APPLICATION
The 8600 family of ignition controls provide ignition sequence, flame monitoring and safety shutoff for intermittent pilot
gas fired heating appliances. These controls provide flame sense and operating sequences suitable for the application.
Table 1 describes the main features of each available model.
Valve
Igniter-
Current
Sensor
Rating
Type
Model
@ 24 Vac
S8600B
1.0 A Pilot
b
Separate
and
1.0 A Main
S8600C
Separate
1.0 A Pilot
and
1.0 A Main
S8600H Combination
1.0 A Pilot
c
and
1.0 A Main
S8600M Combination 1.0 A Pilot
and
1.0 A Main
S8610B
Separate
1.0 A Pilot
and
2.0 A Main
S8610C
Separate
1.0 A Pilot
and
2.0 A Main
S8610H Combination 1.0 A Pilot
and
2.0 A Main
S8610M
Separate
1.0 A Pilot
and
2.0 A Main
S8670D Combination 1.0 A Pilot
and
2.0 A Main
บริ ษ ั ท เอดี ด ี เฟอร์ เ นส จํ า กั ด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
Table 1. Intermittent Pilot Ignition Models.
Trial for
Ignition
Prepurge
Pilot
Sequence
Timing
Ignition
None
15 or 90
Lockout
seconds,
as ordered
None
15 or 90
Continuous
seconds,
as ordered
None
15 or 90
Lockout
seconds,
as ordered
None
15 or 90
Continuous
seconds,
as ordered
None
15 or 90
Lockout
seconds,
as ordered
None
15 or 90
Continuous
seconds,
as ordered
None
15 or 90
Lockout
seconds,
as ordered
None
15 or 90
Continuous
seconds,
as ordered
30
15 or 90
Lockout
seconds
seconds,
as ordered
Automatic Ignition Systems
ANSI Z21.20
®
INSTALLATION INSTRUCTIONS
Type
Ignition Sequence Description
Spark and pilot gas ON until lightoff or trial for ignition ends. If
pilot fails to light, pilot gas and spark OFF (100% shutoff), and
lockout. Cycle "Call for Heat" to restart ignition sequence.
Spark and pilot gas ON until lightoff or trial for ignition ends. If
Retry
pilot fails to light, pilot gas and spark OFF (100% shutoff). After
5 minute delay, a new trial for ignition is initiated. This sequence
continues until lightoff or "Call for Heat" is removed.
Spark and pilot gas ON until lightoff or trial for ignition ends. If
pilot fails to light, pilot gas and spark OFF (100% shutoff), and
lockout. Cycle "Call for Heat" to restart ignition sequence.
Spark and pilot gas ON until lightoff or trial for ignition ends. If
Retry
pilot fails to light, pilot gas and spark OFF (100% shutoff). After
5 minute delay, a new trial for ignition is initiated. This sequence
continues until lightoff or "Call for Heat" is removed.
Spark and pilot gas ON until lightoff or trial for ignition ends. If
pilot fails to light, pilot gas and spark OFF (100% shutoff), and
lockout. Cycle "Call for Heat" to restart ignition sequence.
Spark and pilot gas ON until lightoff or trial for ignition ends. If
Retry
pilot fails to light, pilot gas and spark OFF (100% shutoff). After
5 minute delay, a new trial for ignition is initiated. This sequence
continues until lightoff or "Call for Heat" is removed.
Spark and pilot gas ON until lightoff or trial for ignition ends. If
pilot fails to light, pilot gas and spark OFF (100% shutoff), and
lockout. Cycle "Call for Heat" to restart ignition sequence.
Spark and pilot gas ON until lightoff or trial for ignition ends. If
Retry
pilot fails to light, pilot gas and spark OFF (100% shutoff). After
5 minute delay, a new trial for ignition is initiated. This sequence
continues until lightoff or "Call for Heat" is removed.
After prepurge, spark and pilot gas ON until lightoff or trial for
ignition ends. If pilot fails to light, pilot gas and spark OFF
(100% shutoff), and lockout. Cycle "Call for Heat" to restart
ignition sequence.
a
69-1954-01
Table of Contents
loading

Summary of Contents for Honeywell S8600B

  • Page 1 บริ ษ ั ท เอดี ด ี เฟอร์ เ นส จํ า กั ด ADD FURNACE CO.,LTD. 44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K Intermittent Pilot Gas Ignition Control INSTALLATION INSTRUCTIONS APPLICATION The 8600 family of ignition controls provide ignition sequence, flame monitoring and safety shutoff for intermittent pilot gas fired heating appliances.
  • Page 2: Specifications

    44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL Table 1. Intermittent Pilot Ignition Models. (Continued) Valve...
  • Page 3: Installation

    44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL High Humidity or Dripping Water WARNING Dripping water can cause the control to fail. Never install an appliance where water can drip on the controls.
  • Page 4 CONNECT IGNITION CABLE Use Honeywell ignition cable or construct an ignition cable that Mount the module with the terminals down to protect them from conforms to suitable national standards such as Underwriters dripping water and dust.
  • Page 5 44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL Connect remaining system components to the ignition module terminals as shown in the appropriate wiring Table 4.
  • Page 6 44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL S8600 B,C; S8610 B,C S8600 H,M; S8610 H,M; S8670 D,E...
  • Page 7 44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL S8600 B,C; S8610 B,C; S8670 J,K Step 2: Verify control system ground.
  • Page 8: Trial For Pilot Ignition

    44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL GAS LEAK TEST (DOWNSTREAM OF GAS The S8600 family uses a two-level pilot flame proving sequence.
  • Page 9 44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL OPERATING SEQUENCE - STANDARD MODELS S8600 C, M; S8610 C, M = RETRY S8600 B, H;...
  • Page 10: Troubleshooting

    44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL OPERATING SEQUENCE - PREPURGE MODELS S8760 E, K = RETRY...
  • Page 11: Ignition System Checks

    44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL from ignition cable or other heavily IMPORTANT 1. The following service procedures are provided insulated wire.
  • Page 12: Led Status And Troubleshooting

    44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL • If necessary, adjust pilot flame by turning the • Recheck ignition sequence as follows.
  • Page 13 44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL Table 6. Continuous Retry Models C, M, E, and K Only—Green LED Status Codes. (Continued) Green LED...
  • Page 14 44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL Table 7. Lockout Models B, H D, and J Only—Green LED Status Codes. (Continued) Green LED...
  • Page 15: Troubleshooting Guide

    44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL Troubleshooting Guide Refer to the following guide for troubleshooting (Fig. 14).
  • Page 16 บริ ษ ั ท เอดี ด ี เฟอร์ เ นส จํ า กั ด ADD FURNACE CO.,LTD. 44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170 โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258 https://www.add-furnace.com E-mail: [email protected] S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K INTERMITTENT PILOT GAS IGNITION CONTROL 69-1954—01...

Table of Contents