B
Installation altitude
Dimensioning
Size 0:
Restrictions for continuous
duty with 125 % I
N
1) Electrical installation in compliance with applicable regulations is necessary for maintaining the EMC limit value class. Comply with the
installation notes.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Operating Instructions V3 – MOVITRAC® B
All sizes
Up to h ≤ 1000 m (3281 ft) without restrictions.
The following restrictions apply at h ≥ 1000 m (3281 ft):
from 1000 m (3281 ft) to max. 4000 m (13120 ft):
– I
reduction by 1 % per 100 m (328 ft)
N
from 2000 m (6562 ft) to max. 4000 m (13120 ft):
– AC 230 V units: Reduction of the rated mains voltage V
100 m (328 ft)
– AC 500 V units: Reduction of the rated mains voltage V
100 m (328 ft)
Over 2000 m (6562 ft) only overvoltage class 2, external measures are required for
overvoltage class 3. Overvoltage classes according to DIN VDE 0110-1.
According to DIN ISO 276-v
Maximum ambient temperature ϑ
Maximum rated mains voltage V
No DIN rail mounting / submounting resistor
At 1 × 230 V: Provide ND line choke
Technical Data
General technical data
mains
mains
: 40 °C (104 °F)
A
: 400 V
mains
n
kVA
8
f
i
P
Hz
by AC 3 V per
by AC 6 V per
85