Honeywell NOTIFIER RP-2002C Instruction Manual page 144

Agent release panel
Table of Contents
NFPA Standard-Specific Requirements
NFPA 72 Remote Station Protective Signaling System
Notes:
1.
Cut Jumper JP30 on the RP-2002 main circuit board to supervise placement of the 4XTM
module.
2.
Refer to "4XTM Municipal Box Transmitter Option Module" on page 33 for detailed
information.
Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.
Figure C.3 Remote Station Connection Using 4XTM Module
144
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver Model RS82.
RP-2002 Series Manual — P/N 53039:E6 1/26/2017
NFPA 72 Auxiliary Fire Alarm System
Polarity Shown is
Normal Standby
+
-
+
Power limited
-
(Dummy load with a 4.7KΩ, ¼ watt resistor
when no connection is made)
4XTM Transmitter Module