Honeywell PWTA40 Series Installation Instructions page 3

Conduit wet pressure transmitters
1 2 3
ELEMENT A ELEMENT B
IMPORTANT
Cable shielding should ONLY be connected to the
GROUND terminal at the PWTA transmitter. DO
NOT connect cable shielding at the pressure sen-
sor.
Picture above shows the 5 wires connected prop-
erly from the sensor to the PWTA transmitter (+/-
voltage supply (terminals 1 and GROUND), +/-
feedback from transducer (terminals 2 and 3) and
shield wire (GROUND terminal).
8. Connect conduit fittings to the sensors and PWTA
transmitter. Use water tight fittings if required by
your installation conditions.
9. Wire PWTA transmitter for voltage or current output
as shown (Remote zero wiring is optional):
10. Use the following diagram for the remaining config-
uration of your PWTA system.
1 2 3
PWTA SERIES CONDUIT WET PRESSURE TRANSMITTERS
ZERO
A
B
C
1 2 3
ELEMENT A ELEMENT B
11. Select 20 mA, 5 V or 10 V output using OUTPUT
switch based on wiring configuration.
4-20mA
0-5V
0-10V
12. Verify the PSIG jumper matches the PSIG rating on
the sensors.
Sensor Identification:
PWTA40-X = 100 PSIG
PWTA100-X = 100 PSIG
PWTA250-X = 250 PSIG
PWTA Transmitter Jumper Configuration:
[
SENSOR
25
PSIG
100
PSI
RUN
UNI
SLOW
A-B
13. Select differential pressure range using RANGE
switch. Identify if your PWTA transmitter is labeled a
PWTA40, PWTA100, or PWTA250 model. Each
Transmitter provides three PSID ranges based on the
PSIG rating on sensors A and B. Use the appropriate
3
4-20mA
0-5V
0-10V
25
50
100
250
PSI
BAR
RUN
TEST
UNI
BI
SLOW
FAST
A-B
B-A
1 2 3
]
50
250
kPa
TEST
BI
FAST
B-A
31-00396—01
loading

This manual is also suitable for:

Pwta100 seriesPwta250 series