Precautions When Charging Refrigerant; To Determine The Additional Refrigerant Amount; To Determine The Complete Recharge Amount; To Charge Additional Refrigerant - Daikin Altherma EVLQ05+08CA Installer's Reference Manual

Hybrid heat pump
Hide thumbs Also See for Altherma EVLQ05+08CA:
Table of Contents
7
|
Installation

7.9.2 Precautions when charging refrigerant

7.9.3 To determine the additional refrigerant amount

7.9.4 To determine the complete recharge amount

7.9.5 To charge additional refrigerant

7.9.6 To fix the fluorinated greenhouse gases label

Installer reference guide
80
INFORMATION
Also read the precautions and requirements in the following chapters:
General safety precautions
Preparation
If the total liquid piping
length is...
≤10 m
>10 m
INFORMATION
Piping length is the one-way length of liquid piping.
WARNING
ONLY use R410A as refrigerant. Other substances may cause explosions and
accidents.
R410A contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 2087.5. Do NOT vent these gases into the atmosphere.
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
CAUTION
To avoid compressor breakdown, do NOT charge more than the specified amount of
refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant piping is
connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to the service port.
2 Charge the additional refrigerant amount.
3 Open the gas stop valve.
If pump down is needed in case of dismantling or relocating the system, see
4
"14.2 To pump
down" [
1 Fill in the label as follows:
Do NOT add additional refrigerant.
R=(total length (m) of liquid piping⁠ – ⁠ 1 0 m)×0.020
R=Additional charge (kg) (rounded in units of
0.01 kg)
 220] for more details.
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Then...
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10