Section 10: Addressable Beam Detectors; Description; Installation And Wiring; 1: Setting An Slc Address For A Beam Detector - Honeywell Fire-Lite Alarms MS-9200 Wiring Manual

Intelligent control panel, slc
Table of Contents

10.1 Description

The BEAM355, BEAM355S, and OSI-RI-FL are intelligent, addressable projected beam smoke detectors, designed for protecting
open areas with high and sloping ceilings and wide-open areas, where spot type smoke detectors are difficult to install and maintain. The
BEAM355S has an integral sensitivity test feature that consists of a test filter attached to a servomotor inside the detector optics.
NOTE: This section provides basic wiring and addressing information For critical information on device installation, operation and
alignment, refer to the Installation Instructions provided with these devices.

10.2 Installation and Wiring

10.2.1 Setting an SLC Address for a Beam Detector
Each beam detector is factory preset with an address of "00." To set an SLC address, use a common screwdriver to adjust the address
rotary code switches on the detector to the desired address (refer to 5.2.1"Setting an SLC address for a Single Point Module" on
page 33).
10.2.2 Wiring a Beam Detector
Typical wiring of a BEAM355 beam detector connected to an SLC is illustrated in the figure below.
Alignment Mirror
Alignment Gunsight
Alignment Position
Indicator
Optics Lock-down
Screws
Class X Isolator Shunts
Test Option (-)
Test Option (+)
60

Section 10: Addressable Beam Detectors

not used
not used
RTS151/KEY& RTS-451/KEY
Connections
Figure 10.1 BEAM355 Beam Detector Terminal Block Wiring
Digital Signal
Strength Readout
Horizontal Adjustment
Alignment Switch
Sensitivity Switch
Test Switch
Vertical Adjustment
Reset Switch
SLC (-) to next device
SLC (+) to next device
SLC (-) from panel or previous device
SLC (+) from panel or previous device
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019