the drive and the motor so that is
does not exceed the length shown below.
FVRF12C9S-2UX : 165 feet (50m)
FVRF25 to 005C9S-2UX : 325 feet (100m)
1/8
1/4
FVRF12
FVRF25
C9S-2UX C9S-2UX C9S-2UX C9S-2UX C9S-2UX C9S-2UX C9S-2UX
[kVA]
0.28
0.56
15
15
5
1/2
1
2
FVRF50
FVRF001 FVRF002 FVRF003 FVRF005
1.0
1.6
2.8
14
24
10
3
5
4.0
6.6
12
20
30
20
30
20
30
C92-2-15
17