Measured Circuit - Panasonic KW2M-A User Manual

Eco power meter
Hide thumbs Also See for KW2M-A:
Table of Contents
◆Applicable wire (a crimp-type terminal is recommended.)
・Stripping length: 7 to 8mm
・Power supply/Measured voltage
Screw type: M3
Tightening torque: 0.5 to 0.6N・m
Sectional area: single /stranded wire 0.13 to 6mm
・for 2pcs.
single/stranded wire 2pcs.×0.5 to 2.5mm
・Measured current (CT input)
Screw size: Push-in type
Sectional area: single /stranded wire 0.13 to 1.5mm
*Use a wire suitable for the current to be measured.
・RS485 communication
Screw size: Push-in type
Sectional area: single /stranded wire 0.13 to 1.5mm
*Use a shielded wire for RS485 communication.
・Output/Input
Screw size: Push-in type
Sectional area: single /stranded wire 0.13 to 1.5mm

4.2 Measured circuit

・It is possible to use two different measurement voltages (2 circuits of same system with 1 unit).
・Each unit (main unit, expansion unit (power measurement, power measurement + pulse output)) can
measure 2 circuits of a single-phase two-wire system, and 1 circuit of a single-phase three-wire system
or three-phase three-wire system. Each unit can be used with a different phase and wire system.
However, check the wiring carefully.
・It is not possible to take measurement with only the expansion unit. Every expansion unit must be
connected to a main unit.
Up to 3 expansion units can be connected to 1 main unit.
*Power source system
・The power source system is the electrical power system from one power source (normally one
transformer).
・KW2M-A can measure 1-system max. 24-circuit of 1P2W system and 1-system max. 8-circuit of 1P3W
and 3P3W system by connecting a main unit and expansion units.
・In order to measure several systems, it is necessary to use one main unit for each system.
KW2M-A/X User's Manual
2
(AWG26 to12)
2
(AWG20 to 12)
2
(AWG24 to16)
2
(AWG24 to16)
2
(AWG24 to16)