E: 33. Indoor Unit Motor Electricity Consumption Detection Error (Indoor Unit) - Fujitsu ABYG18KRTA Service Manual

Ceiling type air conditioner
Hide thumbs Also See for ABYG18KRTA:
Table of Contents
2-8. E: 33. Indoor unit motor electricity consumption detection
error (Indoor unit)
Wired remote
Indicator
controller
Indoor unit motor electricity
Detective actuator
consumption detection
Forecast of cause
Check point 1. Check the rotation of fan
Rotate the fan by hand when the operation is off. (Check if fan is caught, drop off or locked motor)
→ If fan or bearing is abnormal, replace it.
Check point 2. Check ambient temperature around the motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat.)
→ Upon the temperature coming down, restart operation.
Check point 3. Check indoor unit fan motor
Check indoor unit fan motor. (Refer to indoor unit fan motor in
03-46.)
→ If indoor unit fan motor is abnormal, replace it.
Check point 4. Replace main PCB
If check point 1-3 does not improve the symptom, change main PCB.

2-8. E: 33. Indoor unit motor electricity consumption detection error (Indoor unit)

Error code
End
When the voltage value or the current value of the motor
go beyond the limits
Fan motor failure
Main PCB failure
"Service parts information"
- (03-12) -
E: 33
on page
2. Troubleshooting with error code