4. Troubleshooting
Protection control function
4.5 Protection control function
This Chiller unit is provided with protection control functions to release abnormal statuses before reaching alarm because
of abnormality occurrence.
Name of
protection control
Conditions for
(Compressor
frequency control)
I1 > Setting value×0.97
Overcurrent
protection
I1 > Setting value
(Unit current)
* I1: Unit current
Pd-Ps ≤ 0.3MPa
Pd-Ps ≤ 0.25MPa
Differential
Pressure Protection
* Pd: High pressure
Ps: Low pressure
Twp ≤ 2ºC
Outlet Water
Temperature
Twp ≤ 1.5ºC
Decrease
* Twp: Outlet water
Prevention
temperature (Protection)
Pd ≥ 1.84MPa
Discharge Pressure
Over-increase
Pd ≥ 1.86MPa
Prevention
*Pd: High pressure
Air-cooled systems
(Cooling only)
Suction Pressure
Ps < 0.17MPa
Decrease
Prevention
Ps < 0.13MPa
* Ps: Low pressure
Cooler inlet
refrigerant
Tr < -4ºC
temperature
* Tr: Cooler inlet
decrease
refrigerant temperature
prevention (at
Cooling operation)
Ps ≤ 0.05MPa AND
100% pressure switch for
detection ON
Frost formation
limitation
Ps ≤ 0.05MPa AND
100% pressure switch for
detection OFF
116
SMGB0082 rev.1 - 07/2015
Description of Control
Operation
Load up prohibition
Forced load down
Load down
prohibition
Forced load up
Load up prohibition
Forced load down
Load up prohibition
Forced load down
Load up prohibition
Forced load down
Load up prohibition
Forced load down
Load up prohibition
Release conditions
I1 < Setting value×0.95
I1 < Setting value×0.98
60 seconds passed and
Pd-Ps > 0.3MPa
Ps > 0.3MPa
30 seconds passed and
Twp > 2ºC
Twp > 2ºC
10 minutes have passed
or
Pd ≤ 1.76MPa
over-increase
Pd ≤ 1.84MPa → To
Control
Air-cooled systems (Cooling
only)
Low pressure
Ps < 0.19MPa
Ps < 0.15MPa
60 seconds passed
5 minutes passed OR Ps ≥
0.1MPa
Display
LCD
Segment
Current
limited
Differential
pressure
limited
Outlet water
temperature
limited
High
pressure
limited
decrease
limited
Cooler
refrigerant
temperature
limited
-
-