Honeywell WEB-VA00IB24NM Installation Instructions Manual

Honeywell WEB-VA00IB24NM Installation Instructions Manual

Bacnet ip/mstp vav controller
Hide thumbs Also See for WEB-VA00IB24NM:

Quick Links

BACnet IP/MSTP VAV Controller
General ................................................................................... 2
Trademark Information ........................................................... 2
Product Description ................................................................ 2
Network Security ..................................................................... 4
General Safety Instructions ...................................................... 4
Specifications .......................................................................... 5
Electrical ................................................................................. 5
Hardware ................................................................................ 5
Communication....................................................................... 5
Airflow Sensor ......................................................................... 5
Operational Environment ....................................................... 5
Sylk™ Devices Supported ........................................................ 5
Universal Input Types and Characteristics .............................. 5
Analog Outputs ....................................................................... 5
Solid State Relay ..................................................................... 5
Standards and Compliances .................................................... 5
Mounting ................................................................................ 7
Mounting Actuator onto Damper Shaft .................................. 7
Differential Pressure Sensor ................................................... 9
Airflow Sensor Replacement ................................................... 10
Wiring ...................................................................................... 11
Power supply ............................................................................ 12
General Information ............................................................... 12
Power Wiring .......................................................................... 12
Communication........................................................................ 15
BACnet MS/TP .......................................................................... 15
BACnet IP ................................................................................. 17
Connecting to a IP network ..................................................... 17
® U.S. Registered Trademark
Copyright © 2020 Honeywell Inc. • All Rights Reserved
INSTALLATION INSTRUCTIONS
Static IP Configuration............................................................. 17
Network Topologies ................................................................ 17
Antenna................................................................................... 18
Sylk Bus™ ................................................................................. 19
Modbus ................................................................................... 20
Wiring Topology ...................................................................... 20
Modbus Master Specifications ................................................ 20
Commissioning......................................................................... 22
Automatic MAC Addressing .................................................... 22
Operator interface LEDs .......................................................... 22
Service Button ......................................................................... 23
Regulatory Information ............................................................ 24
FCC Regulation ........................................................................ 24
Canadian Regulatory Statement ............................................. 24
Approvals, Certifications, Etc ..................................................... 25
Appendix ................................................................................. 26
7
Sensor Input Accuracy ............................................................. 26
Sensor Characteristics .............................................................. 26
NTC10K TYPE II ........................................................................ 27
NTC10K TYPE III ....................................................................... 28
PT100 ...................................................................................... 28
JOHNSON A99 ......................................................................... 28
NTC20K .................................................................................... 29
Nickel Class B DIN 43760 sensors ............................................ 30
10K3A1 .................................................................................... 31
NI1000TK5000 ......................................................................... 32
PT1000 .................................................................................... 33
PT3000 .................................................................................... 35
Related Technical Literature ................................................ 36
Prelim Draft - Brand Neutral
31-XXXX-XX
Table of Contents
loading

Summary of Contents for Honeywell WEB-VA00IB24NM

  • Page 1: Table Of Contents

    BACnet MS/TP ................15 PT1000 ..................33 PT3000 ..................35 BACnet IP ................. 17 Related Technical Literature ..........36 Connecting to a IP network ............. 17 ® U.S. Registered Trademark Copyright © 2020 Honeywell Inc. • All Rights Reserved 31-XXXX-XX...
  • Page 2: General

    Niagara Trademark Information workbench. Sylk™ is a trademark of Honeywell International Inc. All models contain an integral, field-replacable, polarity-free BACnet®is a registered trademark of ASHRAE Inc differential pressure sensor that provides flow measurement for pressure independent applications.
  • Page 3 Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION HW version: RevA ; SW version:1.0.0.0 Table 2. Remote Antenna Part Numbers Antennae Part Number Vendor Name Type Gain ANT-DB1-LCD-SMA LINX External 2.4 GHz: 2.8 dbi ARY113-0012-006-00 Wieson External 2.4 GHz: -0.31dbi DIMENSION 6”...
  • Page 4: Network Security

    Internet, the BACnet IP/MSTP VAV controller automatically becomes a potential target for cyber- attacks. To — Use only Honeywell supplied or approved accessories. ensure safe and reliable operation take necessary protective measures. If it is not necessary for the BACnet IP/MSTP VAV —...
  • Page 5: Specifications

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION SPECIFICATIONS Operational Environment Storage: -40 °F to 150 °F (-40 °C to 66 °C) Operation: 32 °F to 122 °F (0 °C to 50 °C) Electrical Humidity: 5% to 95% RH., non-condensing Voltage Range: 20-30 VAC;...
  • Page 6 Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION Wireless Connectivity Table 3. Connectivity Frequency Range Connectivity Medium Frequency range E.I.R.P for CE E.I.R.P for FCC/IC Bluetooth 2400 MHz- 2483.5 MHz 20 mW 20 mW 31-XXXX-XX...
  • Page 7: Mounting

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION MOUNTING To mount the BACnet IP/MSTP VAV refer the mounting instructions(XX-XXXX) provided with the controller. Before mounting the controller on damper shaft, review the power, inputs and output specifications. See “Specifications”...
  • Page 8 Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION IMPORTANT: NOTE: NOTE: The controller is not position sensitive and can be The actuator is shipped with the mechanical end- limit set mounted sideways or upside down. Use the drill- ing screws set to 95 degrees of rotation.
  • Page 9: Differential Pressure Sensor

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION If the damper rotates counterclockwise (CCW) to open, and When twin tubing is used from the pickup, split the pickup the angle of the damper open-to-closed is 45 or 60 degrees: tubing a short length to accommodate the connections.
  • Page 10: Airflow Sensor Replacement

    Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION effect past the heater and tends to keep most dust off the Airflow Sensor Replacement bridge structure. The heat affect, along with a simple filter, can Procedure to replace the airflow sensor is as follows: help to keep the dust from causing output shifts in the output of the device.
  • Page 11: Wiring

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION WIRING 7 x Universal Input/Output (UIO) Output Connection Example Output Type Load 0 to 10 Vdc, 10 mA max. •1k IN 0V 4 to 20 mA ”550 0V IN 0V IN Input Connection Example Volatage Inputs...
  • Page 12: Power Supply

    Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION POWER SUPPLY ing a supply cord, plug, or other means for discon- necting from the power supply must have the means of disconnection incorporated in the fixed wiring. This type General Information of disconnection must have a contact separation of at least 1/8 in.
  • Page 13 Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION Line DO NOT SWITCH ON POWER 100 VA max. Voltage 24 Vac Supply voltage: 24 Vac (20 to 30 Vac) 50/60 Hz This equipment For UL rating the must be earthed transformer must (grounded) be class 2 rated.
  • Page 14 Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION The RS485 Standard Wiring Method According to the RS485 standard (TIA/EIA 485: “Electrical NOTE: Characteristics of Generators and Receivers for Use in Balanced NOTE: Digital Multipoint Systems”), only one driver communicating via an RS485 interface may transmit data at a time.
  • Page 15: Communication

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION COMMUNICATION To set the MS/TP MAC address of a BACNET BACnet MSTP VAV controller: Find an unused MAC address on the MS/TP net- work to BACNET MS/TP which the BACnet MS/TP VAV controller con- nects. Locate the DIP switch bank on the BACNET MS/TP VAV Each controller uses a BACnet MS/TP communications port.
  • Page 16 Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION Termination Resistors • Belden 9842 or 9842NH and • Daisy-chain topology. Matched terminating resistors are required at each end of a — Must conform to TIA/EIA RS485 cabling guidelines and segment bus wired across (+) and (-).
  • Page 17: Bacnet Ip

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION BACNET IP Network Topologies — Recommended cable: Cat5/Cat6 Table 9. Default IP Address — Maximum distance between 2 controllers or controller and switch should be less than 328 ft. (100 meters) Static IP Address 0.0.0.0 Subnet Mask...
  • Page 18: Antenna

    Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION Antenna IP and MSTP VAV controller has a local rubber antenna included in the kit. The antenna facilitates wireless communication via Wi-Fi and Bluetooth with other devices. If the IP VAV controller is mounted inside a cabinet/enclosure and you are using the local antenna, use an enclosure that is made of a nonmetallic material to achieve a reliable wireless signal.
  • Page 19: Sylk Bus

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION Table 11. Recommended max. distances from controller to TR40x/T42x • Do not install the antenna close to the floor. wall modules (Continued) Standard non-twisted thermostat wire shielded Single twisted pair, Non-Shielded, or Non- Shielded, Stranded or Solid Stranded or Solid...
  • Page 20: Modbus

    RS485 repeaters are possible but have not been tested by can function only as a Modbus Master. In general, the TIA/EIA Honeywell. Therefore it is the responsibility of the installing / 485 wiring rules must be followed. commissioning person to ensure proper function.
  • Page 21 Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION — Must conform to TIA/EIA 485 cabling guidelines. With regards to Figure. 3 above, note the following: “TIA/EIA 485 Cable Specifications” on page — Should not extend beyond a single building. NOTE: NOTE: —...
  • Page 22: Commissioning

    Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION COMMISSIONING Automatic MAC Addressing NOTE: NOTE: Automatic MAC addressing will be enabled only if dip switches are all-on or all-off. In contrast to other controllers, the BACNET MSTP Figure 21.
  • Page 23: Service Button

    = 130)) to be sent. alarm Normal operation Return the controller for repair. Contact Honeywell WEBs Customer Care for assistance. The ON/OFF frequencies listed in Table above can be converted from "Hz" (i.e., "ON/OFF per second") to "ON/OFF per minute" by multiplying them by 60.
  • Page 24: Regulatory Information

    Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION REGULATORY INFORMATION : To maintain compliance with the RF exposure EMF Statement requirement, a separation distance of 20 cm between the FCC Regulation device and the human should be maintained. This device complies with Part 15 of the FCC Rules.
  • Page 25: Approvals, Certifications, Etc

    — CAN/CSA-E60730-1:02, Standard for Automatic Restriction of Chemicals (REACH) — Electrical Controls for Household and Similar Use, Part 1: General Requirements; Honeywell takes compliance with REACH very — Complementary listing for UL916, CSA C22.2 No. 205; seriously. — BTL-listed, BACnet AAC profile;...
  • Page 26: Appendix

    Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION APPENDIX Recognition of Sensor Failure of Sensor Inputs Sensor Input Accuracy The thresholds at which sensor failures – i.e., sensor breaks (SB) and short-circuits (SC) – are recognized depends upon The controller's internal sensor inputs support both the given sensor type.
  • Page 27: Ntc10K Type Ii

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION NTC10K TYPE II Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal [° F] [° C] [KΩ] voltage [° F] [° C] [KΩ] voltage [° F] [°...
  • Page 28: Ntc10K Type Iii

    Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION NTC10K TYPE III PT100 JOHNSON A99 Temp. Temp.[° C] Resistance [Ω] [° F] Temp. Temp.[° C] Resistance [Ω] 82.2 1362 Temp. [° F] Temp.[° C] Resistance Temp. [° F] Temp.[° C] Resistanc [°...
  • Page 29: Ntc20K

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION NTC20K Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal [° F] [° C] [KΩ] voltage [° F] [° C] [KΩ] voltage [° F] [° C] [KΩ] voltage Temp.
  • Page 30: Nickel Class B Din 43760 Sensors

    Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION Nickel Class B DIN 43760 sensors T(R) = a´ +b´(1+c´R)½ +d´R5+e´R7 dT < 0.12 K (higher order equations on request) The characteristic of the nickel temperature sensor is specified Coefficients as per DIN 43760.
  • Page 31: 10K3A1

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION 10K3A1 Temp. [° F] Temp.[° C] Resistance Temp. [° F] Temp.[° C] Resistance Temp. [° F] Temp.[° C] Resistance [Ω] [Ω] [Ω] 37.4 28054 116.6 4040 195.8 Temp. [° F] Temp.[° C] Resistance [Ω] 39.2 26687...
  • Page 32: Ni1000Tk5000

    Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION NI1000TK5000 Sensor Type Nominal Resistance Sensitivity Ω : 1000 Ni1000 TK5000 DIN B TC: 5000 ppm/K °F °C 790.88 830.84 826.8 822.78 818.76 814.75 810.75 806.76 802.78 798.8 794.84 871.69 867.57...
  • Page 33: Pt1000

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION PT1000 Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal [° F] [° C] [KΩ] voltage [° F] [° C] [KΩ] voltage [° F] [° C] [KΩ] voltage Temp.
  • Page 34 Prelim Draft - Brand Neutral BACnet IP/MSTP VAV Controller - INSTALLATION INSTRUCTION Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal [° F] [° C] [KΩ] voltage [° F] [° C] [KΩ] voltage [°...
  • Page 35: Pt3000

    Prelim Draft - Brand Neutral BACNET IP/MSTP VAV - INSTALLATION INSTRUCTION PT3000 Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal Temp. Temp. Resistance Terminal [° F] [° C] [KΩ] voltage [° F] [° C] [KΩ] voltage [° F] [° C] [KΩ] voltage Temp.
  • Page 36: Related Technical Literature

    The material in this document is for information purposes only. The content and the product described are subject to change without notice. Honeywell makes no representations or warranties with respect to this document. In no event shall Honeywell be liable for technical or editorial omissions or mistakes in this document, nor shall it be liable for any damages, direct or incidental, arising out of or related to the use of this document.

Table of Contents