Wiring; Terminal Connection Diagram - Mitsubishi Electric FR-F740-00023-EC Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-F740-00023-EC:
Table of Contents

Wiring

1.2 Wiring

1.2.1

Terminal connection diagram

*1. DC reactor (FR-HEL)
Source logic
Main circuit terminal
Control circuit terminal
Three-phase AC
power supply
*2. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
Control input signals (No voltage input allowed)
Forward
Terminal functions
vary with the input
Reverse
terminal assignment
(Pr. 178 to Pr. 189)
Start self-holding selection
High speed
Multi-speed
Middle speed
selection
Low speed
Jog mode
Second function selection
*3. AU terminal
Output stop
can be used
as PTC input
terminal.
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
power failure
Contact input common (Sink)
(Common for external power supply transistor)
24VDC power supply
Contact input common
(Common for external power supply transistor)
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k Ω
*5
Auxiliary input (+)
(-)
Terminal 4 input
(+)
(-)
(Current input)
* 4. Terminal input
specifications can be
changed by analog input
specifications switchover
(Pr. 73, Pr. 267).
* 5. It is recommended to use
2W1kΩ when the
frequency setting signal is
changed frequently.
CAUTION
· To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables.
· After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
4
Be sure to connect the DC reactor
supplied with the 01800 or more.
When a DC reactor is connected
to the 01160 or less, remove the
Earth
jumper across P1-P/+.
MC
MCCB
R/L1
S/L2
T/L3
R1/L11
Jumper
*2
S1/L21
Earth
STF
rotation
start
STR
rotation
start
STOP
RH
RM
RL
JOG
RT
MRS
RES
Reset
AU
CS
SD
PC
10E(+10V)
10(+5V)
3
2
2
5
1
1
4
Connector
for plug-in option
connection
*1
Jumper
Jumper
P1
P/+
PX
N/-
PR
*7
*7
Inrush current
limit circuit
ON
EMC filter
ON/OFF
OFF
connector
Main circuit
Control circuit
*3
AU
PTC
24V
PU
connector
Initial value
0 to 5VDC
0 to 10VDC
selected
* 4
4 to 20mADC
(Analog common)
Initial
0 to ± 10VDC
value
* 4
selected
0 to ± 5VDC
Initial
4 to 20mADC
value
0 to 5VDC
selected * 4
0 to 10VDC
Option connector 1
Terminating
resistor
Resistor unit
*6. A CN8 connector is
(Option)
provided with the
Brake unit
01800 or more.
(Option)
*7.
Do not use PR and PX terminals.
Please do not remove the jumper
connected to terminal PR and PX.
CN8
*6
U
V
W
C1
Terminal functions
B1
Relay output 1
vary with the output
(Alarm output)
terminal assignment
A1
(Pr. 195, Pr. 196)
C2
B2
Relay output 2
A2
Open collector output
RUN
Running
Terminal functions
SU
vary with the output
Up to frequency
terminal assignment
IPF
Instantaneous
(Pr. 190 to Pr. 194)
power failure
OL
Overload
FU
Frequency detection
SE
Open collector output common
Sink / source common
(+)
CA
Analog current output
(0 to 20mADC)
(-)
(+)
AM
Analog signal output
(0 to 10VDC)
5
(-)
RS-485 terminals
TXD+
TXD-
Data transmission
RXD+
Data reception
RXD-
SG
GND
5V
(Permissible load
VCC
current 100mA)
Motor
IM
Earth
Relay output