E: 12. Wired Remote Controller Communication Error (Indoor Unit) - Fujitsu ABYG18KRTA Service Manual

Ceiling type air conditioner
Hide thumbs Also See for ABYG18KRTA:
Table of Contents
2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Wired remote
Indicator
controller
Indoor unit
Detective actuator
Wired remote control
Forecast of cause
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
Check Point 1-2 : Check Wired remote controller
and main PCB
Check voltage at CN14 of main PCB
(terminal 1—3, terminal 1—2). (Power
supply to the remote controller)
Upon correcting the removed connec-
tor or mis-wiring, reset the power.
Check Point 2 : Wire installation wrong remote controller group setting
Wrong wire connection in remote controller group (Please refer to the installation manual)
The number of connecting indoor unit and remote controller in one remote controller group
were less than 32 units.
Check Point 2-1 : Check Indoor unit main PCB
Check if main PCB damage
Change main PCB and check the error after setting remote controller address

2-3. E: 12. Wired remote controller communication error (Indoor unit)

Error code
Main PCB
End
End
When the indoor unit cannot receive the signal from
Wired remote controller more than 1 minute during
normal operation.
Terminal connection abnormal
Wired remote control failure
Main PCB failure
If it is DC 12 V, remote controller is failure.
(Main PCB is normal)
Replace remote control
If it is DC 0 V, main PCB is failure. (Check
remote controller once again)
Replace main PCB
- (03-7) -
E: 12
2. Troubleshooting with error code
Table of Contents
loading