Honeywell Fire-Lite Alarms D350RPL Installation And Maintenance Instructions Manual

Intelligent photoelectronic duct smoke detector with extended air speed range
D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Before installing detectors, please thoroughly read the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications, which
provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are avail-
able from NEMA (National Electrical Manufacturers Association, 2101 L Street NW, Washington, DC 20037). NFPA Standards 72 and
90A should also be referenced for detailed information.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. The detector should be cleaned
at least once a year.
GENERAL DESCRIPTION
An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct system is distributed
to the entire building. Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in the duct.
The D350RPL air duct smoke detector is a photoelectric detector. This smoke detection method combines with an efficient housing
design that samples air passing through a duct and allows detection of a developing hazardous condition. When sufficient smoke is
sensed, an alarm signal is initiated at the fire control panel monitoring the detector, and appropriate action can be taken to shut off
fans, blowers and change over air handling systems, etc. This can prevent the distribution or it can isolate toxic smoke and fire gases
throughout the areas served by the duct system.
Two LEDs on each detector may illuminate, if programmed by the system control panel, to provide a local alarm indication. There
is also a remote alarm output for use with auxiliary devices. The D350RPL has remote test capability with the RTS451/RTS451KEY
Remote Test Station.
The D350RPL incorporates a cover tamper feature. When the cover is removed for more than 20 minutes, the unit loses communication
at the panel, a trouble is indicated at the panel and the alarm relay switches states thereby shutting down fans, dampers and blowers.
In the case when the sensor is removed or when there is no power to the unit, only a trouble is indicated at the panel (alarm relay
does not work any longer).
CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT
The D350RPL Duct Smoke Detector consists of the following items (See Figure 1.):
Figure 1. Exploded view of duct smoke detector components:
FOAM GASKETS
SAMPLING
TUBE
DETECTOR
BOARD
DETECTOR
COVER
NOTE: For ducts over 1
1
feet, longer sampling tubes must be ordered to complete the installation. They must be the correct length for the
2
width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for different duct widths.
F300-28-00
WITH EXTENDED AIR SPEED RANGE
CONDUIT
HOLES
SAMPLING
TUBE
FILTERS
COVER MOUNTING SCREWS
Contents Of The Duct Smoke Detector
1. Complete duct smoke detector assembly
with sensor
2. Two #10 x 1
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws for
the sampling tube and optional exhaust
tube extension
DETECTOR
8. One sampling tube end cap
HOUSING
9. One plastic sampling tube
TERMINAL
10. One #8 self-tapping screw for plastic sam-
STRIP
pling tube
NOTE: A detector sensor board DOES NOT need
POWER
to be ordered separately.
BOARD
H0129-00
1
Fire•Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472, 203-484-7161
1
˝ sheet metal mounting screws
4
I56-1974-006R
Table of Contents
loading

Summary of Contents for Honeywell Fire-Lite Alarms D350RPL

  • Page 1: Install The Sampling Tube For Ducts Less Than

    D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installing detectors, please thoroughly read the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are avail- able from NEMA (National Electrical Manufacturers Association, 2101 L Street NW, Washington, DC 20037).
  • Page 2: Table Of Contents

    WARNING LIMITATIONS OF DUCT DETECTORS WARNING The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a substitute for early warning in a building’s regular fire detection system.
  • Page 3: Step 3. Secure The Detector Housing To The Duct

    [3] Secure The Detector Housing To The Duct Slide the foam gaskets over the tube bushings as shown in Figure 3. Use the two 1 ⁄ ˝ long sheet metal screws to screw the detector housing to the duct. CAUTION: Do not overtighten the screws. Table 1.
  • Page 4: Installation For Ducts More Than 8 Feet (2.4M) Wide

    [4.2] Installation For Ducts More Than 8 Feet (2.4m) Wide NOTE: To install sampling tubes in ducts more than 8 feet (2.4m) wide, work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet (2.4m) is accomplished by using the ST-10 sampling tube. If the tube is shorter than the width of the air duct, install the end cap into the sampling tube as shown in Figure 4 and support the end opposite the duct smoke detector.
  • Page 5: Step 7. Perform Detector Check

    Panels offer different feature sets across different panel models. As a result, certain features of the D350RPL may be available on some control panels, but not on others. The possible features available in the D350RPL, if supported by the control panel are: 1.
  • Page 6 [9.1.5] Filter Replacement The filters do not substantially affect smoke performance even when up to 90% of the filter is clogged. Quarterly visual inspection usu- ally suffices to determine whether the filters should be replaced because only a high percentage of contamination affects performance. If further testing is required, compare differential pressure readings with and without the filters installed.
  • Page 7 [9.2.2] Alarm Tests [9.2.2.1] M02-04-00 Magnet Test 1. Place the painted surface of the magnet onto the TEST locator on the bottom of the detector housing (Figure 13). 2. Verify system control panel alarm status and control panel execution of all intended auxiliary functions (i.e. fan shutdown, damper control, etc.) 3.
  • Page 8 [10] Board Replacement Contact Ratings [10.1] Sensor Board Replacement Alarm auxiliary contacts* (DPDT) 10 A @ 30 VDC 1. Remove the two sensor board mounting screws. 10 A @ 277 VAC (.75 power factor) 2. Pull gently on the board to remove it. 3.

Table of Contents