7-5. Fresh air control

The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as below.

7-6. Compressor preheating

By preheating the compressor, warm airflow is quickly discharged when the operation is started.
• Models: AOYG18KBTB, AOYG22KBTB, and AOYG24KBTB
– Triggering condition
• 30 minutes after compressor stopped.
• Outdoor unit heat exchanger temperature (Tn)
When the jumper wire (JM2) is disconnected:
• Models: AOYG30KBTB, AOYG36KBTB, and AOYG45KBTB
– Triggering condition 1
• Outdoor temperature ≤ 20°C
When outdoor temperature reaches 26°C, compressor preheating stops.
• 30 minutes after compressor stopped
– Triggering condition 2
7-5. Fresh air control
Operation
Fan motor
(Indoor unit)
Stop
Operation
Fan motor
(for Fresh Air)
Stop
-2°C
5°C
Tn
Off
0°C
On
Tn: Outdoor unit heat exchanger temp.
Tn
Tn
Off
-4°C
On
Tn
Tn
Off
7°C
On
Tn
2°C