4. Electrical work
2-zone temperature control
Control option A
This option features the main controller, the Mitsubishi Electric wireless remote
controller and a locally supplied thermostat.
The wireless remote controller is used to monitor the Zone1 room temperature and the
thermostat is used to monitor the Zone2 room temperature.
The thermostat can be also allocated to Zone1 and the wireless remote controller to
Zone2.
The wireless remote controller can be also used to make changes to the space heating
settings, boost DHW (*1) and switch to holiday mode without having to use the main
controller.
If more than one wireless remote controller is used, the last temperature setting
adjustment/demand will be applied to ALL rooms in same zone.
Wire the wireless receiver to FTC4 (Master) referring to the wireless remote controller
instruction manual. Turn DIP SW1-8 to ON. Before operation configure the wireless
remote controller to transmit and receive data referring to the wireless remote control-
ler installation manual.)
The thermostat is used to set the maximum temperature for heating Zone2 room.
The thermostat is wired to IN6 on FTC4 (Master). (If the thermostat is allocated to
Zone1, it is wired to IN1 on TBI.1.) (Refer to 4.5.)
Control option B
This option features the main controller, the Mitsubishi Electric thermistor and a locally
supplied thermostat that are wired to FTC4 (Master).
The thermistor is used to monitor the Zone1 room temperature and the thermostat is
used to control the Zone2 room temperature.
The thermostat can be also allocated to Zone1 and the thermistor to Zone2.
The thermistor can not make any changes in control operation. Any changes to DHW
(*1) must be made using the main controller mounted on the FTC4 (Master).
Wire the thermistor to the TH1 connector on FTC4 (Master).
The number of room temperature thermistors that can be connected to FTC4 (Master) is
always one.
The thermostat is used to set the maximum temperature for heating Zone2 room.
The thermostat is wired to IN6 on FTC4 (Master). (If the thermostat is allocated to
Zone1, wire it to IN1 on TBI.1.) (Refer to 4.5)
Control option C
This option features the main controller (with in-built thermistor) that is removed from
the FTC4 (Master) to monitor the Zone1 room temperature and a locally supplied ther-
mostat to monitor the Zone2 room temperature.
The thermostat can be also allocated to Zone1 and the thermistor to Zone2.
A thermistor built into the main controller can be used for monitoring the room tempera-
ture for Auto Adaptation function whilst keeping all its features of the main controller
available.
The main controller and FTC4 (Master) are connected by a 2-core, 0.3 mm², non-polar
cable (field supply) with a maximum length of 500 m.
To use the sensor in the main controller the main controller should be detached from
the FTC4 (Master). Otherwise it will detect the temperature of the FTC4 (Master) in-
stead of room temperature. This will affect the output of the space heating.
The thermostat is used to set the maximum temperature for heating Zone2 room.
The thermostat is wired to IN6 on FTC4 (Master). (If the thermostat is allocated to
Zone1, wire it to IN1 on TBI.1.) (Refer to 4.5.)
Control option D
This option features the locally supplied thermostats wired to FTC4 (Master). The ther-
mostats are individually allocated to Zone1 and Zone2. The thermostats are used to
set each maximum temperature for heating Zone1 and Zone2 rooms. Any changes to
DHW (*1) must be made using the main controller mounted on the FTC4 (Master).
The thermostat for Zone1 is wired to IN1 in TBI.1 on FTC4 (Master).
The thermostat for Zone2 is wired to IN6 in TBI.1 on FTC4 (Master).
*1 If applicable
*2 For the options above, the sensor types can be exchanged between Zone1 and Zone2. (e.g. Wireless remote controller in Zone1 and Room temp thermostat in Zone2 can
be changed to Room temp thermostat and wireless remote controller, respectively).
Also, the wireless remote controller can be used to function as a thermostat as well, if required.
Wireless receiver
(option)
FTC4
(Master)
Outdoor unit
Main controller
Zone1: Room temp. control (Auto adaptation)
Zone2: Compensation curve or flow temp. control
FTC4
(Master)
Outdoor unit
Main controller
Zone1: Room temp. control (Auto adaptation)
Zone2: Compensation curve or flow temp. control
FTC4
(Master)
Outdoor unit
Zone1: Room temp. control (Auto adaptation)
Zone2: Compensation curve or flow temp. control
FTC4
(Master)
Main controller
Outdoor unit
Zone1, Zone2: Compensation curve or flow temp. control
Wireless remote controller
(option)
20.0°C
Max. 8
20.0°C
Zone1
20.0°C
Room temperature
thermostat
(field supply)
Zone2
Room temperature
thermistor (option)
Zone1
20.0°C
Room temperature
thermostat
(field supply)
Zone2
Main controller
(remote position)
Zone1
20.0°C
Room temperature
thermostat
(field supply)
Zone2
Room temperature
thermostat
(field supply)
Zone1
20.0°C
Room temperature
thermostat
(field supply)
Zone2
1