Fan Control - Hitachi SAMURAI Series Service Manual

Air cooled water chillers and air to water heat pump
Hide thumbs Also See for SAMURAI Series:
Table of Contents
2. Control Functions
Control of the cooling cycle

2.2.2 Fan Control

1 Cooling operation
This product uses fan revolution control by means of inverter to control high pressure.
The target pressure is set from outdoor temperature, and the variation of the number of revolutions is managed by PI
control. There is no switching of the number of units.

Image diagram of fan control
Silence priority mode
Night shift
(*)
Outdoor temperature (ºC)
(*) In case of class 40HP
2 Heating operation
Low pressure is controller by using fan revolution control by means of inverter.
The variation of the number of revolutions is managed by PI control, to achieve a target low pressure of 0.5 MPa. There 
is no switching of the number of units. The usage frequency range is the same as in cooling operation. Also, the following
control is enabled to respond to sudden changes.
Low pressure over-increase prevention control
With low pressure ≤ 0.3 MPa, +10 Hz output
45
SMGB0082 rev.1 - 07/2015
Max Frequency
RCME-40AH1
52Hz
RCME-50AH1
57Hz
RCME-60AH1
60Hz
RCME-70AH1
60Hz
Standard mode
High pressure
The fan speeds down when the high
pressure is about to fall under the
target value
Fan frequency
Time
The fan speeds up when the high
pressure is about to exceed the
target value
Min Frequency
7Hz
7Hz
7Hz
7Hz
• Operation at 7 Hz during 15 seconds after fan 
startup, then shift to PI control afterwards.
• The calculation period of PI control is 10
seconds.
• The target high pressure is set according to
the image beside, but the high-low pressure
difference required by the compressor is set
with preference.
• Calculations are not performed when the target
value for high pressure lies within +0/-0.1 MPa. 
• The following controls are enabled to respond
to sudden changes.
High pressure over-increase prevention
• With high pressure ≥ 1.3 MPa, + 10 Hz output
• With high pressure ≥ 1.6 MPa, maximum 
frequency output
• With detection temperature of liquid
temperature thermistor ≥ 56ºC, maximum 
frequency output
High pressure over-decrease prevention
• With high pressure ≤ 0.3MPa, - 10 Hz output
• With high pressure ≤ 0.25 MPa, minimum 
frequency output
2