Honeywell WEB-600E Manual

Network controllers
WEB-600E and CP-600E Network
Controllers
ABOUT THIS GUIDE
This document covers installation instruction of Honeywell's
WEB-600E controller. It assumes that you are an engineer,
technician, or service person who is performing control
system installation. Instructions in this document apply to the
following products:
Model
WEB-600E,
DIN mount WEB-600E and CP-600E
WEB-600E-USA,
controller, powered by one of the two
CP-600E,
separate plug-in power supply
CP-600E-USA
modules, or by wall mount AC power
adapter. Controller supports optional
I/O expansion modules and internal
communications option cards.
NPB-PWR-H
24Vac/dc input/15Vdc output power
supply module, DIN mountable.
NPB-PWR-UN-H
120–240Vac universal input/15Vdc
output power supply module, DIN
mountable.
NPB-WPM-US
External wall mount power adapter
(input 90-254 Vac, 50-60 Hz, output
15Vdc, 1A)
NOTE: Not covered in this document is the WEBs-AX
software installation and configuration required
for a fully functioning unit. Refer to the JACE
Niagara AX Install and Startup Guide for this
information.
In addition, the installation of controller expan-
sion options are covered in separate documents.
See Related Documentation, and also the section
"About Expansion Options" on page 5.
The Content of this document equally applies to
CP-600E product.
Related Documentation
For more information on configuring and using the WEB-600E
controller, refer to the following documents:
• JACE NiagaraAX Install and Startup Guide
• JACE Data Recovery Service (SRAM Support) -
Engineering Notes
Description
INSTALLATION INSTRUCTIONS
• IO-16-H Installation and Configuration Guide
• IO-34-H Installation and Configuration Guide
• Various option card installation documents, such as:
— NPB-LON Option Install Sheet
— NPB-2X-485 Option Install Sheet
— NPB-RS232 Option Install Sheet
— NPB-GPRS Modem Option Install Sheet
— NPB-ZWAVE Option Card Install Sheet
• NiagaraAX Ndio Guide
• NiagaraAX User Guide
PREPARATION
Unpack the controller and inspect the package contents for
damaged or missing components. If damaged, notify the
appropriate carrier at once and return any damaged
components for immediate repair or replacement. See
"Returning a Defective Unit" on page 17
• Included in this Package
• Material and Tools Required
Included in this Package
Included in this package you should find the following items:
• a WEB-600E or a CP-600E controller.
• This WEB-600E and CP-600E Network Controllers, Part
Number 62-0433_A Rev 9/12
• a hardware bag containing the following items:
— One (1) grounding wire, with quick-disconnect 0.187"
female connector.
Material and Tools Required
The following supplies and tools are typically required for
installation:
• A suitable power module, as one of the following types:
— NPB-PWR-H: 24Vac or 24Vdc, in-line, DIN mount
capable, with grounding wire
— NPB-PWR-UN-H: 120–240Vac, in-line, DIN mount
capable, with grounding wire
— NPB-WPM-US: External wall mount power adapter
(input 90-254 Vac, 50-60 Hz, output 15Vdc, 1A)
NOTE: Using an NPB-PWR-H power module provides
the widest operating temperature range. See
"Environmental Requirements" on page 3.
62-0433-01
Table of Contents
loading

Summary of Contents for Honeywell WEB-600E

  • Page 1 • Various option card installation documents, such as: This document covers installation instruction of Honeywell's — NPB-LON Option Install Sheet WEB-600E controller. It assumes that you are an engineer, — NPB-2X-485 Option Install Sheet technician, or service person who is performing control —...
  • Page 2: Static Discharge Precautions

    WEB-600E AND CP-600E NETWORK CONTROLLERS • If using a NPB-PWR-H (24V) power module, either one of WARNING the following: — UL listed, Class 2, 24Vac transformer, rated at mini- • Depending on power module used, the circuit mum of 7.5VA to 20VA (approximate range of control- powering the controller is 120–240Vac at 50/60...
  • Page 3: Physical Mounting

    WEB-600E AND CP-600E NETWORK CONTROLLERS away such equipment. Instead, these products must enter the • The optional NiMH battery pack is not installed. recycling process. To properly dispose of this product, please Otherwise, the maximum ambient operating temperature take it to a local recycling center.
  • Page 4 IF INSTALLING IO MODULES AND USING THE NPB-PWR-H OR NPB-PWR-UN-H POWER SUPPLY MODULE, THE POWER SUPPLY MODULE INSTALLS AT THE END OF THE CHAIN. M33914 Fig. 1. WEB-600E controller and accessory mounting details. To mount on DIN rail: 5. Slide the accessory module along the DIN rail to con- 1.
  • Page 5: Board Layout

    Board Layout Figure 3 shows the location of LEDs, option slots, and other features of the WEB-600E controller with cover removed. For a side view of communications ports and other features, see Fig. 6.
  • Page 6 Power to the controller must be OFF when installing or removing option cards, or damage will occur! Also, you must be very careful to plug an option card into its connector properly (pins aligned). Table 1. WEB-600E Controller Option Card. Option Description Notes NPB-2X-485 Dual, optically-isolated, RS- If installed in Option slot 1, ports operate as COM3 and COM4.
  • Page 7: Installing An Option Card

    Set the battery and bracket assembly over the option card slots, with the mounting holes aligned Mounting an option card in a WEB-600E controller: with the standoffs. 1. If a station is running, stop it using the platform Applica- c.
  • Page 8: Wiring Details

    WEB-600E AND CP-600E NETWORK CONTROLLERS Table 2. Accessory Modules Compatible with the WEB-600E Controller. (Continued) Model Description Notes IO-34-H DIN-mountable, combined 34 points I/O with 24V Only one IO-34-H module per controller. isolated power module, used to provide I/O points as...
  • Page 9 EARTH GROUND NEUTRAL NOTE: THE 6-PIN CONNECTOR ON THE NPB-PWR-UN-H IS NOT USED WITH A WEB-600E SERIES CONTROLLER. THE 6-PIN CONNECTOR IS DESIGNED FOR USE WITH OTHER CONTROLLERS OR MODULES, AND MUST BE LEFT UNUSED. M33919 Fig. 5. NPB-PWR-UN-H module wiring connections.
  • Page 10: Communications Wiring

    NPB-WPM-US (WALL COM2 MOUNT AC) M33920 Fig. 6. WEB-600E controller bottom side (cover removed). ETHERNET Refer to the JACE NiagaraAX Install and Startup Guide for Two, female 10/100-Mbit Ethernet connections are provided details on changing IP address using the platform on the controller.
  • Page 11 WEB-600E AND CP-600E NETWORK CONTROLLERS Need for RS-485 Bias The controller is a serial DTE device, such that another DTE device (PC, for example) requires a “null modem” cable. If connecting to a DCE device such as a modem, use a straight- NOTE: A full discussion of communication line termina- through cable.
  • Page 12 WEB-600E AND CP-600E NETWORK CONTROLLERS PHILLIPS HEAD COVER REMOVED, SCREWS REVEALS METAL SHIELD METAL SHIELD LIFTED AWAY NPM6E BOARD METAL STANDOFFS NPM6E BOARD LIFTED AWAY JUMPER BLOCK FOR RS-485 BIASING M33921 Fig. 7. Basic stages of controller disassembly. Disassembling the controller: NOTE: Be mindful of the “side clips”...
  • Page 13: Power Up And Initial Checkout

    13. Complete WEBs-AX details on the operation of the applied. Once the controller boots, the yellow “BEAT” LED WEB-600E’s integral SRAM are in the WEB Data Recovery should start blinking, at a typical rate of 1Hz. Blinking should Service (SRAM support) - Engineering Notes document.
  • Page 14: Status Leds

    WEB-600E AND CP-600E NETWORK CONTROLLERS Serial Ports PowerMonitorService). Station alarms are generated whenever primary power is lost, or if the battery is uncharged LEDs for the two serial ports are located on the controller’s or unable to hold a sufficient charge.
  • Page 15: Battery Maintenance

    NIMH BATTERY PLUGGED INTO CONNECTOR ON CONTROLLER M33923 Fig. 9. Optional NiMH battery pack in WEB-600E controller. Battery maintenance CAUTION Battery life expectancy is a function of its discharge cycles Use only NiMH battery packs approved for use (the number of discharges and their depth) and the ambient with the WEB-600E.
  • Page 16: Non-Replaceable Parts

    New Replacement Unit wires from the installed IO modules. b. Remove the installed accessory modules, starting To replace an entire unit, order and install a new WEB-600E with the end module. controller. If the faulty controller is still in warranty, you can c.
  • Page 17: Returning A Defective Unit

    It has been tested and found to comply with replaced part. the limits for a Class A computing device pursuant to Subpart Do not return an out-of-warranty WEB-600E con- J of Part 15 of FCC Rules, which are designed to provide troller.
  • Page 18: Ce Declaration Of Conformity

    WEB-600E AND CP-600E NETWORK CONTROLLERS CE DECLARATION OF CONFORMITY Application of 2004-108-EC Council Directive: Manufacturer’s Tridium Inc. Name: Manufacturer’s 3951 Westerre Parkway, Suite 350 Address: Richmond, Virginia 23233 United States of America Manufacturer’s Steve Fey, President Representative: Tridium Inc. Product Model...
  • Page 19: Tab Mounting Dimensions

    WEB-600E AND CP-600E NETWORK CONTROLLERS TAB MOUNTING DIMENSIONS Measurements are in inches and (mm). Note that DIN mounting is recommended over tab mounting. See Fig. 1. Fig. 10. Tab mounting dimentions. 1-64 6-23/32 (171) DIA. WEB-600E 3-3/4 (95) NOTE: ELECTRONIC AND PRINTED VERSIONS OF THIS 2-1/2 DOCUMENT MAY NOT SHOW DIMENSIONS TO SCALE.
  • Page 20 WEB-600E AND CP-600E NETWORK CONTROLLERS By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’...

This manual is also suitable for:

Cp-600eWeb-600e-usaCp-600e-usa

Table of Contents