FINE TUNING SENSORLESS VECTOR

In most cases fine tuning is not required with the standard motor constants that are supplied when selecting the correct
motor constant profile in parameter H003. Before making adjustments, try selecting a motor constant profile (1) smaller
or larger than the combined connected motors in kW's in parameter H003.
Status
Momentary speed variation is negative
Powering
Momentary speed variation is positive
Regeneration
Motor generates an impact at start
Starting
Decelerating
Low Frequency
Operation
Symptom
Torque is insufficient at
low speed (~ few Hz)
Motor runs backward for short
moment at start
Motor runs unsteadily
Motor rotation is unstable
Adjustment Method
Increase the motor constant R2 step by step
from the set value up to 1.2 times of the set
value
Decrease the motor constant R2 step by step
from the set value up to 0.8 times of the set
value
Increase the motor constant R1 step by step
from the set value up to 1.2 times of the set
value
Increase the motor constant Io step by step
from the set value up to 1.2 times of the set
value
Reduce the motor constant J from the set value
Decrease the speed response factor
Set 01 (enable) on reverse run protection
function (b046)
Decrease the speed response factor
Decrease the motor constant J from the set
value
Increase the motor constant J from the set
value
Increase the speed response factor
Adjustment
Parameter
H021
H021
H020
H023
H024
H005
b046
H005
H024
H024
H005
Page 21