Piping installation

8.2.2 Precautions when connecting the refrigerant piping

Installer reference guide
86
Keeping in mind the guidelines for:
-
Pipe bending
-
Flaring pipe ends
-
Brazing
-
Using the stop valves
INFORMATION
Also read the precautions and requirements in the following chapters:
"3 General safety
"8.1 Preparing refrigerant
DANGER: RISK OF BURNING/SCALDING
NOTICE
Do NOT use mineral oil on flared part.
Do NOT reuse piping from previous installations.
NEVER install a drier to this R410A unit to guarantee its lifetime. The drying
material may dissolve and damage the system.
NOTICE
Take the following precautions on refrigerant piping into account:
Avoid anything but the designated refrigerant to get mixed into the refrigerant
cycle (e.g. air).
Only use R410A when adding refrigerant.
Only use installation tools (e.g. manifold gauge set) that are exclusively used for
R410A installations to withstand the pressure and to prevent foreign materials
(e.g. mineral oils and moisture) from mixing into the system.
Install the piping so that the flare is NOT subjected to mechanical stress
Protect the piping as described in the following table to prevent dirt, liquid or
dust from entering the piping.
Use caution when passing copper tubes through walls (see figure below).
Unit
Outdoor unit
>1 month
<1 month
Indoor unit
Regardless of the period
precautions" [
4
 12]
4
piping" [
 84]
Installation period
EVLQ05+08CA + EHYHBH05A + EHYHBH/X08A + EHYKOMB33AA
Protection method
Pinch the pipe
Pinch or tape the pipe
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09