Motor Brake Parameters; Vfd Control Modes - Hitachi WJ200 Instruction Manual

Hide thumbs Also See for WJ200:
Table of Contents

MOTOR BRAKE PARAMETERS

The motor brake parameters ca be adjusted based on the application needs.
Brake wait time for release – After the Brake Release Frequency Setting is reached, the inverter waits for the braking wait time
(b121)
Brake wait time for acceleration – The inverter waits for the Brake Wait Time for Acceleration (b122), and then starts accelerating
the motor up to the set acceleration frequency.
Brake wait time for stopping – Once the brake release signal is turned off, the inverter waits for the Brake Wait Time for Stopping
(b123), and then starts decelerating the motor down to 0Hz.
Function
Brake release frequency
Brake set frequency
Brake wait time for release
Brake wait time for acceleration
Brake wait time for stopping
AL output relay output function

VFD CONTROL MODES

The VFD control mode is pre-set from Detroit Hoist and should not be changed unless directed to by a Detroit Hoist employee.
Constant torque is typically used for all bridge motions and load brake hoist motions. Constant torque can be configured for manual
torque boost or automatic torque boost. The default from Detroit Hoist is manual torque boost. Automatic torque boost uses the
manual torque boost parameters as a start value and then adjusts based on the voltage compensation gain and slip compensation
gain.
Sensorless vector is typically used for hoist trolleys to provide higher torque but can also be used for all motions if configured
correctly.
Function
Supported VFD Control Modes
Parameter
b125
b127
b121
b122
b123
C026
Parameter
A044
Value
2.50 Hz
2.50 Hz
0.00 s
0.00 s
0.00 s
19: BRK
Value
00 = Constant Torque
03 = Sensorless Vector
Page 17